Hub 13 LLC
1310 W NICHOLAS DR, Oak Creek, WI 53154 · Milwaukee County
Establishment
- Type
- Pool / recreational water (Pool - Moderate with Features)
- Inspected by
- Oak Creek Health Department
- License / ID
- DPIN-CKEJ8K
- Status
- Permitted
- Phone
- (414) 433-8778
- Official record
- Oak Creek Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 4 | 3 |
| 2025 | 6 | 23 | 5 |
| 2024 | 2 | 16 | 2 |
| 2023 | 4 | 26 | 0 |
Inspections
-
Jun 17, 2026 Follow Up · No items found
No violations cited.
-
Jun 15, 2026 Routine · 3 critical, 1 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 547 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0.4ppm of chlorine. An hour later after turning on the pumps it was 0.2ppm.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Minimum level is 1.0ppm.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
FIRST AID KIT-PROVIDED IN POOL AREA
The first aid kit is missing from the pool area, or within 25 feet of enclosure with signage posted in the enclosure telling where the first aid kit is. First aid kit was located in the locked pool pump room.
Correction: Provide a first aid kit in the pool area or, if the first aid kit is within 25 feet of the enclosure, post signage that tells where the first aid kit is located.
Code ATCP 76.27(1)(a) - FIRST AID KIT PRESENT
-
Serious
Critical
CLOSING CRITERIA-FAILURE TO MEET 76.16
The Responsible Supervisor or operator has not closed the pool after failure to comply with the water quality requirements. Chlorine levels were at 0.4ppm and the minimum is 1.0ppm.
Correction: Close the pool in the event of failure to comply with the water quality requirements pursuant to s. ATCP 76.16.
Code ATCP 76.30 (1)(b) - FAILURE TO MEET ATCP 76.16
-
Not serious
Non-critical
Repeat
-
Jul 8, 2025 Follow Up · 2 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition. Flow meter was reading 0 gpm.
Correction: Adjust or repair the flowmeter
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
CHEMICAL FEEDERS USED-CAPABLE OF PROVIDING REQUIRED RESIDUAL
Chlorine feeder is not capable of providing required chemical residual. Jeff first test this morning found 0 ppm of chlorine. He added some shock to the pool. My test at about 10:30am found 0.4ppm of chlorine. Shock was added to get to 2.2 ppm. Chlorine feeder was continually pumping chlorine during this time until shock was added, which time it did stop feeding with an ORP reading of 790mv.
Correction: Check the chlorine feeder pump for actual chemical feeding (pump primed?) Will test pool water at least 2X daily until the controller can be looked at. Pool was allowed to open.
Code ATCP 76.13(1)(b)3. - CAPABLE OF PROVIDING REQUIRED RESIDUAL
-
Not serious
Non-critical
-
Jul 7, 2025 Follow Up · 1 critical, 4 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 617 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV. Manual testing is required 2X per day.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING WATER POTENTIAL
7/7/25: The water potential ("ORP") is 393 mV and water has not been tested manually. No manaul water test was done as of 10:30am.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
INCREASED TESTING MAY BE REQUIRED
The department or its agent has required more frequent testing but the testing has not been performed. Due to the controller not working, water testing was required to be done 2X per day. No testing was done on 7/4 and 7/5.
Correction: Perform any increased testing that the department or its agent has required.
Code ATCP 76.18(4) - INCREASED TESTING
-
Not serious
Non-critical
OPERATOR RESPONSIBILITIES
The operator has not been responsible for equipment shut-down and daily maintenance of water quality pursuant. The controller has not been working and no chlorine has been feeding into the pool.
Correction: Provide a pool operator who is responsible and providing active managerial control for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality.
Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is at 0 ppm. Range is to be 1 - 10 ppm.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Not serious
Non-critical
Repeat
-
Jul 1, 2025 Re-inspection · 1 critical, 3 non-critical, 2 repeat
-
Not serious
Non-critical
SKIMMER POOL RECIRCULATION FLOW
Proportion of water recirculating from skimmer and main drain is 100% from the main drain due to a water leak from the equalizer lines. No water is coming to the circulation pump through the skimmers.
