Milwaukee Country Club

8000 N RANGE LINE, River Hills, WI 53217 · Milwaukee County

11cited violations
2serious tier
5inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
North Shore Health Department
License / ID
SYOG-7QRUW5
Status
Permitted
Phone
(414) 362-5200
Official record
North Shore Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026131
2025130
2024241
2023110

Inspections

  1. Aug 19, 2026 Routine · 1 critical, 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is [615] mV and water has not been tested manually.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Serious Critical Corrected on site

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is [0 ppm ] for chlorine.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Minimum amount required is 1 ppm. Pool adjusted to 8.5 ppm during the inspection.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

  2. Aug 6, 2025 Routine · 3 non-critical, 1 repeat
    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool. The combine chlorine plan template will be sent by the NSHD.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is [560] mV and water has not been tested manually.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

  3. Aug 14, 2024 Routine · 1 critical, 1 non-critical
    • Not serious Non-critical

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is [495 ] mV and water has not been tested manually. The ORP was increasing at the time of inspection.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Serious Critical Corrected on site

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is [0.5 ppm]. The Chlorine was raised to 3.5 ppm at the time of the inspection

      Correction: Maintain chlorine level above 1.0 ppm.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

  4. May 24, 2024 Pre-inspection · 2 non-critical
    • Not serious Non-critical

      SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED

      The shower, toilet and dressing facilities are under construction. Millwork is being completed. The toilet, shower, sinks are functioning.

      Correction: Complete construction. The counter top is to be installed June 3rd.

      Code ATCP 76.33 (2)(a)1. - GOOD REPAIR

    • Not serious Non-critical

      POOL EQUIPMENT-PROPERLY MAINTAINED

      The pool area is under construction and the pool shall not open until construction is complete and area is cleaned.

      Correction: Finish construction and clean deck area prior to opening.

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

  5. Jun 20, 2023 Routine · 1 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeter is not functional because sand was stuck in the tube.

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

Source: North Shore Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.