Inn On Maritime Bay Pool
101 MARITIME DR, Manitowoc, WI 54220 · Manitowoc County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Manitowoc County Health Department
- License / ID
- AZIR-AQ4M5S
- Status
- Permitted
- Phone
- (920) 682-7000
- Official record
- Manitowoc County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 0 |
| 2025 | 2 | 13 | 3 |
| 2024 | 1 | 14 | 3 |
Inspections
-
Jun 24, 2026 Routine · 2 non-critical, 1 repeat
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
-
May 9, 2025 Follow Up · 4 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available
Correction: Provide a spare strainer or screen
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
STAFF TRAINED IN SAFETY DATA SHEETS
Staff are not trained in the use of the safety data sheet and where they are located.
Correction: Train staff in the use of the safety data sheet and where they are located.
Code ATCP 76.12 (4)(b)3 - STAFF TRAINED IN SAFETY DATA SHEETS
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
-
Apr 8, 2025 Routine · 3 critical, 6 non-critical, 5 repeat
-
Not serious
Non-critical
Repeat
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available
Correction: Provide a spare strainer or screen
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
STAFF TRAINED IN SAFETY DATA SHEETS
Staff are not trained in the use of the safety data sheet and where they are located.
Correction: Train staff in the use of the safety data sheet and where they are located.
Code ATCP 76.12 (4)(b)3 - STAFF TRAINED IN SAFETY DATA SHEETS
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. The pool light is missing and an open hole remains.
Correction: Maintain the pool equipment.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Serious
Critical
WATER SUPPLY PROTECTION
Approved backflow or backsiphonage protection does not exist between potable water supply inlet and the overflow point of pool, makeup tank, surge tank or slurry tank and another approved device does not exist.
Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool, makeup tank, surge tank, solution tank, or slurry tank.
Code ATCP 76.19(1) - PROTECTION
-
Serious
Critical
DRINKING FOUNTAIN PROVIDED
There is no drinking fountain provided.
Correction: Provide a drinking fountain within 300 feet walking distance.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Serious
Critical
Repeat
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
-
Apr 11, 2024 Routine · 3 critical, 11 non-critical
-
Not serious
Non-critical
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available
Correction: Provide a spare strainer or screen
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
EMERGENCY CONTACT PHONE NUMBERS
Emergency contact phone numbers are not in the chemical storage area or readily accessible.
Correction: Provide emergency contact numbers in the chemical storage area or readily accessible.
Code ATCP 76.12 (2)(j) - EMERGENCY CONTACT PHONE NUMBERS
-
Not serious
Non-critical
SAFETY DATA SHEET
Safety data sheets not available for each chemical.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
STAFF TRAINED IN SAFETY DATA SHEETS
Staff are not trained in the use of the safety data sheet and where they are located.
Correction: Train staff in the use of the safety data sheet and where they are located.
Code ATCP 76.12 (4)(b)3 - STAFF TRAINED IN SAFETY DATA SHEETS
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. Some of the reagents have expired..
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
FIRST AID KIT ITEMS
The first aid kit is present but missing items.
Correction: Replace the missing items in the first aid kit.
Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS
-
Not serious
Non-critical
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT
The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.
Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.
Code ATCP 76.38(2)(a) - DRAIN COVER LOG
-
Serious
Critical
OPERATOR KNOWLEDGE-MONTHLY TESTING
The person responsible is not able to describe how monthly testing is performed.
Correction: Ensure that operator can describe how monthly testing is performed.
Code ATCP 76.13 (1)(c)2.d - MONTHLY TESTING
-
Serious
Critical
HAZARDOUS CONDITION
There is a hazardous condition at the pool. Pool lights are not illuminated
Correction: Correct the hazardous condition. Pool lighting is new, facility is working with Backus Electric, emails and receipts reviewed.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Source: Manitowoc County Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.