Four Points By Sheraton Milwaukee North - Indoor Pool
8900 N KILDEER CT, Brown Deer, WI 53209 · Milwaukee County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- North Shore Health Department
- License / ID
- BSIY-BMLRFP
- Status
- Permitted
- Official record
- North Shore Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 9 | 2 |
| 2025 | 2 | 12 | 3 |
| 2024 | 2 | 11 | 0 |
| 2023 | 2 | 5 | 1 |
Inspections
-
Sep 24, 2026 Routine · 2 critical, 7 non-critical, 2 repeat
-
Not serious
Non-critical
SKIMMER POOL RECIRCULATION FLOW
Proportion of water recirculating from skimmer and main drain is at 100% for both main drain and skimmer.
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available
Correction: Provide a spare strainer or screen
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not functional. However, the pump has a flow indicator through an app, but this is not and indication of how many gallons are moving within this system. But a preprogrammed app based on RPM of the motor.
Correction: Repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises. The pump curve was obtained online.
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
POOL BASIN MAINTAINED FREE OF DEFECTS
Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There is a portion of the basin wall missing.
Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.
Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. It appears the ORP is calling for acid but the chemical feeder is not working.
Correction: Maintain the pool equipment.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Serious
Critical
PH
The pH is [>8.0 ].
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
MAXIMUM CHLORINE
The maximum chlorine residual exceeds 10 ppm and is at 12.5 ppm.
Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE
-
Not serious
Non-critical
-
Aug 4, 2025 Re-inspection · 1 critical, 3 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The flowmeter is reading 30 gpm. The pool is 14,000 gallons. The flow rate is 7.7 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of 6 hours. Facility requested 60 days to replace pumps.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Serious
Critical
Repeat
DRINKING FOUNTAIN PROVIDED
The drinking fountain does not work.
Correction: Repair drinking fountain. New fountain is ordered.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Not serious
Non-critical
Repeat
-
Jul 21, 2025 Routine · 2 critical, 6 non-critical
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The flowmeter is reading 30 gpm. The pool is 14,000 gallons. The flow rate is 7.7 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of 6 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. Some reagents have expired.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
POSTING SIGNAGE-MAX PATRON LOAD
Maximum patron load is not posted.
Correction: Post signage indicating Maximum patron load.
Code ATCP 76.29(1)(e) - MAX PATRON LOAD
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
POOL DECK-DEPTH MARKINGS MAINTAINED
Pool deck area not maintained so that depth markings along the edge of the pool are clearly visible and readable.
Correction: Maintain pool deck area so that depth markings along the edge of the pool are clearly visible and readable.
Code ATCP 76.33(1)(b)4. - DEPTH MARKINGS
-
Serious
Critical
DRINKING FOUNTAIN PROVIDED
The drinking fountain does not work.
Correction: Repair drinking fountain.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Serious
Critical
Corrected on site
GATES AND DOORS-LOCKABLE
The door was propped open at the time of the inspection. The only other mens restroom available to public is out of order. Staff are redirecting the public to the indoor pool to use the restroom.
Correction: Keep door closed and locked at all times. Educational moment.
Code ATCP 76.34(4)(a)(1m)(c)- LOCKABLE
-
Not serious
Non-critical
-
Jul 11, 2024 Re-inspection · 4 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
POOL RULES LETTER OR SYMBOL SIZE
Pool rules letters are less than one inch in height.
Correction: Correct the size of the letters or symbols, so that letters are at least one inch in height and symbols are at least 4 inches in height. NEW SIGN ORDERED AND WILL SEND PICTURE OF CORRECTION WHEN HUNG.
Code ATCP 76.29(1)(a)2. -LETTER OR SYMBOL SIZE
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding. SIGN ORDERED AND WILL SEND PICTURE WHEN IT IS HUNG.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
POOL EQUIPMENT-REPAIRED AS NECESSARY
Vent pipe for fuel burning appliance in the pump room requires replacement because it has eroded and is setting off the carbon monoxide detector.
Correction: Repair or replace duct.
Code ATCP 76.33(1)(e)4. - EQPT REPAIRED AS NEEDED
-
Not serious
Non-critical
Repeat
-
Jun 27, 2024 Routine · 7 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not working.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use. The pool is not being tested on the weekends. There is also times when staff are not onsite to test.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Not serious
Non-critical
POOL RULES LETTER OR SYMBOL SIZE
Pool rules letters are less than one inch in height.
Correction: Correct the size of the letters or symbols, so that letters are at least one inch in height and symbols are at least 4 inches in height.
Code ATCP 76.29(1)(a)2. -LETTER OR SYMBOL SIZE
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
POOL EQUIPMENT-REPAIRED AS NECESSARY
Vent pipe for fuel burning appliance in the pump room requires replacement because it has eroded and is setting off the carbon monoxide detector.
Correction: Repair or replace duct.
Code ATCP 76.33(1)(e)4. - EQPT REPAIRED AS NEEDED
-
Not serious
Non-critical
-
Aug 9, 2023 Re-inspection · 2 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
HAZARDOUS OBJECT OR MATERIAL IN THE POOL AREA
A feeder was added to the return line. This feeder is unknown and not NSF approved.
Correction: Remove feeder from the pool. The feeder was bypassed at the time of inspection and not in use.
Code ATCP 76.34(1)
-
Not serious
Non-critical
Repeat
SIGNAGE - LETTERS TOO SMALL
The letters on the pool rules signage are less than 1-inch in height.
Correction: Reprint the sign in compliance with ATCP 76.29(1)(b).
Code [A] ATCP 76.29(1)(b)
-
Not serious
Non-critical
Repeat
-
Aug 7, 2023 Routine · 1 critical, 2 non-critical
-
Not serious
Non-critical
HAZARDOUS OBJECT OR MATERIAL IN THE POOL AREA
A feeder was added to the return line. This feeder is unknown and not NSF approved.
Correction: Remove feeder from the pool. The feeder was bypassed at the time of inspection and not in use.
Code ATCP 76.34(1)
-
Not serious
Non-critical
SIGNAGE - LETTERS TOO SMALL
The letters on the pool rules signage are less than 1-inch in height.
Correction: Reprint the sign in compliance with ATCP 76.29(1)(b).
Code [A] ATCP 76.29(1)(b)
-
Serious
Critical
SKIMMER COVERS NOT SECURE
The main drain cover is missing.
Correction: Secure covers so they are not easily removed. Visual re-inspection required prior to opening. Pool was closed.
Code [C] ATCP 76.11(2)(b)
-
Not serious
Non-critical
Source: North Shore Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.