Woodcreek Apartments
3113 15TH ST, Kenosha, WI 53144 · Kenosha County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Kenosha County Division of Health
- License / ID
- NFRY-8XQ4HC
- Status
- Permitted
- Phone
- (262) 552-8365
- Official record
- Kenosha County Division of Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 1 | 0 |
| 2025 | 2 | 5 | 1 |
| 2024 | 2 | 10 | 1 |
Inspections
-
Jul 21, 2026 Routine · 1 non-critical
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The turnover rate is approximately 6.77 hours
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate so it is less than 6 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
-
Aug 19, 2025 Routine · 1 non-critical
-
Not serious
Non-critical
FIRST AID KIT ITEMS
The first aid kit is present but missing unexpired eye wash solution and surgical gloves. I informed the PIC of this, and they said they would have them replaced.
Correction: Replace the missing items in the first aid kit.
Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS
-
Not serious
Non-critical
-
May 27, 2025 Routine · 1 critical, 3 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Observed 1 of 3 weirs is missing. Person In Charge is aware of the issue and stated they ordered another.
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
Corrected on site
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
Observed the float in the flowmeter is not being maintained in operating condition. Observed the float is stuck and unable to get flow rate. PIC is currently trying fix the float in operating condition. PIC was able to fix float. Able to get flowrate.
Correction: Adjust or repair the [ ].
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Corrected on site
POOL RULES SIGNAGE-SHOWER
Observed Pool rules missing rule: Shower immediately before entering the pool and after use of a steam room, sauna, or toilet facilities. Establishment had half of the rule. Informed PIC and PIC got a new updated sign posted.
Correction: Include pool rule on sign: Shower immediately before entering the pool and after use of a steam room, sauna, or toilet facilities.
Code ATCP 76.29(1)(b)1.c. - SHOWER
-
Serious
Critical
Corrected on site
WATER SUPPLY PROTECTION
Observed approved backflow or backsiphonage protection does not exist between potable water supply inlet and the overflow point of pool, makeup tank, surge tank or slurry tank and another approved device does not exist. Observed hose connection to hose bib on water supply pipe in pump room without a backflow preventor device. Informed PIC and PIC got a backflow preventor device on the hose bib.
Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool, makeup tank, surge tank, solution tank, or slurry tank.
Code ATCP 76.19(1) - PROTECTION
-
Not serious
Non-critical
Repeat
-
Jun 4, 2024 Re-inspection · 4 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. Weir doors are missing discussed with staff that each skimmer needs a weir door or floating weir .
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
Repeat
INLETS CHECKED AND ADJUSTED
Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are all pointed towards the pool. Discussed with staff that inlets need to face all the same direction to create uniform distrubution.
Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.
Code ATCP 76.11(2)(c) - INLETS POSITIONED
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. The plunger in flowmeter is stuck and is not moving. Discussed with staff on fixing or replacieng the plunger for the flowmeter to calculate the flowrate .
Correction: Adjust or repair the the plunger in the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area. Disucssed with staff that the pool needs two emgergency blankets.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
Repeat
-
May 29, 2024 Routine · 1 critical, 5 non-critical
-
Not serious
Non-critical
Corrected on site
SKIMMER POOL RECIRCULATION FLOW
Proportion of water recirculating from skimmer and main drain are both fully opened. Disucssed with staff that main drain valve needs to be slightly opened like a third to create the 20% and skimmer valve to be fully opened to create the 80 percent. Staff corrected valve positions.
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmers not repaired or replaced as needed. Weir doors are missing discussed with staff that each skimmer needs a weir door or floating weir .
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
INLETS CHECKED AND ADJUSTED
Inlets have not been checked and adjusted to ensure a uniform distribution pattern and effective skimming. Inlets are all pointed towards the pool. Discussed with staff that inlets need to face all the same direction to create uniform distrubution.
Correction: Check and adjust inlets to ensure a uniform distribution pattern and effective skimming as needed.
Code ATCP 76.11(2)(c) - INLETS POSITIONED
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. The plunger in flowmeter is stuck and is not moving. Discussed with staff on fixing or replacieng the plunger for the flowmeter to calculate the flowrate .
Correction: Adjust or repair the the plunger in the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area. Disucssed with staff that the pool needs two emgergency blankets.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Serious
Critical
RESCUE EQUIPMENT GOOD REPAIR
The rescue equipment is not in good repair. Shepherd's crook is missing the crook part. Is dicussed with staff on repairing or replacing shepherd's crook.
Correction: Maintain all rescue equipment in good repair.
Code ATCP 76.26(1)(a)1. - RESCUE EQPT GOOD REPAIR
-
Not serious
Non-critical
Corrected on site
Source: Kenosha County Division of Health. History last read Oct 11, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.