Centennial Park

500 E CENTENNIAL DR, Oak Creek, WI 53154 · Milwaukee County

11cited violations
4serious tier
5inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Oak Creek Health Department
License / ID
DCAI-8RJRC6
Status
Permitted
Phone
(414) 570-1500
Official record
Oak Creek Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026110
2025244
2024130
2023130

Inspections

  1. Jul 8, 2026 Routine · 1 non-critical
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. Was at 6.79 with a maximum allowed at 6.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate. Rick stated that one of the propellors in the pump is bad.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

  2. Jun 27, 2025 Follow Up · 2 critical, 2 repeat
    • Serious Critical Repeat

      WATER SUPPLY PROTECTION

      Approved backflow or backsiphonage protection does not exist between potable water supply inlet and the pipe going to the pool. A hose is used and the end of the hose is below the top of the inlet pipe.

      Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool. Install a hose bib at the faucet. Operator is to obtain a hose bib today and install.

      Code ATCP 76.19(1) - PROTECTION

    • Serious Critical Repeat

      HAZARDOUS CONDITION

      There is a hazardous condition at the pool. The latest records indicate that the main drain covers and equalizer covers all expired 5/2025.

      Correction: Correct the hazardous condition by replacing the main drain covers and equalizer covers. All covers were observed today in good condition and the pool will be allowed to stay open under conditions, which are: The operator must log daily inspection of the main drain covers and equalizer covers to ensure no cracks, breaks, missing screws, or other visible damage or defects are observed. The operator

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  3. Jun 26, 2025 Routine · 2 critical
    • Serious Critical

      WATER SUPPLY PROTECTION

      Approved backflow or backsiphonage protection does not exist between potable water supply inlet and the pipe going to the pool. A hose is used and the end of the hose is below the top of the inlet pipe.

      Correction: Provide approved backflow and backsiphonage protection between the water supply and the overflow point of any pool. Install a hose bib at the faucet. Operator is to obtain a hose bib today and install.

      Code ATCP 76.19(1) - PROTECTION

    • Serious Critical

      HAZARDOUS CONDITION

      There is a hazardous condition at the pool. The latest records indicate that the main drain covers and equalizer covers all expired 5/2025.

      Correction: Correct the hazardous condition by replacing the main drain covers and equalizer covers. All covers were observed today in good condition and the pool will be allowed to stay open under conditions, which are: The operator must log daily inspection of the main drain covers and equalizer covers to ensure no cracks, breaks, missing screws, or other visible damage or defects are observed. The operator

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  4. Jul 10, 2024 Routine · 3 non-critical
    • Not serious Non-critical

      SPARE STRAINER BASKET OR SCREEN AVAILABLE

      Spare strainer or screen not available

      Correction: Provide a spare strainer or screen

      Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN

    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation turnover rate has not been met. With the reading of 65gpm from the flow meter, the turnover rate is about 12 hours. Formula to calculate turn over: 48929 (gallon of water in pool) divided by 65 (flow meter reading) divided by 60 minutes = 12.5 (TO)

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate. A minimum of 6 hours is required.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      WATER LEVEL-SKIMMERS MAINTAINED

      Water level in a skimmer pool is not allowing for effective skimming. Water level is too high.

      Correction: Maintain the water level in the pool so that the skimmer weir is half submerged, or, in the case of a floating weir, used according to manufacturer's instructions.

      Code ATCP 76.19(3)(a) - SKIMMERS MAINTAINED

  5. Jul 11, 2023 Routine · 3 non-critical
    • Not serious Non-critical Corrected on site

      RECIRCULATION RATE NOT MET - POOLS

      The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours. Initial reading was 115gpm and was increased to 145gpm to get to under 6 hours or turn over.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

    • Not serious Non-critical

      WATER TESTING FREQUENCY - POOLS

      The water testing frequency is not in compliance with ATCP 76.18(1). Some of the weekends and most of the daily 2X checks are not being performed.

      Correction: Perform water testing in accordance with ATCP 76.18(1). Without a controller, 2X/day water chemistry checks are required and all days that the pool is open for swimming including weekends.

      Code ATCP 76.18(1)

    • Not serious Non-critical

      SPARE STRAINER BASKET - REQUIREMENT

      A spare strainer basket or screen for the skimmers or the recirculation pump is not located on site.

      Correction: Provide a spare basket or screen.

      Code [A] ATCP 76.11(2)(d)

Source: Oak Creek Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.