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. Flow meter is not working.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 617 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV. Manual testing is required 2X per day.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Serious
Critical
Repeat
Corrected on site
MINIMUM DISINFECTANT RESIDUAL
Disinfectant or sanitizer level is 0.2ppm of chlorine. Minimum of 1.0ppm is required.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Shock is to be added to raise the chlorine level.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Not serious
Non-critical
-
Jun 20, 2025 Follow Up · No items found
No violations cited.
-
Jun 9, 2025 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
SIGNAGE 'NO LIFEGUARD ON DUTY'
A pool not required to have a lifeguard, does not have a 'no lifeguard on duty' sign with lettering 4" high.
Correction: Provide a sign to indicate 'no lifeguard on duty.'
Code ATCP 76.23(2)- NO LIFEGUARD ON DUTY
-
Not serious
Non-critical
Repeat
-
Jun 6, 2025 Routine · 3 critical, 8 non-critical, 6 repeat
-
Not serious
Non-critical
EMERGENCY CONTACT PHONE NUMBERS
Emergency contact phone numbers are not in the chemical storage area or readily accessible.
Correction: Provide emergency contact numbers in the chemical storage area or readily accessible.
Code ATCP 76.12 (2)(j) - EMERGENCY CONTACT PHONE NUMBERS
-
Not serious
Non-critical
SAFETY DATA SHEET
Safety data sheet was not available for all the pool chemicals used.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
Repeat
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 324 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
Repeat
SIGNAGE 'NO LIFEGUARD ON DUTY'
A pool not required to have a lifeguard, does not have a 'no lifeguard on duty' sign with lettering 4" high.
Correction: Provide a sign to indicate 'no lifeguard on duty.'
Code ATCP 76.23(2)- NO LIFEGUARD ON DUTY
-
Not serious
Non-critical
EMERGENCY BLANKETS
Two emergency blankets in good condition are not available in the pool area.
Correction: Provide two emergency blankets in good condition in the pool area.
Code ATCP 76.27(3) - EMERGENCY BLANKETS
-
Not serious
Non-critical
Repeat
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
POOL BASIN ROUTINELY BRUSHED, VACUUMED
Pool basin is not routinely brushed or vacuumed to keep the basin and surrounding appurtenances free of sediment, lint, hair, debris, algae, and slime growth and discoloration. Debris and dirt were at the bottom of the pool basin.
Correction: Routinely brush or vacuum the pool basin to keep the basin and surrounding appurtenances free of sediment, lint, hair, debris, algae, and slime growth and discoloration.
Code ATCP 76.33(1)(a)1- POOL BASIN BRUSHED, VACUUMED
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 1ppm and the level was 0.2ppm.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
PH
The pH is 6.8.
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
Repeat
RESPONSIBLE SUPERVISOR POOL CLOSED
Responsible supervisor is not ensuring that pool is closed pursuant to ATCP 76.30, closing criteria. Pool chlorine and pH levels were out of range and the pool was not closed until told to close.
Correction: Have the responsible supervisor ensure that the pool is closed pursuant to ATCP 76.30, closing criteria.
Code ATCP 76.21 (1)(c)10. - CLOSE POOL
-
Not serious
Non-critical
-
Jul 9, 2024 Follow Up · No items found
No violations cited.
-
Jun 26, 2024 Routine · 2 critical, 14 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition. No reading on the digital guage.
Correction: Adjust or repair the guage.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 253 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV. Water was tested and 0ppm chlorine was found.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER
Pool water is not tested for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use. No records from the previous 2 weeks for pool testing was available. No results from yesterday and today were documented.
Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.
Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level. No results were documented from the previous 2 weeks.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
ALKALINITY TEST
Pool water not tested at least once a week for total alkalinity. No results were available from the previous 2 weeks.
Correction: Test pool water at least once a week for total alkalinity.
Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY
-
Not serious
Non-critical
CYANURIC TEST
Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week. No results were available from the previous 2 weeks.
Correction: Test water for the cyanuric acid at least once a week.
Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC
-
Not serious
Non-critical
SIGNAGE 'NO LIFEGUARD ON DUTY'
A pool not required to have a lifeguard, does not have a 'no lifeguard on duty' sign.
Correction: Provide a sign to indicate 'no lifeguard on duty.'
Code ATCP 76.23(2)- NO LIFEGUARD ON DUTY
-
Not serious
Non-critical
MAX PATRON LOAD WATER ATTRACTION
There is no maximum patron load signage posted.
Correction: Calculate the maximum patron load to provide at least 15 square feet per patron and monitor the pool area and do not allow maximum patron load to be exceeded.
Code ATCP 76.25(1) - WATER ATTRACTION
-
Not serious
Non-critical
POOL RULES POSTED
The pool rules are not posted.
Correction: Post the pool rules. Refer to ATCP 76.29 for all the required pool rules.
Code ATCP 76.29(1)(a)1. - SIGNAGE POSTED
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding. Signage was provided.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
OPERATING REPORTS-CHEMICAL TESTING
The operator did not record the following on the operating report: Results for chemical testing. Results were missing from the past 2 weeks.
Correction: Record the following on the operating report, results for chemical testing.
Code ATCP 76.32(1)(a) - CHEMICAL TESTING
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Not serious
Non-critical
POOL DECK-OUTDOOR-CLEANED
Outdoor pool deck area not cleaned as needed. Algae is growing on the north side of the pool on the deck.
Correction: Clean outdoor pool deck area as needed.
Code ATCP 76.33(1)(b)3. - OUTDOOR DECK CLEANED
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0 ppm of chlorine
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Shock was added to the pool to raise the chlorine level
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
RESPONSIBLE SUPERVISOR POOL CLOSED
Responsible supervisor is not ensuring that pool is closed pursuant to ATCP 76.30, closing criteria. The pool has 0ppm of chlorine.
Correction: Have the responsible supervisor ensure that the pool is closed pursuant to ATCP 76.30, closing criteria.
Code ATCP 76.21 (1)(c)10. - CLOSE POOL
-
Not serious
Non-critical
-
Aug 9, 2023 Follow Up · 6 non-critical, 6 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL
The flow meter is not functional.
Correction: Repair or replace the specified equipment so an accurate reading can be recorded.
Code ATCP 76.11(5)
-
Not serious
Non-critical
Repeat
MSDS AVAILABILITY
Material safety data sheets are not available for all chemicals used in the facility.
Correction: Provide material safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Non-critical
Repeat
BIOHAZARD KIT UNAVAILABLE
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Non-critical
Repeat
ATTENDANT FOR WATER ATTRACTION WHIRLPOOL
No attendant is available for periodic supervision of the whirlpool.
Correction: The whirlpool must be closed until periodic supervision by an attendant is available.
Code [A] ATCP 76.22(1)(d)
-
Not serious
Non-critical
Repeat
MAXIMUM PATRON LOAD NOT POSTED
The maximum patron load is not posted in the facility.
Correction: Post the maximum patron load in accordance with ATCP 76.29(1)(d).
Code [A] ATCP 76.29(1)(d)
-
Not serious
Non-critical
Repeat
RULES MISSING - GENERAL
The pool rule signage is from the State of Illinois Dept of Health and does not meet the requirements of the State of Wisconsin.
Correction: Provide a sign in compliance with ATCP 76.29(1)(b).
Code [D] ATCP 76.29(1)(b)
-
Not serious
Non-critical
Repeat
-
Aug 8, 2023 Follow Up · 6 non-critical, 6 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL
The flow meter is not functional.
Correction: Repair or replace the specified equipment so an accurate reading can be recorded.
Code ATCP 76.11(5)
-
Not serious
Non-critical
Repeat
MSDS AVAILABILITY
Material safety data sheets are not available for all chemicals used in the facility.
Correction: Provide material safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Non-critical
Repeat
BIOHAZARD KIT UNAVAILABLE
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Non-critical
Repeat
ATTENDANT FOR WATER ATTRACTION WHIRLPOOL
No attendant is available for periodic supervision of the whirlpool.
