Park Plaza Apartments Pool

8901 PARK PLAZA CT, Brown Deer, WI 53223 · Milwaukee County

40cited violations
9serious tier
8inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
North Shore Health Department
License / ID
SYOG-7QRUVW
Status
Permitted
Phone
(414) 354-3970
Official record
North Shore Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026271
2025140
20243175
20232123

Inspections

  1. Aug 21, 2026 Re-inspection · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. Make, model, installation date, and lifespan of equalizer covers not available.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises. 8/21/2026 - Drain cover documentation is present. Operator is still attempting to locate equalizer information.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

  2. Jul 29, 2026 Routine · 1 critical, 5 non-critical, 1 repeat
    • Not serious Non-critical Corrected on site

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. At time of inspection, the turnover rate was 7.36 hours.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate. Person in charge backwashed the filters during the inspection, which raised the flow rate to 150 gallons per minute and turnover rate subsequently decreased to 5.8 hours.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical Repeat

      REAGENTS REPLACED

      Test kit reagents not replaced as recommended by the manufacturer. Two of the reagents are expired: pH indicator and sodium thiosulfate.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical

      POSTING SIGNAGE-MAX PATRON LOAD

      Maximum patron load is not posted.

      Correction: Post signage indicating Maximum patron load.

      Code ATCP 76.29(1)(e) - MAX PATRON LOAD

    • Not serious Non-critical

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. Make, model, installation date, and lifespan of equalizer covers not available.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Serious Critical

      TELEPHONE ACCESSIBLE

      A telephone or other approved communication technology capable of connecting to emergency services is not working.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services. The pool shall remain closed until the emergency phone is working.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

  3. Jul 10, 2025 Routine · 4 non-critical, 2 repeat
    • Not serious Non-critical Corrected on site

      SKIMMER POOL RECIRCULATION FLOW

      Proportion of water recirculating from skimmer and main drain is mostly from the main drain.

      Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer. Skimmer to main drain ratio was adjusted during the inspection.

      Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW

    • Not serious Non-critical

      REAGENTS REPLACED

      Test kit reagents not replaced as recommended by the manufacturer. Several reagents in test kit are expired.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding was not posted in a visible location. During the inspection, it was found in the mechanical room.

      Correction: Provide signage or provide other communication warning against prolonged breath holding. Operator will relocate the sign to a location in the pool area where it is visible to patrons.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There is chipping of paint on surface of pool basin.

      Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

  4. Aug 13, 2024 Re-inspection 2 · 1 critical, 4 non-critical, 4 repeat
    • Not serious Non-critical Repeat

      SKIMMERS MAINTAINED CLEAN

      Skimmers, gutters, drains not maintained clean. Debris floatin in the skimmers.

      Correction: Maintain the skimmers in clean condition.

      Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding. SIGN IS ORDERED.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There is some chipping of paint in the pool basin.

      Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Not serious Non-critical Repeat

      VGBA DRAIN COVER INFO-LIFESPAN

      The VGBA log or other proof does not indicate drain cover life span.

      Correction: Indicate in the log the drain cover life span. The health department will provide new log. VGBA INFO PROVIDED AND DRAIN COVERS REQUIRE REPLACEMENT BEFORE OPENING NEXT YEAR.

      Code ATCP 76.38(2)(b)4. - LIFESPAN

    • Serious Critical

      WATER CLARITY

      Pool water not transparent and free from cloudiness. Main drain grating and outline not readily visible from pool deck.

      Correction: Close the pool until the pool water is transparent and free from cloudiness and so that main drain grating and outline are readily visible from pool deck. WATER STILL CLOUDY SINCE PUMP IS REPAIRED. MANAGER STATED THE POOL WILL NOT OPEN UNTIL CLEAR AND THE MAIN DRAINS ARE VISIBLE.

      Code ATCP 76.16 (2) - CLARITY

  5. Aug 12, 2024 Re-inspection · 3 critical, 4 non-critical, 3 repeat
    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding. SIGN IS ORDERED.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      VGBA DRAIN COVER INFO-LIFESPAN

      The VGBA log or other proof does not indicate drain cover life span.

      Correction: Indicate in the log the drain cover life span. The health department will provide new log. VGBA INFO PROVIDED AND DRAIN COVERS REQUIRE REPLACEMENT BEFORE OPENING NEXT YEAR.

      Code ATCP 76.38(2)(b)4. - LIFESPAN

    • Not serious Non-critical Repeat

      SKIMMERS MAINTAINED CLEAN

      Skimmers, gutters, drains not maintained clean. Debris floatin in the skimmers.

      Correction: Maintain the skimmers in clean condition.

      Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN

    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There is some chipping of paint in the pool basin.

      Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Serious Critical

      RECIRCULATION SYSTEM CONTINUOUS OPERATION

      The pool recirculation system is not operational and was open to the public.

      Correction: The pool must be closed immediately until the recirculation system is in place and in continuous operation.

