Gables At Oak Creek
50 E FIELD STONE CIRCLE, Oak Creek, WI 53154 · Milwaukee County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Oak Creek Health Department
- License / ID
- HSAT-7QWJVK
- Status
- Permitted
- Phone
- (414) 762-0033
- Official record
- Oak Creek Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 3 | 2 |
| 2025 | 3 | 12 | 5 |
| 2024 | 2 | 14 | 4 |
| 2023 | 1 | 3 | 0 |
Inspections
-
Jun 26, 2026 Follow Up · No items found
No violations cited.
-
Jun 25, 2026 Routine · 2 critical, 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. Water flow to the flowmeter was turned off and when turned on, the bobber did not move from the bottom.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Serious
Critical
Corrected on site
PH
The pH is below 7.0. The test water sample was yellow.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better. Soda ash is being added to the pool water. Pool was closed.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
TELEPHONE ACCESSIBLE
A telephone or other approved communication technology capable of connecting to emergency services is not working.
Correction: Provide a working telephone or other technology capable of connecting with emergency services. With a push button phone, a DATCP approved variance is required. Pool is closed until the emergency phone is working.
Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE
-
Not serious
Non-critical
Repeat
-
Jul 25, 2025 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. Reagents are expired. Still using kit from last year.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
Repeat
-
Jun 26, 2025 Re-inspection · 2 critical, 2 non-critical, 4 repeat
-
Not serious
Non-critical
Repeat
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. Reagents are expired. Still using kit from last year.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
Repeat
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Serious
Critical
Repeat
WATER SUPPLY PROTECTION
Approved backflow or backsiphonage protection does not exist between potable water supply inlet and the overflow point of pool.
Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool. Air gap would be sufficient.
Code ATCP 76.19(1) - PROTECTION
-
Serious
Critical
Repeat
GATES AND DOORS EXIT
A key is required to exit a pool enclosure.
Correction: Provide an exit from the pool enclosure that does not require a key, punch code, or electronic method to exit a pool enclosure.
Code ATCP 76.34(4)(a)(1m)(d)- EXIT UNRESTRICTED
-
Not serious
Non-critical
Repeat
-
Jun 24, 2025 Routine · 3 critical, 4 non-critical, 1 repeat
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition. The bobber is stuck.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. Reagents are expired. Still using kit from last year.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
RESCUE EQUIPMENT ACCESSIBLE
The rescue equipment is not in a conspicuous place and readily accessible. The shepards crook is laying outside of the fencing for the pool along side the pool pump buiding.
Correction: Maintain rescue equipment in a conspicuous and accessible location. Hang shepards crook inside the pool enclosure.
Code ATCP 76.26(1)(a)2. - RESCUE EQPT ACCESSIBLE
-
Not serious
Non-critical
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Serious
Critical
WATER SUPPLY PROTECTION
Approved backflow or backsiphonage protection does not exist between potable water supply inlet and the overflow point of pool.
Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool. Air gap would be sufficient.
Code ATCP 76.19(1) - PROTECTION
-
Serious
Critical
Repeat
HAZARDOUS CONDITION
There is a hazardous condition at the pool. Two screws out of 4 are missing from one of the main drain covers. The other main drain cover is missing 1 screw out of 4 screws. Equalizer covers had expired 5/19/24, from the latest information provided.
Correction: Correct the hazardous condition. Replace screws in main drain covers and replace equalizer covers if no documentation of replacement from the past year is provided.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Serious
Critical
GATES AND DOORS EXIT
A key is required to exit a pool enclosure.
Correction: Provide an exit from the pool enclosure that does not require a key, punch code, or electronic method to exit a pool enclosure.
Code ATCP 76.34(4)(a)(1m)(d)- EXIT UNRESTRICTED
-
Not serious
Non-critical
-
Jun 19, 2024 Follow Up · 1 critical, 2 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool. A template was given to the operator.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Repeat
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use. No testing is performed on the weekends.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Serious
Critical
Repeat
HAZARDOUS CONDITION
There is a hazardous condition at the pool. The equalizer covers were replaced on 5/16/19 with a SDX/Paramount cover and this cover is good for 5 years and has since expired.
Correction: Correct the hazardous condition. Monitor covers daily for defects/damage and note on pool log sheet until they are replaced. Replace covers ASAP or before next season.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
Repeat
-
Jun 12, 2024 Routine · 3 critical, 8 non-critical
-
Not serious
Non-critical
Corrected on site
SKIMMER POOL RECIRCULATION FLOW
Proportion of water recirculating from skimmer and main drain is 100% open for both skimmer and main drain.
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer. Main drain valve was closed most of the way to get to 80/20.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 40ppm..
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool. A template was given to the operator.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use. No testing is performed on the weekends.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
ALKALINITY TEST
Pool water not tested at least once a week for total alkalinity.
Correction: Test pool water at least once a week for total alkalinity.
Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Serious
Critical
CHEMICAL STORAGE ACCESS RESTRICTED
Chemical storage area access not restricted to authorized personnel. There is no lock on the overhead door, allowing access to swimmers.
Correction: Restrict access to chemical storage area to only authorized personnel.
Code ATCP 76.12 (2)(d) - ACCESS RESTRICTED
-
Serious
Critical
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Serious
Critical
HAZARDOUS CONDITION
There is a hazardous condition at the pool. The equalizer covers were replaced on 5/16/19 with a SDX/Paramount cover and this cover is good for 5 years and has since expired.
Correction: Correct the hazardous condition. Monitor covers daily for defects/damage and note on pool log sheet until they are replaced. Replace covers ASAP or before next season.
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
Corrected on site
-
Jun 13, 2023 Routine · 3 non-critical
-
Not serious
Non-critical
SAND FILTER BACKWASHING
The sand filter is not being backwashed in accordance with ATCP 76.11(6)(b). Operator was back washing after a rise of 3psi.
Correction: Backwash the sand filter in accordance with ATCP 76.11(6)(b).
Code ATCP 76.11(6)(b)
-
Not serious
Non-critical
ALKALINITY OUT OF BALANCE
The total alkalinity is 30ppm.
Correction: Maintain the total alkalinity between 60 and 180 ppm.
Code ATCP 76.14(4)(d)
-
Not serious
Non-critical
RECORD RETENTION
Copy of ATCP 76 was not available for review.
Correction: Keep records in accordance with ATCP 76.32(3).
Code [A] ATCP 76.32(3)
-
Not serious
Non-critical
Source: Oak Creek Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.