  1. Jun 4, 2026 Routine · 3 non-critical
    • Serious Critical

      FBA vent to outdoors

      The FBA dryer in main laundry was not properly shielded from open flame. The facility obtained a new, smaller dryer and a portion of the wall is missing. This different size dryer creates an opening so that combustion air can not be properly vented. Also, the lever vent to the outside was full of lint and requires cleaning.

      Correction: Install the fuel-burning appliances in accordance with the manufacturer’s installation specifications to vent outdoors. Cover this portion of the dryer to meet the manufactures specs.

      Code ATCP 72.18(10)(a)1.

    • Not serious Non-critical

      Sleeping rooms maintained in good repair

      Many sleeping rooms are not maintained in good repair. Stained couches, smoke detection hanging from the wall, cracked shower tubs.

      Correction: Maintain all sleeping rooms in good repair.

      Code ATCP 72.19(1)(a)2.

    • Not serious Non-critical

      Pest control - openable windows screened

      The window in 226 is not screened.

      Correction: All openable windows within in individually keyed units need to have a screen.

      Code ATCP 72.19(2)(a)3.b.

  2. Oct 9, 2025 Re-inspection · 3 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      SMOKE DETECTORS - REQUIREMENT

      Smoke detector in room 228 was beeping, indicating that it is not working properly.

      Correction: Provide operational smoke detectors in all sleeping rooms and required locations.

      Code ATCP 72.14 (2) (c)

    • Not serious Non-critical Repeat

      WINDOW SCREENING

      Window screen missing from rooms 304, 407. These rooms opened to the outside at the time of the inspection.

      Correction: Provide screening on all windows that can be opened to the outside.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical Repeat

      CLEANLINESS OF EQUIPMENT AND FURNISHINGS

      The furniture in room 200 is stained and soiled with splatter of a substance.

      Correction: Maintain equipment and furnishings in a clean condition.

      Code [B] ATCP 72.11 (6)

  3. Oct 1, 2025 Routine · 5 non-critical, 1 repeat
    • Not serious Non-critical

      SMOKE DETECTORS - REQUIREMENT

      Smoke detector in room 228 was beeping, indicating that it is not working properly.

      Correction: Provide operational smoke detectors in all sleeping rooms and required locations.

      Code ATCP 72.14 (2) (c)

    • Not serious Non-critical

      WINDOW SCREENING

      Window screen missing from rooms 304, 407. These rooms opened to the outside at the time of the inspection.

      Correction: Provide screening on all windows that can be opened to the outside.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical

      CLEANLINESS OF EQUIPMENT AND FURNISHINGS

      The furniture in room 200 is stained and soiled with splatter of a substance.

      Correction: Maintain equipment and furnishings in a clean condition.

      Code [B] ATCP 72.11 (6)

    • Not serious Non-critical

      GENERAL MAINTENANCE

      The handrail in the tub of room 125 is not maintained or in good repair.

      Correction: Maintained establishment in a manner conducive to the health, comfort and safety of its guests.

      Code [C] ATCP 72.15 (1)

    • Not serious Non-critical Repeat

      VENTILATION - MAINTAINED

      The vent screen behind the dryers is clogged with lint. This screen requires more frequently. The screen must remain clear to allow the exit of potential carbon monoxides.

      Correction: Clean vent screen.

      Code [T] ATCP 72.14 (1)

  4. Oct 22, 2024 Routine · 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      CLEANLINESS OF LINENS - DIRTY

      Linens in 401 are stained.

      Correction: Linens must be changed between different guests and at least once per week. Provide clean linen in identified rooms before new occupancy.

      Code [B] ATCP 72.11 (5)

    • Not serious Non-critical Repeat Corrected on site

      VENTILATION - MAINTAINED

      Ventilation system for the dryer was clogged. Facility cleans once and week. It was recommended to clean twice per week.

      Correction: Repair ventilation system to working order.

      Code [T] ATCP 72.14 (1)

  5. Feb 23, 2024 Follow Up · 3 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      INSECT AND RODENT CONTROL

      Weather stripping missing on some of the door leading to the outside.

      Correction: Contact a pest control company to evaluate and eliminate the presence and harborage of insects and rodents.

      Code ATCP 72.15 (3)

    • Not serious Non-critical Repeat

      MATTRESS PAD PROVIDED/SUFFICIENT SIZE

      Mattress pad does not completely cover mattress.

      Correction: Provide a mattress pad that completely covers the mattress.

      Code [H] ATCP 72.11 (5)

    • Not serious Non-critical Repeat

      VENTILATION - MAINTAINED

      Exhaust louver was inoperative behind the dryers.

      Correction: Repair ventilation system to working order.

