RecordWell Data

Holy Family Wellness Center - Lap Pool

1650 SOUTH 41ST, Manitowoc, WI 54220 · Manitowoc County

5cited violations
1serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Manitowoc County Health Department
License / ID
HSAT-7QXPF5
Status
Permitted
Phone
(262) 875-1875
Official record
Manitowoc County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026100
2025110
2024141
2023100

Inspections

  1. Apr 9, 2026 Routine · No items found

    No violations cited.

  2. Feb 20, 2025 Routine · 1 non-critical
    • Not serious Non-critical

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      Some of the showers in the women's bathroom/changing rooms have tiles missing from around the drain area causing standing water.

      Correction: Maintain the shower, toilet and dressing facilities in good repair. Replace tiles.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

  3. Apr 9, 2024 Routine · 1 critical, 3 non-critical
    • Not serious Non-critical

      COMBINED CHLORINE PLAN VOLUME OF POOL

      The combined chlorine plan does not include volume of pool. The volume of Lap Pool is 59,653 gallons.

      Correction: Include the volume of pool in the combined chlorine plan.

      Code ATCP 76.14(5)(e)2.b.- VOLUME OF POOL

    • Not serious Non-critical

      COMBINED CHLORINE PLAN VOLUME OF SOURCE WATER ADDED-RANGE

      The combined chlorine plan does not include range of volume of fresh source water added to pool each day.

      Correction: Include the range of volume of fresh source water added to pool each day in the combined chlorine plan.

      Code ATCP 76.14(5)(e)2.c. - VOLUME OF SOURCE WATER ADDED

    • Not serious Non-critical

      COMBINED CHLORINE PLAN SHOWERING REQUIREMENTS

      The combined chlorine plan does not include description of showering requirements and how communicated to patrons. For example: entrance to the pool from showering areas states that "patrons must shower before entering the pool" and any other means of communication the establishement may use to communicate this requirement.

      Correction: Include a description of showering requirements and how communicated to patrons in the combined chlorine plan.

      Code ATCP 76.14(5)(e)2.d. - SHOWERING REQUIREMENTS

    • Serious Critical

      INTERLOCK LOG-INFORMATION

      The monthly testing log is missing or incomplete. Althought the Chemical Interlock Checklist Form provided by DATCP is voluntary, it is strongly recommended that this form be used as it provides a template for the required information needed during Interlock testing. The 'Interlock Testing for Pools' form provided by the establishment during the inspection can be used as part of the requirement of the monthly testing log.

      Correction: Maintain a log that is documented with the date, results, and the name of the person performing the interlock test.

      Code ATCP 76.13 (1)(c)4.a - INTERLOCK LOG, INFORMATION REQUIRED

  4. May 31, 2023 Routine · No items found

    No violations cited.

Source: Manitowoc County Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.