Glen Hills Middle School
2600 W MILL RD, Glendale, WI 53209 · Milwaukee County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- North Shore Health Department
- License / ID
- HSAT-7QXKNQ
- Status
- Permitted
- Phone
- (414) 351-7545
- Official record
- North Shore Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 4 | 1 |
| 2024 | 1 | 4 | 0 |
| 2023 | 2 | 4 | 1 |
Inspections
-
Feb 10, 2026 Re-inspection · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is 250 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water. 2/10/26: At re-inspection, alkalinity was slightly elevated at 190 ppm. Person in charge adjusted pH on controller.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Repeat
-
Feb 2, 2026 Routine · 1 critical, 2 non-critical, 1 repeat
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is 250 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Serious
Critical
PH
The pH is 8.6
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Not serious
Non-critical
-
Dec 3, 2024 Routine · 4 non-critical
-
Not serious
Non-critical
INTERLOCKED-ELECTRICAL
Power to recirculation system is not interlocked with the power to the chemical feed.
Correction: Provide interlock between the power to the recirculation system and power to the chemical feeder(s).
Code ATCP 76.13 (1)(c)1.a. - ELECTRICAL INTERLOCK PRESENT
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is [230 ppm].
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant on Saturday's. The facility may obtain testing logs from Nicolet.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
-
Dec 13, 2023 Re-inspection · No items found
No violations cited.
-
Oct 31, 2023 Routine · 1 critical, 3 non-critical
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
POOL RULES POSTED
The pool rules are not posted.
Correction: Post the pool rules. Rules shall be posted in the pool area.
Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED
-
Not serious
Non-critical
DRINKING FOUNTAIN MAINTAINED
The drinking fountain is not in clean and sanitary condition. The basin for the fountain is rusted.
Correction: Maintain the drinking fountain in clean and sanitary condition.
Code ATCP 76.33(1)(g)2.-DRINKING FOUNTAIN CLEAN
-
Serious
Critical
PH
The pH is [>8.0 ].
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Not serious
Non-critical
Source: North Shore Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.