Elite Sports Club - North Shore Womans Whirlpool
5750 N GLEN PARK RD, Glendale, WI 53209 · Milwaukee County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- North Shore Health Department
- License / ID
- BSIY-BKFPPN
- Status
- Permitted
- Official record
- North Shore Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2025 | 3 | 18 | 4 |
| 2023 | 2 | 4 | 3 |
Inspections
-
Jan 28, 2025 Re-inspection · 2 critical, 3 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainert not available
Correction: Provide a spare strainer.
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-BACKWASH
The operator did not record the following on the operating report: The dates on which backwashing was completed.
Correction: Record the following on the operating report, the dates when backwashing was completed.
Code ATCP 76.32(1)(b) - BACKWASH
-
Not serious
Non-critical
Repeat
POOL BASIN MAINTAINED FREE OF DEFECTS
Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition.
Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.
Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR
-
Serious
Critical
PH
The pH is [>8.0].
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better. The facility shall close the pool until rebalanced.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm.
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Not serious
Non-critical
Repeat
-
Jan 27, 2025 Re-inspection · 1 critical, 5 non-critical, 5 repeat
-
Not serious
Non-critical
Repeat
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainert not available
Correction: Provide a spare strainer.
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
Repeat
WATER LEVEL-SKIMMERS MAINTAINED
Water level in a skimmer pool is not allowing for effective skimming.
Correction: Maintain the water level in the pool so that the skimmer weir is half submerged.
Code ATCP 76.19(3)(a) - SKIMMERS MAINTAINED
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-BACKWASH
The operator did not record the following on the operating report: The dates on which backwashing was completed.
Correction: Record the following on the operating report, the dates when backwashing was completed.
Code ATCP 76.32(1)(b) - BACKWASH
-
Not serious
Non-critical
Repeat
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
Repeat
POOL BASIN MAINTAINED FREE OF DEFECTS
Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition.
Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.
Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR
-
Serious
Critical
INTERLOCKED-ELECTRICAL
Power to recirculation system is not interlocked with the power to the chemical feed.
Correction: Provide interlock between the power to the recirculation system and power to the chemical feeder(s). Close the pool until a interlock system is provided.
Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT
-
Not serious
Non-critical
Repeat
-
Jan 17, 2025 Routine · 1 critical, 6 non-critical
-
Not serious
Non-critical
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainert not available
Correction: Provide a spare strainer.
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
WATER LEVEL-SKIMMERS MAINTAINED
Water level in a skimmer pool is not allowing for effective skimming.
Correction: Maintain the water level in the pool so that the skimmer weir is half submerged.
Code ATCP 76.19(3)(a) - SKIMMERS MAINTAINED
-
Not serious
Non-critical
OPERATING REPORTS-BACKWASH
The operator did not record the following on the operating report: The dates on which backwashing was completed.
Correction: Record the following on the operating report, the dates when backwashing was completed.
Code ATCP 76.32(1)(b) - BACKWASH
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
POOL BASIN MAINTAINED FREE OF DEFECTS
Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition.
Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.
Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR
-
Serious
Critical
CLOSING CRITERIA-NON-OPERATIONAL RECIRD PUMP
The pump is not moving water through the recirculation system.
Correction: Close the pool in the event of a nonoperational circulation pump, filter, or disinfectant or sanitizer feeder. Do not reopen until the flow is correct and the flowmeter is working properly.
Code ATCP 76.30 (1)(d) - NON-OPERATIONAL RECIRC PUMP
-
Not serious
Non-critical
-
May 5, 2023 Re-inspection · No items found
No violations cited.
-
May 1, 2023 Re-inspection · 3 critical, 1 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
EQUIPMENT NOT MAINTAINED
There is a plumbing leak that is leaking into a funnel
Correction: Repair and maintain all equipment pursuant to ATCP 76.33(1)(e).
Code ATCP 76.33(1)(e)
-
Serious
Critical
Repeat
pH OUT OF BALANCE
The pH is [7.0 ].
Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.
Code ATCP 76.14(4)(c)
-
Serious
Critical
Repeat
CHLORINE TOO LOW
The chlorine residual was [1.8 ppm ] at the time of the inspection.
Correction: Close the pool and raise the chlorine residual to [3.0 ppm ] before re-opening.
Code [A] ATCP 76.14(4)(a)
-
Serious
Critical
Repeat
SKIMMER COVERS NOT SECURE
The main drain cover is missing a screw(s). This is an imminent health hazard and violates VGBA requirements.
Correction: The whirlpool shall immediately close and remain closed until repaired and a reinspection is completed. The facility shall place a "Pool Closed" sign and barricade the pool to prevent entry. The facility shall have 14 days to comply. GRATES WERE REPAIRED AND NOW HAVE CRACKS. THE GRATES NOW MUST BE REPLACES AND THE POOL SHALL REMAIN CLOSED UNTIL GRATES ARE REPLACED AND INSPECTED.
Code [C] ATCP 76.11(2)(b)
-
Not serious
Non-critical
Repeat
Source: North Shore Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.