Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
North Shore Health Department
License / ID
BSIY-ANSJF6
Status
Permitted
Official record
North Shore Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20262101
20252183
2024180
2023271

Inspections

  1. Aug 18, 2026 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is [40 ppm].

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water. AT THE TIME OF THE INSPECTION, THE OPERATOR STATED THAT THE ALK IS LOW BECAUSE THEY JUST REFILLED IT. NOT CHECKED.

      Code ATCP 76.14(5)(d) - ALKALINITY

  2. Aug 11, 2026 Routine · 1 critical, 8 non-critical, 3 repeat
    • Not serious Non-critical

      SKIMMER POOL RECIRCULATION FLOW

      Proportion of water recirculating from skimmer and main drain is 100 percent open.

      Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical

      SKIMMERS MAINTAINED CLEAN

      Skimmers not maintained clean. The baskets were full of debris and toys.

      Correction: Maintain the skimmers in clean condition.

      Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition.

      Correction: Adjust or repair the flowmeter

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is [40 ppm].

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      SIGNAGE 'NO LIFEGUARD ON DUTY'

      A pool not required to have a lifeguard, does not have a 'no lifeguard on duty' sign.

      Correction: Provide a sign to indicate 'no lifeguard on duty.'

      Code ATCP 76.23(2)- NO LIFEGUARD ON DUTY

    • Not serious Non-critical Repeat

      POOL RULES POSTED

      The pool rules are not posted.

      Correction: Post the pool rules.

      Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical

      HAZARDOUS CONDITION

      There is a hazardous condition at the pool. Drain cover is missing a screw.

      Correction: The facility closed the pool until the screw is added per the manufactures specifications.

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  3. Oct 1, 2025 Re-inspection · 1 critical, 6 non-critical, 7 repeat
    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. Weir doors missing..

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is 40.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      CYANURIC TEST

      Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week. It is tested monthly.

      Correction: Test water for the cyanuric acid at least once a week.

      Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC

    • Not serious Non-critical Repeat

      TELEPHONE-EMERGENCY NUMBERS AND ADDRESS

      A list of emergency numbers and facility address not attached or posted near telephone. .

      Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.

      Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED

    • Not serious Non-critical Repeat

      EMERGENCY BLANKETS

      Two emergency blankets in good condition are not available in the pool area.

      Correction: Provide two emergency blankets in good condition in the pool area.

      Code ATCP 76.27(3) - EMERGENCY BLANKETS

    • Not serious Non-critical Repeat

      POSTING SIGNAGE-MAX PATRON LOAD

      Maximum patron load is not posted.

      Correction: Post signage indicating Maximum patron load.

      Code ATCP 76.29(1)(e) - MAX PATRON LOAD

    • Serious Critical Repeat

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve or drain cover specifications.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  4. Aug 27, 2025 Routine · 2 critical, 9 non-critical, 4 repeat
    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. Weir doors missing..

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is 40.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is 500 mV and water has not been tested manually.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      CYANURIC TEST

      Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week. It is tested monthly.

      Correction: Test water for the cyanuric acid at least once a week.

      Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC

    • Not serious Non-critical

      TELEPHONE-EMERGENCY NUMBERS AND ADDRESS

      A list of emergency numbers and facility address not attached or posted near telephone. .

      Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.

      Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED

    • Not serious Non-critical

      EMERGENCY BLANKETS

      Two emergency blankets in good condition are not available in the pool area.

      Correction: Provide two emergency blankets in good condition in the pool area.

      Code ATCP 76.27(3) - EMERGENCY BLANKETS

    • Not serious Non-critical Repeat

      POOL RULES POSTED

      The pool rules are not posted at wading pool.

      Correction: Post the pool rules.

      Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED

    • Not serious Non-critical

      POSTING SIGNAGE-MAX PATRON LOAD

      Maximum patron load is not posted.

      Correction: Post signage indicating Maximum patron load.

      Code ATCP 76.29(1)(e) - MAX PATRON LOAD

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

    • Serious Critical

      VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO

      The operator of an existing pool does not have the pump curve or drain cover specifications.

      Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.

      Code ATCP 76.38(1)(b) - PUMP CURVE

  5. Aug 14, 2024 Routine · 8 non-critical
    • Not serious Non-critical

      SKIMMER POOL RECIRCULATION FLOW

      Proportion of water recirculating from skimmer and main drain is open fully.

      Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers missing weir doors.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not functioning.

      Correction: Adjust or repair the flowmeter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is [20 ppm ].

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is [343 ] mV and water has not been tested manually.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      INCREASED TESTING MAY BE REQUIRED

      The facility test for alk, cya and combined chlorine.

      Correction: Perform routine tests for chemistry of the pool.

      Code ATCP 76.18(4) - INCREASED TESTING

    • Not serious Non-critical

      MAX PATRON LOAD WADING POOL

      The wading pool patron load is not posted.

      Correction: Calculate the maximum patron load to provide at least 15 square feet per patron and do not allow the maximum patron load to be exceeded.

      Code ATCP 76.25(2)(c) - WADING POOL

    • Not serious Non-critical

      POOL RULES POSTED

      The pool rules are not posted.

      Correction: Post the pool rules.

      Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED

  6. Aug 4, 2023 Re-inspection · 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeter is not functional.

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical Repeat

      ALKALINITY OUT OF BALANCE

      The total alkalinity is [40 ppm].

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

  7. Jul 27, 2023 Routine · 1 critical, 4 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeter is not functional.

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical Repeat

      ALKALINITY OUT OF BALANCE

      The total alkalinity is [40 ppm].

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

    • Not serious Non-critical

      WATER POTENTIAL OUT OF RANGE

      The water potential was [550] mV at the time of the inspection.

      Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed.

      Code ATCP 76.14(5)(a)

    • Not serious Non-critical

      WATER TESTING FREQUENCY - POOLS

      The water testing logs not available for review.

      Correction: Perform water testing in accordance with ATCP 76.18(1). Maintain logs.

      Code ATCP 76.18(1)

    • Serious Critical Repeat

      pH OUT OF BALANCE

      The pH is [8.5 ].

      Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.

      Code ATCP 76.14(4)(c)

Source: North Shore Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.