      Code [T] ATCP 72.14 (1)

  6. Sep 27, 2023 Re-inspection 2 · 2 non-critical
    • Not serious Non-critical

      CLEANLINESS OF EQUIPMENT AND FURNISHINGS

      Carpet and couches in many areas are soiled.

      Correction: Maintain equipment and furnishings in a clean condition or replace. WILL BE PART OF THE INTERIOR RENOVATION.

      Code [B] ATCP 72.11 (6)

    • Not serious Non-critical

      PREMISE – EXTERIOR BUILDING

      Exterior is not maintained or in good repair. The pilar in the back of the building requires repair

      Correction: Repair and maintain the exterior of all buildings. THIS REPAIR IS DECORATIVE AND NOT STRUCTURAL. THE FACILITY WILL REPAIR WHEN THE UPDATE OCCURS.

      Code [D] ATCP 72.15 (4)

  7. Sep 22, 2023 Re-inspection · 2 critical, 9 non-critical, 11 repeat
    • Not serious Non-critical Repeat

      WINDOW SCREENING

      Window screen missing. There is a pattern of noncompliance. The screens were originally removed with the intent to bolt the windows closed. The windows were not bolted and could be opened.

      Correction: Provide screening on all windows that can be opened to the outside or bolt all windows in all rooms.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical Repeat

      ROOMS IN A CLEAN CONDITION

      Room 234 is not maintained in a clean and sanitary condition. There was food debris on floor, the garbage's were not emptied, sour cream lid found near the bed, a dark slide found on nightstand.

      Correction: Maintain all sleeping rooms in a clean and sanitary condition.

      Code [A] ATCP 72.15 (2)

    • Not serious Non-critical Repeat

      CLEANLINESS OF LINENS - DIRTY

      Sheets were stained and not clean in a ready to rent room.

      Correction: Linens must be changed between different guests and at least once per week. Provide clean linen in identified rooms before new occupancy.

      Code [B] ATCP 72.11 (5)

    • Not serious Non-critical Repeat

      CLEANLINESS OF EQUIPMENT AND FURNISHINGS

      Carpet and couches in many arreas are soiled.

      Correction: Maintain equipment and furnishings in a clean condition or replace.

      Code [B] ATCP 72.11 (6)

    • Not serious Non-critical Repeat

      PLUMBING FIXTURES – SANITARY CONDITION

      The ice machine on the 2nd floor is not properly air gapped. The splash guard near the ice chute is broken and requires repair to be easily cleanable.

      Correction: Maintain plumbing and fixtures in a sanitary condition.

      Code [C] ATCP 72.10 (4)

    • Not serious Non-critical Repeat

      PREMISE – EXTERIOR BUILDING

      Exterior is not maintained or in good repair. The pilar in the back of the building requires repair

      Correction: Repair and maintain the exterior of all buildings.

      Code [D] ATCP 72.15 (4)

    • Not serious Non-critical Repeat

      MATTRESS PAD PROVIDED/SUFFICIENT SIZE

      Mattress pad does not completely cover mattress in room 210. Mattress pad is missing in room 307.

      Correction: Provide a mattress pad that completely covers the mattress. Provide mattress pads in each room.

      Code [H] ATCP 72.11 (5)

    • Not serious Non-critical Repeat

      FIRE ALARM – TESTING LOG

      Log of fire alarm testing was absent, incomplete, or unavailable.

      Correction: Log of fire alarm testing is required per NFPA requirements. Log needs to include date, specific location of testing, results, corrective action, and name of person conducting test. Store log in fire proof location and retrieve per request of regulatory officials.

      Code [P] ATCP 72.14 (1)

    • Not serious Non-critical Repeat

      VENTILATION - MAINTAINED

      Exhaust louver behind the dryer is not maintained and is full of dryer lint. This unit is no longer able to properly exhaust to the outside without being cleaned. Vents in rooms have a build-up of mold.

      Correction: Clean and maintain ventilation systems.

      Code [T] ATCP 72.14 (1)

    • Serious Critical Repeat

      SMOKE DETECTORS - REQUIREMENT

      A general pattern of noncompliance. Smoke detectors found to have a manufactures date of 1992 and 2002. Smoke detectors require replacement after 10 years.

      Correction: Provide operational smoke detectors in all sleeping rooms and required locations. Provide proof of replacement for all rooms in the building that require new smoke detectors. State Law requires expired smoke detectors to be replaced in 5 days. See comments.

      Code ATCP 72.14 (2) (c)

    • Serious Critical Repeat

      FIRE ALARM – WORKING ORDER

      The fire alarm system panel was in "trouble" status and in "supervisory" status. "Supervisory" status is for the approved disconnection for the sprinkler system in the pool, however the "trouble" indicator is unknown.

