River Tennis Club

8188 N GREEN BAY, River Hills, WI 53217

14cited violations
4serious tier
5inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
North Shore Health Department
License / ID
SYOG-7QRUYN
Status
Permitted
Phone
(414) 354-8815
Official record
North Shore Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026272
2025262
2023110

Inspections

  1. Sep 2, 2026 Re-inspection · 1 critical, 2 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is 530 mV and water has not been tested manually.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical Repeat

      BIOHAZARD KIT-AVAILABLE

      A biohazard kit is not available.

      Correction: Provide a biohazard kit for the pool.

      Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE

    • Serious Critical Repeat

      TELEPHONE-OTHER TECHNOLOGIES,RELIABLE SERVICE CONNECTION

      Cordless phone does not have reliable service connection. 9-2-2026 - Upon re-inspection, facility had changed to a corded phone, however, it does not appear to have a permanent continuous power supply with battery backup. Phone is connected to electrical outlet and internet router.

      Correction: Provide a reliable service connection for the communication technology.

      Code ATCP 76.26(2)(b)2. - TELEPHONE, OTHER TECHNOLOGIES, CONNECTI

  2. Aug 26, 2026 Routine · 1 critical, 3 non-critical
    • Not serious Non-critical

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is 530 mV and water has not been tested manually.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      FIRST AID KIT-EYE WASH SOLUTION

      The first aid kit is missing eye wash solution.

      Correction: Provide eye wash solution for the first aid kit.

      Code ATCP 76.27(1)(b)5. - EYE WASH SOLUTION

    • Not serious Non-critical

      BIOHAZARD KIT-AVAILABLE

      A biohazard kit is not available.

      Correction: Provide a biohazard kit for the pool.

      Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE

    • Serious Critical

      TELEPHONE-OTHER TECHNOLOGIES,RELIABLE SERVICE CONNECTION

      Cordless phone does not have reliable service connection.

      Correction: Provide a reliable service connection for the communication technology.

      Code ATCP 76.26(2)(b)2. - TELEPHONE, OTHER TECHNOLOGIES, CONNECTI

  3. Jul 8, 2025 Re-inspection · No items found

    No violations cited.

  4. Jun 30, 2025 Routine · 2 critical, 4 non-critical
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Turnover rate is 10 hours. Person in charge stated pool is 75, 000 gallons and flow meter is at 125 gpm.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      REAGENTS REPLACED

      Test kit reagents not replaced as recommended by the manufacturer. Several reagents in test kit are expired.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical

      RESCUE EQUIPMENT ACCESSIBLE

      The rescue equipment is not in a conspicuous place and readily accessible. Shepherd's crook is not acceccible to pool patrons.

      Correction: Maintain rescue equipment in a conspicuous and accessible location.

      Code ATCP 76.26(1)(a)2. - RESCUE EQPT ACCESSIBLE

    • Not serious Non-critical

      VGBA DRAIN COVER INFO-LIFESPAN

      The VGBA log or other proof does not indicate drain cover life span.

      Correction: Indicate in the log the drain cover life span.

      Code ATCP 76.38(2)(b)4. - LIFESPAN

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is 0.2 ppm for chlorine (erosion).

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      RING BOUY

      There is no rope attached to ring buoy.

      Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.

      Code ATCP 76.26(1)(b)2.a - RING BOUY

  5. Aug 7, 2023 Routine · 1 non-critical
    • Not serious Non-critical

      DISINFECTANT FEEDER NOT ELECTRICALLY CONNECTED

      The disinfectant feeder pump is not electrically connected to the recirculation pump control circuit.

      Correction: Electrically connect the disinfectant feeder to the recirculation pump so it cannot keep running when the recirculation pump is turned off.

      Code ATCP 76.13(1)(c)

Source: North Shore Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.