Correction: The whirlpool must be closed until periodic supervision by an attendant is available.
Code [A] ATCP 76.22(1)(d)
-
Not serious
Non-critical
Repeat
MAXIMUM PATRON LOAD NOT POSTED
The maximum patron load is not posted in the facility.
Correction: Post the maximum patron load in accordance with ATCP 76.29(1)(d).
Code [A] ATCP 76.29(1)(d)
-
Not serious
Non-critical
Repeat
RULES MISSING - GENERAL
The pool rule signage is from the State of Illinois Dept of Health and does not meet the requirements of the State of Wisconsin.
Correction: Provide a sign in compliance with ATCP 76.29(1)(b).
Code [D] ATCP 76.29(1)(b)
-
Not serious
Non-critical
Repeat
-
Jun 2, 2023 Pre-inspection Follow Up · 6 non-critical, 6 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL
The flow meter is not functional.
Correction: Repair or replace the specified equipment so an accurate reading can be recorded.
Code ATCP 76.11(5)
-
Not serious
Non-critical
Repeat
MSDS AVAILABILITY
Material safety data sheets are not available for all chemicals used in the facility.
Correction: Provide material safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Non-critical
Repeat
BIOHAZARD KIT UNAVAILABLE
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Non-critical
Repeat
ATTENDANT FOR WATER ATTRACTION WHIRLPOOL
No attendant is available for periodic supervision of the whirlpool.
Correction: The whirlpool must be closed until periodic supervision by an attendant is available.
Code [A] ATCP 76.22(1)(d)
-
Not serious
Non-critical
Repeat
MAXIMUM PATRON LOAD NOT POSTED
The maximum patron load is not posted in the facility.
Correction: Post the maximum patron load in accordance with ATCP 76.29(1)(d).
Code [A] ATCP 76.29(1)(d)
-
Not serious
Non-critical
Repeat
RULES MISSING - GENERAL
The pool rule signage is from the State of Illinois Dept of Health and does not meet the requirements of the State of Wisconsin.
Correction: Provide a sign in compliance with ATCP 76.29(1)(b).
Code [D] ATCP 76.29(1)(b)
-
Not serious
Non-critical
Repeat
-
May 31, 2023 Pre-inspection Follow Up · 8 non-critical, 2 repeat
-
Not serious
Non-critical
FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL
The flow meter is not functional.
Correction: Repair or replace the specified equipment so an accurate reading can be recorded.
Code ATCP 76.11(5)
-
Not serious
Non-critical
NO CERTIFIED OPERATOR AT WATER ATTRACTION
The facility is not staffed with a current certified water attraction operator.
Correction: Acquire or train a certified water attraction operator for the facility.
Code ATCP 76.20(2)(a)
-
Not serious
Non-critical
BIOHAZARD KIT UNAVAILABLE
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Non-critical
ATTENDANT FOR WATER ATTRACTION WHIRLPOOL
No attendant is available for periodic supervision of the whirlpool.
Correction: The whirlpool must be closed until periodic supervision by an attendant is available.
Code [A] ATCP 76.22(1)(d)
-
Not serious
Non-critical
RECORD RETENTION
5/31/23: ATCP 76 is not available on site. No DSPS approved pool plans are not available for review.
Correction: Keep records in accordance with ATCP 76.32(3).
Code [A] ATCP 76.32(3)
-
Not serious
Non-critical
RULES MISSING - GENERAL
The pool rule signage is from the State of Illinois Dept of Health and does not meet the requirements of the State of Wisconsin.
Correction: Provide a sign in compliance with ATCP 76.29(1)(b).
Code [D] ATCP 76.29(1)(b)
-
Not serious
Non-critical
Repeat
MSDS AVAILABILITY
Material safety data sheets are not available for all chemicals used in the facility.
Correction: Provide material safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Non-critical
Repeat
MAXIMUM PATRON LOAD NOT POSTED
The maximum patron load is not posted in the facility.
Correction: Post the maximum patron load in accordance with ATCP 76.29(1)(d).
Code [A] ATCP 76.29(1)(d)
-
Not serious
Non-critical
Source: Oak Creek Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.