      Code ATCP 76.11(1) - RECIRCULATION SYSTEM PRESENT, CONTINUOUSLY O

    • Serious Critical

      WATER CLARITY

      Pool water not transparent and free from cloudiness. Main drain grating and outline not readily visible from pool deck.

      Correction: Close the pool until the pool water is transparent and free from cloudiness and so that main drain grating and outline are readily visible from pool deck.

      Code ATCP 76.16 (2) - CLARITY

    • Serious Critical Repeat

      TELEPHONE ACCESSIBLE

      A telephone capable of connecting to emergency services is not working. Tested the phone and it does not connect to 9-1-1.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services. TELEPHONE STILL DID NOT CONNECT TO 9-1-1.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

  6. Aug 5, 2024 Routine · 1 critical, 4 non-critical
    • Not serious Non-critical

      SKIMMERS MAINTAINED CLEAN

      Skimmers, gutters, drains not maintained clean. Debris floatin in the skimmers.

      Correction: Maintain the skimmers in clean condition.

      Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Pool basin not Maintained free of cracks or other defects and repaired or refinished as necessary to maintain it in a cleanable condition. There is some chipping of paint in the pool basin.

      Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Not serious Non-critical

      VGBA DRAIN COVER INFO-LIFESPAN

      The VGBA log or other proof does not indicate drain cover life span.

      Correction: Indicate in the log the drain cover life span. The health department will provide new log.

      Code ATCP 76.38(2)(b)4. - LIFESPAN

    • Serious Critical

      TELEPHONE ACCESSIBLE

      A telephone capable of connecting to emergency services is not working. Tested the phone and it does not connect to 9-1-1.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

  7. Jul 12, 2023 Re-inspection · 1 critical, 3 non-critical, 4 repeat
    • Not serious Non-critical Repeat

      RESCUE EQUIPMENT NOT ACCESSIBLE

      The rope for the ring buoy is old and not in good condition.

      Correction: Replace rope.

      Code ATCP 76.26(1)(a)

    • Not serious Non-critical Repeat

      SKIMMER/MAIN DRAIN RATIO INCORRECT

      The skimmer to main drain flow ration is not set correctly. The main drain is open more than 20%.

      Correction: Readjust the flow so that only 20% comes through the main drain and 80% comes through the skimmers.

      Code [A] ATCP 76.11(2)(a)

    • Not serious Non-critical Repeat

      CRACKS OR PITTING IN THE POOL BASIN

      The pool basin is pitted or damaged.

      Correction: Repair the pool basin so it is finished and easily cleanable.

      Code [B] ATCP 76.33(1)(a)

    • Serious Critical Repeat

      TELEPHONE NOT WORKING

      The emergency telephone does not work.

      Correction: Provide a functional emergency telephone immediately.

      Code [A] ATCP 76.26(2)

  8. Jul 10, 2023 Routine · 2 critical, 6 non-critical
    • Not serious Non-critical

      WATER TESTING FREQUENCY - POOLS

      The water testing log not available for review during the inspection.

      Correction: Maintain testing logs.

      Code ATCP 76.18(1)

    • Not serious Non-critical

      RESCUE EQUIPMENT NOT ACCESSIBLE

      The rope for the ring buoy is old and not in good condition.

      Correction: Replace rope.

      Code ATCP 76.26(1)(a)

    • Not serious Non-critical

      LIGHTING

      The lighting housing in the pool is not maintained in good repair and sealed to the pool basin.

      Correction: Maintain all lighting in operating condition.

      Code ATCP 76.33(4)(c)

    • Not serious Non-critical

      SKIMMER/MAIN DRAIN RATIO INCORRECT

      The skimmer to main drain flow ration is not set correctly. The main drain is open more than 20%.

      Correction: Readjust the flow so that only 20% comes through the main drain and 80% comes through the skimmers.

      Code [A] ATCP 76.11(2)(a)

    • Not serious Non-critical

      DRINKING FOUNTAIN NOT FUNCTIONAL

      The drinking fountain has been removed.

      Correction: Replace the drinking fountain.

      Code [A] ATCP 76.33(1)(g)

    • Not serious Non-critical

      CRACKS OR PITTING IN THE POOL BASIN

      The pool basin is pitted or damaged.

      Correction: Repair the pool basin so it is finished and easily cleanable.

      Code [B] ATCP 76.33(1)(a)

    • Serious Critical

      SKIMMERS/GUTTERS NOT CLEANED

      Skimmers are not clean. The main drain cover is missing screws and this is an imminent health hazard.

      Correction: Maintain in a clean condition. The main drain cover shall be maintained in good condition. The main drain cover shall be repaired according to the manufactures certification. The pool shall remain closed until re-inspection is made.

      Code [A] ATCP 76.11(2)(b)

    • Serious Critical

      TELEPHONE NOT WORKING

      The emergency telephone does not work.

      Correction: Provide a functional emergency telephone immediately.

      Code [A] ATCP 76.26(2)

Source: North Shore Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.