      Correction: Repair the fire alarm system immediately.

      Code [O] ATCP 72.14 (1)

  8. Sep 13, 2023 Routine · 2 critical, 11 non-critical
    • Not serious Non-critical

      TOILET FACILITIES - SOAP AND TOWELS

      Soap not provided in the toilet rooms in lobby.

      Correction: Provide soap, single-service towels, or other approved means of drying hands in each toilet room.

      Code ATCP 72.10 (6) (d)

    • Not serious Non-critical

      WINDOW SCREENING

      Window screen missing. There is a pattern of noncompliance. The screens were originally removed with the intent to bolt the windows closed. The windows were not bolted and could be opened.

      Correction: Provide screening on all windows that can be opened to the outside or bolt all windows in all rooms.

      Code ATCP 72.14 (2) (e)

    • Not serious Non-critical

      ROOMS IN A CLEAN CONDITION

      Room 234 is not maintained in a clean and sanitary condition. There was food debris on floor, the garbage's were not emptied, sour cream lid found near the bed, a dark slide found on nightstand.

      Correction: Maintain all sleeping rooms in a clean and sanitary condition.

      Code [A] ATCP 72.15 (2)

    • Not serious Non-critical

      CLEANLINESS OF LINENS - DIRTY

      Sheets were stained and not clean in a ready to rent room.

      Correction: Linens must be changed between different guests and at least once per week. Provide clean linen in identified rooms before new occupancy.

      Code [B] ATCP 72.11 (5)

    • Not serious Non-critical

      CLEANLINESS OF EQUIPMENT AND FURNISHINGS

      Carpet and couches in many arreas are soiled.

      Correction: Maintain equipment and furnishings in a clean condition or replace.

      Code [B] ATCP 72.11 (6)

    • Not serious Non-critical

      PLUMBING FIXTURES – SANITARY CONDITION

      The ice machine on the 2nd floor is not properly air gapped. The splash guard near the ice chute is broken and requires repair to be easily cleanable.

      Correction: Maintain plumbing and fixtures in a sanitary condition.

      Code [C] ATCP 72.10 (4)

    • Not serious Non-critical

      GENERAL MAINTENANCE

      Phones not working in many rooms.

      Correction: Maintained establishment in a manner conducive to the health, comfort and safety of its guests. Repair premises and replace or repair phones throughout.

      Code [C] ATCP 72.15 (1)

    • Not serious Non-critical

      PREMISE – EXTERIOR BUILDING

      Exterior is not maintained or in good repair. The pilar in the back of the building requires repair

      Correction: Repair and maintain the exterior of all buildings.

      Code [D] ATCP 72.15 (4)

    • Not serious Non-critical

      MATTRESS PAD PROVIDED/SUFFICIENT SIZE

      Mattress pad does not completely cover mattress in room 210. Mattress pad is missing in room 307.

      Correction: Provide a mattress pad that completely covers the mattress. Provide mattress pads in each room.

      Code [H] ATCP 72.11 (5)

    • Not serious Non-critical

      FIRE ALARM – TESTING LOG

      Log of fire alarm testing was absent, incomplete, or unavailable.

      Correction: Log of fire alarm testing is required per NFPA requirements. Log needs to include date, specific location of testing, results, corrective action, and name of person conducting test. Store log in fire proof location and retrieve per request of regulatory officials.

      Code [P] ATCP 72.14 (1)

    • Not serious Non-critical

      VENTILATION - MAINTAINED

      Exhaust louver behind the dryer is not maintained and is full of dryer lint. This unit is no longer able to properly exhaust to the outside without being cleaned. Vents in rooms have a build-up of mold.

      Correction: Clean and maintain ventilation systems.

      Code [T] ATCP 72.14 (1)

    • Serious Critical

      SMOKE DETECTORS - REQUIREMENT

      A general pattern of noncompliance. Smoke detectors found to have a manufactures date of 1992 and 2002. Smoke detectors require replacement after 10 years.

      Correction: Provide operational smoke detectors in all sleeping rooms and required locations. Provide proof of replacement for all rooms in the building that require new smoke detectors. State Law requires expired smoke detectors to be replaced in 5 days. See comments.

      Code ATCP 72.14 (2) (c)

    • Serious Critical

      FIRE ALARM – WORKING ORDER

      The fire alarm system panel was in "trouble" status and in "supervisory" status. "Supervisory" status is for the approved disconnection for the sprinkler system in the pool, however the "trouble" indicator is unknown.

      Correction: Repair the fire alarm system immediately.

      Code [O] ATCP 72.14 (1)