RecordWell Data

Lincoln High School Pool

1433 S 8TH, Manitowoc, WI 54221 · Manitowoc County

28cited violations
11serious tier
5inspections

Establishment

Type
Pool / recreational water (Pool - Moderate)
Inspected by
Manitowoc County Health Department
License / ID
HSAT-7QWCQ8
Status
Permitted
Phone
(920) 663-9600
Official record
Manitowoc County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026242
20252147
20241102

Inspections

  1. Aug 24, 2026 Admin Follow Up · 1 critical, 1 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower, toilet and dressing facilities are not maintained in good repair. The automatic handwash sinks do not stay on for a minimum of 15 seconds when activated in the men's locker room.

      Correction: Maintain the shower, toilet and dressing facilities in good repair. Repair/adjust the handwash sinks.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Serious Critical Repeat

      Modification(s) made but no DSPS Approval available for them.

      The operator modified a pool and did not submit pool construction plans to DSPS for review and approval. The chlorine erosion feeder was replaced with a liquid chlorine system without plan review and approval from DSPS.

      Correction: Have WI-licensed architect or engineer submit pool construction (modification) plans to DSPS and obtain approval from DSPS for the construction of the pool. Documenation of plan submittal to DSPS must be provided to MCHD by June 1, 2026 to avoid further action.

      Code ATCP 76.04 (2) - PLANS SUBMITTED TO DSPS FOR MODIFICATION, A

  2. Apr 21, 2026 Routine · 1 critical, 1 non-critical
    • Not serious Non-critical

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower, toilet and dressing facilities are not maintained in good repair. The automatic handwash sinks do not stay on for a minimum of 15 seconds when activated in the men's locker room.

      Correction: Maintain the shower, toilet and dressing facilities in good repair. Repair/adjust the handwash sinks.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Serious Critical

      Modification(s) made but no DSPS Approval available for them.

      The operator modified a pool and did not submit pool construction plans to DSPS for review and approval. The chlorine erosion feeder was replaced with a liquid chlorine system without plan review and approval from DSPS.

      Correction: Have WI-licensed architect or engineer submit pool construction (modification) plans to DSPS and obtain approval from DSPS for the construction of the pool. Documenation of plan submittal to DSPS must be provided to MCHD by June 1, 2026 to avoid further action.

      Code ATCP 76.04 (2) - PLANS SUBMITTED TO DSPS FOR MODIFICATION, A

  3. May 22, 2025 Follow Up · No items found

    No violations cited.

  4. Apr 22, 2025 Routine · 7 critical, 7 non-critical, 2 repeat
    • Not serious Non-critical

      REVERSE FLOW RECIRCULATION

      Proportion of required circulation is not 100% through the gutter or skimmer. Main drain valve is open about 40-50%.

      Correction: Adjust recirculation so 100% of required circulation is through the gutter or skimmer.

      Code ATCP 76.11(2)(a) 2. c. - REVERSE FLOW POOL FLOW

    • Not serious Non-critical

      BACKWASH PROCEDURES POSTED ON EASILY READ CHART

      The backwash procedure is not conspicuously posted on an easily read chart. Operator did not know how to perform a backwash. An outside contractor was being used to do backwashing

      Correction: Post the backwash procedure on an easily read chart.

      Code ATCP 76.11(6)(a) 4. - PROCEDURE POSTED

    • Not serious Non-critical

      SAFETY DATA SHEET

      The current MSDS sheets were in very poor condition.

      Correction: Maintain a good quality safety data sheet for each chemical on site. A binder or folder is recommended to protect the documents.

      Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS

    • Not serious Non-critical Repeat

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept. The monthly checks were not completed and logged during the last few months.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      REAGENTS REPLACED

      Test kit reagents not replaced as recommended by the manufacturer. Most of the reagents were expired.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical

      ELECTRONIC MONITORING FREQUENCY OF TESTING

      The pool, with an electronic monitoring device, has not been consistently manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual.

      Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.

      Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ

    • Not serious Non-critical

      LIFEGUARD, ATTENDANT STAFFING PLAN REQUIRED

      No lifeguard and attendant staffing plan is available.

      Correction: Prepare and maintain a lifeguard staffing plan.

      Code ATCP 76.22(1)(a) - LIFEGUARD, ATTENDANT STAFFING PLAN REQUIR

    • Serious Critical

      OPERATOR KNOWLEDGE- CONNECTION LOCATION FEED AND FLOW SENSING

      The person responsible for interlock testing is not able to describe the location of chemical feed connections and system flow sensing interlocks in the recirculation system.

      Correction: Ensure that operator or their designee is able to describe the location of chemical feed connections and system flow sensing interlocks in the recirculation system.

      Code ATCP 76.13 (1)(c)2.a - FEED AND FLOW SENSING LOCATIONS

    • Serious Critical

      OPERATOR KNOWLEDGE- ELECTRICAL INTERLOCK FUNCTION

      The person responsible is not able to describe how the chemical feeder electrical interlock functions.

      Correction: Ensure that operator can describe how the chemical feeder electrical interlock functions.

      Code ATCP 76.13 (1)(c)2.b - HOW ELECTRICAL INTERLOCK FUNCTIONS

    • Serious Critical

      OPERATOR KNOWLEDGE-FLOW INTERLOCK FUNCTION

      The person responsible is not able to describe how the system flow sensing interlock functions.

      Correction: Ensure that operator can describe how the system flow sensing interlock functions.

      Code ATCP 76.13 (1)(c)2.c - HOW FLOW INTERLOCK FUNCTIONS

    • Serious Critical

      OPERATOR KNOWLEDGE-MONTHLY TESTING

      The person responsible is not able to describe how monthly testing is performed.

      Correction: Ensure that operator can describe how monthly testing is performed.

      Code ATCP 76.13 (1)(c)2.d - MONTHLY TESTING

    • Serious Critical

      OPERATOR KNOWLEDGE SAFETY DURING MONTHLY TESTING

      The person responsible is not able to describe what safety measures that must be employed during monthly testing.

      Correction: Ensure that operator can describe what safety measures that must be employed during monthly testing.

      Code ATCP 76.13 (1)(c)2.e -MONTHLY TESTING SAFETY

    • Serious Critical Repeat

      INTERLOCK CHALLENGE TEST

      Once monthly challenge testing of the chemical feeder system has not been consistently during conducted during 2025 to assess the interlock.

      Correction: Challenge test the chemical feeder system monthly to assess the interlock.

      Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST

    • Serious Critical

      CERTIFICATION MADE AVAILABLE, LIFEGUARD

      A copy of each certification held by a lifeguard has not been made available to the department or its agent.

      Correction: Make a copy of each certification held by a lifeguard available to the department or its agent.

      Code ATCP 76.22(2)(a) - LIFEGUARD CERTIFICATIONS AVAILABLE

  5. Mar 27, 2024 Routine · 2 critical, 8 non-critical
    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      TELEPHONE-EMERGENCY NUMBERS AND ADDRESS

      A list of emergency numbers and facility address not attached or posted near telephone. Numbers were not close to the phone.

      Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device. Move sign with the emergency numbers closer to the phone.

      Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-PUMP CURVE

      The manufacturer’s pump performance curve diagram was not permanently maintained on premises:

      Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.

      Code ATCP 76.32(3)(a)3. - PUMP CURVE

    • Not serious Non-critical Corrected on site

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises. Provided by MCHD.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Not serious Non-critical

      SHOWERS-OPERABLE

      Showers not maintained in an operable condition. One shower in girl's locker room wasn't operating properly.

      Correction: Maintain showers in an operable condition.

      Code ATCP 76.33 (2)(b) - SHOWERS OPERABLE

    • Serious Critical

      INTERLOCK CHALLENGE TEST

      Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.

      Correction: Challenge test the chemical feeder system monthly to assess the interlock.

      Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve..

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

Source: Manitowoc County Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.