Rivers Edge Homes Assoc., INC

4117 W RIVERS EDGE CIR, Brown Deer, WI 53209 · Milwaukee County

6cited violations
2serious tier
6inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
North Shore Health Department
License / ID
SYOG-7QRUVT
Status
Permitted
Phone
(414) 354-0478
Official record
North Shore Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026111
2025231
2024100
2023220

Inspections

  1. Jul 1, 2026 Routine · 1 critical
    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is 1.0 for liquid chlorine in a pool with stabilizer.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

  2. Jul 11, 2025 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Turnover rate is 6.9 hours. The person in charge indicated that the filters may require backwashing. He plans to perform the backwash and provide documentation demonstrating that the flow rate has improved.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate to 6 hours or less.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

  3. Jul 10, 2025 Routine · 1 critical, 1 non-critical
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Turnover rate is 6.9 hours. The person in charge indicated that the filters may require backwashing. He plans to perform the backwash and provide documentation demonstrating that the flow rate has improved.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate to 6 hours or less.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Serious Critical

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

  4. Jul 22, 2024 Routine · No items found

    No violations cited.

  5. Jul 6, 2023 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat Corrected on site

      LIGHTING

      The housing for the light is not secure.

      Correction: Replace and maintain all lighting in operating condition. HORIZON FIXED THE LIGHT HOUSING.

      Code ATCP 76.33(4)(c)

  6. Jun 19, 2023 Routine · 1 non-critical
    • Not serious Non-critical

      LIGHTING

      The housing for the light is not secure.

      Correction: Replace and maintain all lighting in operating condition.

      Code ATCP 76.33(4)(c)

Source: North Shore Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.