RecordWell Data

Porticos Of Fox Point (indoor)

500 W BRADLEY, Fox Point, WI 53217 · Milwaukee County

26cited violations
6serious tier
6inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
North Shore Health Department
License / ID
MWIN-7QYMW3
Status
Permitted
Official record
North Shore Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026150
20252115
2024141
2023260

Inspections

  1. Aug 4, 2026 Routine · 5 non-critical, 1 repeat
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Turnover rate is 7.6 hours.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of 6 hours or less.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      BIOHAZARD KIT-AVAILABLE

      A biohazard kit is not available.

      Correction: Provide a biohazard kit for the pool.

      Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE

    • Not serious Non-critical

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. Equalizer cover documentation needed.

      Correction: Maintain Virginia Graeme Baker Act equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

  2. Aug 19, 2025 Re-inspection · 1 critical, 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-PUMP CURVE

      The manufacturer’s pump performance curve diagram was not permanently maintained on premises:

      Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.

      Code ATCP 76.32(3)(a)3. - PUMP CURVE

    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Serious Critical Corrected on site

      GATES AND DOORS MAINTAINED

      Door has not been maintained for proper operation. The door entering the indoor pool does not properly close and latch.

      Correction: Maintain the door for proper operation. DOOR WAS ADJUSTED TO SELF CLOSE BUT WAS NOT LATCHING. THIS WILL BE ADJUSTED ASAP. SPOKE WITH GM AND MAINTENANCE. EDUCATIONAL MOMENT.

      Code ATCP 76.34(2)(a) - GATES AND DOORS OPERABLE

  3. Aug 7, 2025 Routine · 4 critical, 4 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flow meter is not being maintained in operating condition.

      Correction: Repair or replace flow meter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      SAFETY ROPE IN PLACE WHEN APPLICABLE

      The safety rope not in place when applicable. The safety rope not in place when the pool is not in-use.

      Correction: Maintain the safety rope in place as applicable.

      Code ATCP 76.26(1)(c)2. - SAFETY ROPE IN PLACE WHEN APPLICABLE

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-PUMP CURVE

      The manufacturer’s pump performance curve diagram was not permanently maintained on premises:

      Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.

      Code ATCP 76.32(3)(a)3. - PUMP CURVE

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is [0.5 ppm ] for chlorine.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      PH

      The pH is [7.0].

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical Corrected on site

      CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE

      Operator has not closed the pool due to a nonfunctional emergency phone.

      Correction: Close the pool in the event of a nonfunctional emergency phone. This was corrected at the time of the inspection.

      Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE

    • Serious Critical

      GATES AND DOORS MAINTAINED

      Door has not been maintained for proper operation. The door entering the indoor pool does not properly close and latch.

      Correction: Maintain the door for proper operation.

      Code ATCP 76.34(2)(a) - GATES AND DOORS OPERABLE

  4. Jul 16, 2024 Routine · 1 critical, 3 non-critical
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. Skimmer not functioning adequately. It is not allowing water to flow over top of weir . Water level may be too low in pool.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      FIRST AID KIT ITEMS

      The first aid kit is present but missing items.

      Correction: Replace the missing items in the first aid kit.

      Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical

      WATER SUPPLY PROTECTION

      Approved backflow or backsiphonage protection does not exist between potable water supply inlet and the overflow point of pool, makeup tank, surge tank or slurry tank and another approved device does not exist. No backflow prevention device on indoor pool hose connection.

      Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool, makeup tank, surge tank, solution tank, or slurry tank.

      Code ATCP 76.19(1) - PROTECTION

  5. Aug 2, 2023 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      CYANURIC ACID >30 PPM

      The cyanuric acid concentration is [>100 ppm ].

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

  6. Jul 25, 2023 Routine · 5 non-critical, 4 repeat
    • Not serious Non-critical Repeat

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeter not functional.

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical Repeat

      CYANURIC ACID >30 PPM

      The cyanuric acid concentration is [>100 ppm ].

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

    • Not serious Non-critical Repeat

      pH OUT OF BALANCE

      The pH is [7.0 ].

      Correction: Adjust the pool until the pH falls between 7.2 and 7.8.

      Code ATCP 76.14(4)(c)

    • Not serious Non-critical

      RESCUE EQUIPMENT NOT ACCESSIBLE

      The ring buoy is on site but not readily accessible because the rope is tied with a knot.

      Correction: Keep rope loose for quick use.

      Code ATCP 76.26(1)(a)

    • Not serious Non-critical Repeat

      SAFETY ROPE NOT IN PLACE

      The safety rope is not in place.

      Correction: Put the safety rope in place and ensure that it stays in place during required times.

      Code ATCP 76.26(1)(c)

Source: North Shore Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.