Lighthouse Inn Pool
1515 MEMORIAL DR, Two Rivers, WI 54241 · Manitowoc County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Manitowoc County Health Department
- License / ID
- HSAT-7QXH6F
- Status
- Permitted
- Phone
- (920) 793-4524
- Official record
- Manitowoc County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 1 | 0 |
| 2025 | 1 | 2 | 0 |
| 2024 | 1 | 4 | 1 |
Inspections
-
Feb 13, 2026 Routine · 1 non-critical
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Turnover time was 6.25 hours.
Correction: Adjust equipment to operate at a proper turnover rate; turnover rate for pools shall be 6.0 hours or less.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
-
Mar 13, 2025 Routine · 2 non-critical, 1 repeat
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
-
Feb 27, 2024 Routine · 1 critical, 3 non-critical
-
Not serious
Non-critical
INTERLOCK LOG-MADE AVAILABLE
Log of interlock testing not made available to the department or its agent upon request.
Correction: Make interlock test log available to the department or its agent upon request.
Code ATCP 76.13 (1)(c)4.b - INTERLOCK LOG AVAILABLE
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments. Complete Interlock testing form provided & start logging monthly test results on monthly testing logs.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Source: Manitowoc County Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.