Inspections

  1. Feb 13, 2026 Routine · 1 non-critical
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Turnover time was 6.25 hours.

      Correction: Adjust equipment to operate at a proper turnover rate; turnover rate for pools shall be 6.0 hours or less.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

  2. Mar 13, 2025 Routine · 2 non-critical, 1 repeat
    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

  3. Feb 27, 2024 Routine · 1 critical, 3 non-critical
    • Not serious Non-critical

      INTERLOCK LOG-MADE AVAILABLE

      Log of interlock testing not made available to the department or its agent upon request.

      Correction: Make interlock test log available to the department or its agent upon request.

      Code ATCP 76.13 (1)(c)4.b - INTERLOCK LOG AVAILABLE

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments. Complete Interlock testing form provided & start logging monthly test results on monthly testing logs.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE