Inspections
-
Mar 20, 2026 Routine · 6 non-critical
-
Not serious
Non-critical
HIGH RATE SAND FILTER BACKWASHING
Sand filter is not being backwashed according to manufacturers instructions. The pressure on the filter does not change when backwashing occurs.
Correction: When to backwash should be based upon the change in the pressure gauge readings. Pressure should build and than drop after the backwash occurs.
Code ATCP 76.11(6)(b) 2. - HIGH RATE SAND FILTER BACKWASH
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The conbined chlorine in the whirlpool was 1.4 ppm.
Correction: Implement the combined chlorine plan to lower the combined chlorine present in the whirlpool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagentthiosulfate has expired according to the manufacturer.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
WATER LEVEL-SKIMMERS MAINTAINED
Water level in a skimmer pool is too high and not allowing for effective skimming.
Correction: Maintain the water level in the pool so that the skimmer weir is half submerged, or, in the case of a floating weir, used according to manufacturer's instructions.
Code ATCP 76.19(3)(a) - SKIMMERS MAINTAINED
-
Not serious
Non-critical
THERMOMETER RETURN LINE
An accurate thermometer is not located in the pool water return line.
Correction: Provide an accurate thermometer in the pool water return line.
Code ATCP 76.19(4)(a)1 - THERMOMETER
-
Not serious
Non-critical
FIRST AID KIT ITEMS
The first aid kit is present but missing items.
Correction: Replace the missing items in the first aid kit.
Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS
-
Not serious
Non-critical
-
Mar 28, 2025 Routine · No items found
No violations cited.
-
May 24, 2024 Routine · 1 critical, 8 non-critical
-
Not serious
Non-critical
READABLE CHART
A conspicuously posted, easily read chart that explains the system that corresponds with labels, tags or color coding is not present.
Correction: Provide the chart for labels, tags and color-coding
Code ATCP 76.11(5m)(b) - PIPING CHART
-
Not serious
Non-critical
INTERLOCKED-ELECTRICAL
Power to recirculation system is not interlocked with the power to the chemical feed.
Correction: Provide interlock between the power to the recirculation system and power to the chemical feeder(s).
Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE
Chlorine is used in a whirlpool and pool water is not tested daily for the combined chlorine level.
Correction: Test pool water daily for the combined chlorine level.
Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY
-
Not serious
Non-critical
POSTING SIGNAGE-MAX PATRON LOAD
Maximum patron load is not posted.
Correction: Post signage indicating Maximum patron load.
Code ATCP 76.29(1)(e) - MAX PATRON LOAD
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
POOL DECK-DEPTH MARKINGS MAINTAINED
There is no depth marking on the interior of the whirlpool basin.
Correction: Install depth markings in the interio of the wirlpool basin.
Code ATCP 76.33(1)(b)4. - DEPTH MARKINGS
-
Not serious
Non-critical
AIR MOVEMENT
Air filter is dirty for the ventilation in the wall of the pool enclosure.
Correction: Maintain heating, ventilation, and exhaust equipment to provide air movement to prevent any excessive condensation.
Code ATCP 76.33(4)(b) - AIR MOVEMENT
-
Serious
Critical
Corrected on site
CHEMICAL IS TO BE ADDED TO WATER
Water was added to the muratic acid
Correction: A chemical solution shall be added to water, not by adding water to the chemical. Discussed on site with Brian and Joe why water should not be acid to water.
Code ATCP 76.12 (3)(a) - CHEMICALS ADDED TO WATER
-
Not serious
Non-critical
Source: Marathon County Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.