Aug 4, 2026 Routine · 1 critical, 3 non-critical
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 30 ppm
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
FIRST AID KIT -RESUSCITATION POCKET MASK
The first aid kit is missing a resuscitation pocket mask.
Correction: Provide a resuscitation pocket mask for the first aid kit.
Code ATCP 76.27(1)(b)8.- RESUSCITATION MASK
-
Not serious
Non-critical
VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT
The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement. Drain/equalizer cover information not available.
Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.
Code ATCP 76.38(2)(a) - DRAIN COVER LOG
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 16.0 for bromine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Not serious
Non-critical
-
Aug 19, 2025 Re-inspection · 2 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
Repeat
-
Aug 7, 2025 Routine · 1 critical, 4 non-critical, 1 repeat
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition.
Correction: Repair or replace the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
WATER LEVEL-SKIMMERS MAINTAINED
Water level in a skimmer pool is not allowing for effective skimming because the water level is too high.
Correction: Maintain the water level in the pool so that the skimmer weir is half submerged, or, in the case of a floating weir, used according to manufacturer's instructions.
Code ATCP 76.19(3)(a) - SKIMMERS MAINTAINED
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Serious
Critical
Corrected on site
CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE
Operator has not closed the pool due to a nonfunctional emergency phone.
Correction: Close the pool in the event of a nonfunctional emergency phone. This was corrected at the time of the inspection.
Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE
-
Not serious
Non-critical
-
Jul 16, 2024 Routine · 2 non-critical
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 30.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
WATER LEVEL-SKIMMERS MAINTAINED
Water level in a skimmer pool is not allowing for effective skimming.
Correction: Maintain the water level in the pool so that the skimmer weir is half submerged, or, in the case of a floating weir, used according to manufacturer's instructions.
Code ATCP 76.19(3)(a) - SKIMMERS MAINTAINED
-
Not serious
Non-critical
-
Aug 2, 2023 Re-inspection · No items found
No violations cited.
-
Jul 25, 2023 Routine · 2 non-critical, 1 repeat
-
Not serious
Non-critical
SKIMMERS NOT FUNCTIONING
The skimmer is not adequately removing surface debris.
Correction: Readjust the flow through the skimmers to maintain vigorous skimming action through all skimmers.
Code ATCP 76.11(2)(a)
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL
The flowmeter is not functional.
Correction: Repair or replace the specified equipment so an accurate reading can be recorded.
Code ATCP 76.11(5)
-
Not serious
Non-critical