RecordWell Data

Elite Sports Club - River Glen Indoor Mens Whirlpool

2001 W GOOD HOPE RD, Glendale, WI 53209 · Milwaukee County

23cited violations
2serious tier
7inspections

Establishment

Type
Pool / recreational water (Pool - Moderate)
Inspected by
North Shore Health Department
License / ID
BSIY-BKFR45
Status
Permitted
Official record
North Shore Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20262111
2025151
2024350
2023120

Inspections

  1. Aug 7, 2026 Re-inspection · 5 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is [30 ppm ].

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE

      Chlorine is used in a whirlpool and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY

    • Not serious Non-critical Repeat

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL, ALKALINITY

      Whirlpool water not tested at least once a week for total alkalinity.

      Correction: Test pool water at least once a week for total alkalinity.

      Code ATCP 76.18(2)(c) - ALKALINITY, WHIRL, EX, THERAPY

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary. The pool basin is serverly damaged and requires repair.

      Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

  2. Jul 21, 2026 Routine · 1 critical, 5 non-critical, 1 repeat
    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is [30 ppm ].

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL,COMBINED CHLORINE

      Chlorine is used in a whirlpool and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(2)(b) - COMBINED CHLORINE, WHIRLPOOL, EX, THERAPY

    • Not serious Non-critical

      WHIRLPOOL, THERAPY POOL, EXERCISE POOL, ALKALINITY

      Whirlpool water not tested at least once a week for total alkalinity.

      Correction: Test pool water at least once a week for total alkalinity.

      Code ATCP 76.18(2)(c) - ALKALINITY, WHIRL, EX, THERAPY

    • Not serious Non-critical

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary. The pool basin is serverly damaged and requires repair.

      Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Serious Critical

      CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE

      The whirlpool shall be closed due to a nonworking emergency phone.

      Correction: Close the pool until a phone is provided. Reinspection required. A temporary phone has been installed until the new phone system is installed.

      Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE

  3. Aug 15, 2025 Routine · 1 critical, 4 non-critical
    • Not serious Non-critical Corrected on site

      ALKALINITY

      The total alkalinity is [17 ppm].

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water. This pool was adjusted at the time of the inspection.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      TELEPHONE-EMERGENCY NUMBERS AND ADDRESS

      A list of emergency numbers and facility address not attached or posted near telephone. A sign is not posted near the pool indicating the location of the phone.

      Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device. Post of a sign in the pool area indicating the location of the phone.

      Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED

    • Not serious Non-critical

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Serious Critical Corrected on site

      PH

      The pH is [6.8 ].

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better. This pool was adjust at the time of the inspection.

      Code ATCP 76.14(5)(c) - PH

  4. Aug 8, 2024 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

  5. Aug 2, 2024 Re-inspection · 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Drain covers did have screws to secure the cover.

      Correction: Keep pool closed until repair is made and inspection obtained.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

  6. Jul 31, 2024 Routine · 2 non-critical
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Drain covers did have screws to secure the cover.

      Correction: Keep pool closed until repair is made and inspection obtained.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

  7. Jun 27, 2023 Routine · 2 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      Flowmeter not functional.

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical

      CRACKS OR PITTING IN THE POOL BASIN

      The pool basin is pitted or damaged.

      Correction: Repair the pool basin so it is finished and easily cleanable.

      Code [B] ATCP 76.33(1)(a)

Source: North Shore Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.