RecordWell Data

Woodcreek Apartments

3113 15TH ST, Kenosha, WI 53144 · Kenosha County

16cited violations
2serious tier
5inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Kenosha County Division of Health
License / ID
NFRY-8XQ4HC
Status
Permitted
Phone
(262) 552-8365
Official record
Kenosha County Division of Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026110
2025251
20242101

Inspections

  1. Jul 21, 2026 Routine · 1 non-critical
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The turnover rate is approximately 6.77 hours

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate so it is less than 6 hours.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

  2. Aug 19, 2025 Routine · 1 non-critical
    • Not serious Non-critical

      FIRST AID KIT ITEMS

      The first aid kit is present but missing unexpired eye wash solution and surgical gloves. I informed the PIC of this, and they said they would have them replaced.

      Correction: Replace the missing items in the first aid kit.

      Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS

  3. May 27, 2025 Routine · 1 critical, 3 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Observed 1 of 3 weirs is missing. Person In Charge is aware of the issue and stated they ordered another.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat Corrected on site

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      Observed the float in the flowmeter is not being maintained in operating condition. Observed the float is stuck and unable to get flow rate. PIC is currently trying fix the float in operating condition. PIC was able to fix float. Able to get flowrate.

      Correction: Adjust or repair the [ ].

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Corrected on site

      POOL RULES SIGNAGE-SHOWER

      Observed Pool rules missing rule: Shower immediately before entering the pool and after use of a steam room, sauna, or toilet facilities. Establishment had half of the rule. Informed PIC and PIC got a new updated sign posted.

      Correction: Include pool rule on sign: Shower immediately before entering the pool and after use of a steam room, sauna, or toilet facilities.

      Code ATCP 76.29(1)(b)1.c. - SHOWER

    • Serious Critical Corrected on site

      WATER SUPPLY PROTECTION

      Observed approved backflow or backsiphonage protection does not exist between potable water supply inlet and the overflow point of pool, makeup tank, surge tank or slurry tank and another approved device does not exist. Observed hose connection to hose bib on water supply pipe in pump room without a backflow preventor device. Informed PIC and PIC got a backflow preventor device on the hose bib.

      Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool, makeup tank, surge tank, solution tank, or slurry tank.

      Code ATCP 76.19(1) - PROTECTION

  4. Jun 4, 2024 Re-inspection · 4 non-critical, 4 repeat
    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. Weir doors are missing discussed with staff that each skimmer needs a weir door or floating weir .

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      INLETS CHECKED AND ADJUSTED

      Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are all pointed towards the pool. Discussed with staff that inlets need to face all the same direction to create uniform distrubution.

      Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.

      Code ATCP 76.11(2)(c) - INLETS POSITIONED

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition. The plunger in flowmeter is stuck and is not moving. Discussed with staff on fixing or replacieng the plunger for the flowmeter to calculate the flowrate .

      Correction: Adjust or repair the the plunger in the flowmeter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      EMERGENCY BLANKETS

      Two emergency blankets in good condition are not available in the pool area. Disucssed with staff that the pool needs two emgergency blankets.

      Correction: Provide two emergency blankets in good condition in the pool area.

      Code ATCP 76.27(3) - EMERGENCY BLANKETS

  5. May 29, 2024 Routine · 1 critical, 5 non-critical
    • Not serious Non-critical Corrected on site

      SKIMMER POOL RECIRCULATION FLOW

      Proportion of water recirculating from skimmer and main drain are both fully opened. Disucssed with staff that main drain valve needs to be slightly opened like a third to create the 20% and skimmer valve to be fully opened to create the 80 percent. Staff corrected valve positions.

      Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. Weir doors are missing discussed with staff that each skimmer needs a weir door or floating weir .

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      INLETS CHECKED AND ADJUSTED

      Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are all pointed towards the pool. Discussed with staff that inlets need to face all the same direction to create uniform distrubution.

      Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.

      Code ATCP 76.11(2)(c) - INLETS POSITIONED

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition. The plunger in flowmeter is stuck and is not moving. Discussed with staff on fixing or replacieng the plunger for the flowmeter to calculate the flowrate .

      Correction: Adjust or repair the the plunger in the flowmeter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      EMERGENCY BLANKETS

      Two emergency blankets in good condition are not available in the pool area. Disucssed with staff that the pool needs two emgergency blankets.

      Correction: Provide two emergency blankets in good condition in the pool area.

      Code ATCP 76.27(3) - EMERGENCY BLANKETS

    • Serious Critical

      RESCUE EQUIPMENT GOOD REPAIR

      The rescue equipment is not in good repair. Shepherd's crook is missing the crook part. Is dicussed with staff on repairing or replacing shepherd's crook.

      Correction: Maintain all rescue equipment in good repair.

      Code ATCP 76.26(1)(a)1. - RESCUE EQPT GOOD REPAIR

Source: Kenosha County Division of Health. History last read Oct 11, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.