Karl Jewish Comm Campus General Spa
6255 N SANTA MONICA BLVD, Whitefish Bay, WI 53217 · Milwaukee County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- North Shore Health Department
- License / ID
- SYOG-7QRUXW
- Status
- Permitted
- Phone
- (414) 967-8348
- Official record
- North Shore Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 2 |
| 2025 | 2 | 8 | 3 |
| 2023 | 1 | 1 | 0 |
Inspections
-
May 4, 2026 Routine · 2 critical
-
Serious
Critical
PH
The pH is above 8.0.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
MAXIMUM BROMINE
The maximum total bromine exceeds 10 ppm.
Correction: Close the pool until the total bromine residual is in compliance with Table ATCP 76.14 Table A.
Code ATCP 76.14(5)(g) -MAXIMUM BROMINE
-
Serious
Critical
-
Feb 20, 2025 Re-inspection · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS MAINTAINED CLEAN
Skimmer had a build up of what appeared to be mold on the inside.
Correction: Maintain the skimmers in clean condition.
Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN
-
Not serious
Non-critical
Repeat
-
Feb 6, 2025 Routine · 3 critical, 4 non-critical
-
Not serious
Non-critical
SKIMMERS MAINTAINED CLEAN
Skimmer had a build up of what appeared to be mold on the inside.
Correction: Maintain the skimmers in clean condition.
Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN
-
Not serious
Non-critical
SKIMMERS REPAIRED OR REPLACED AS NEEDED
Skimmer does not have a weir door.
Correction: Repair or replace skimmer, weirs or gutters as needed.
Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Results for chemical testing.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Serious
Critical
Corrected on site
RECIRCULATION SYSTEM CONTINUOUS OPERATION
The pool recirculation system is not operational where the skimmers were not operational.
Correction: The skimmers were not turned back on after conducting work on the pool today. The skimmers were reactivated. It was recommended at the time of the inspection that the pool remain closed to complete one full turnover. The pool operator agreed to do so.
Code ATCP 76.11(1) - RECIRCULATION SYSTEM PRESENT, CONTINUOUSLY O
-
Serious
Critical
AUTOMATIC AND CONTINUOUS DISINFECTION
Pool not automatically disinfected. During the inspection it was found that pucks were placed in the skimmer baskets.
Correction: Ensure that each pool in use is automatically and continuously disinfected by means of disinfectant or sanitizer and feeding equipment that is in compliance with this section and s. ATCP 76.13. The pucks were removed at the time of the inspection. Do not place pucks in the baskets.
Code ATCP 76.14 (1) - AUTOMATIC DISINFECTION
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 3.5 ppm for bromine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Not serious
Non-critical
-
Oct 3, 2023 Routine · 1 non-critical
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 20 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Source: North Shore Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.