Gaslight Pointe

35 HARBORVIEW DR, Racine, WI 53403 · Racine County

49cited violations
16serious tier
8inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
City of Racine Public Health Department
License / ID
HSAT-7QWE6J
Status
Permitted
Phone
(262) 383-3312
Official record
City of Racine Public Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026121
2025161
20243127
20233297

Inspections

  1. Jul 15, 2026 Routine · 1 critical, 1 non-critical, 1 repeat
    • Not serious Non-critical

      FLOWMETER, VALVE OR GAUGE NOT INSTALLED PER MANUFACTURER OR AS VERIFIED BY PUMP CURVE

      Flowmeter observed to be missing in the pump room.

      Correction: Install the flowmeter. according to manufacturer instructions or as verified by pump curve.

      Code ATCP 76.11(5)(b) - FLOWMETER, VALVE, GAUGE NOT INSTALLED PRO

    • Serious Critical Repeat

      HAZARDOUS CONDITION

      The VGBA equalizer drain covers were installed more than 5 years ago but show no visible signs of damage or modification.

      Correction: Replace equalizer drain covers.

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  2. Jul 2, 2025 Routine · 1 critical, 5 non-critical
    • Not serious Non-critical

      LICENSE NOT POSTED

      The license that is posted is expired.

      Correction: Post the current license where it can be viewed by the public.

      Code ATCP 76.05(7) - LICENSE POSTED

    • Not serious Non-critical

      EMERGENCY BLANKETS

      Two emergency blankets in good condition are not available in the pool area.

      Correction: Provide two emergency blankets in good condition in the pool area.

      Code ATCP 76.27(3) - EMERGENCY BLANKETS

    • Not serious Non-critical

      POOL RULES SIGNAGE- COMMUNICABLE DISEASE

      Pool rules missing rule: Do not enter the pool if you have a communicable disease or an open cut.

      Correction: Include pool rule on sign: Do not enter the pool if you have a communicable disease or an open cut.

      Code ATCP 76.29(1)(b)1.a - NO COMMUNICABLE DISEASE, OPEN CUT

    • Not serious Non-critical

      POOL EQUIPMENT-REPAIRED AS NECESSARY

      The grab rails on the stairs and the exit ladder are not secure.

      Correction: Secure on the grab rails on the stairs and the exit ladder.

      Code ATCP 76.33(1)(e)4. - EQPT REPAIRED AS NEEDED

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

    • Serious Critical

      HAZARDOUS CONDITION

      The VGBA equalizer drain covers were installed more than 5 years ago, but show no visible signs of damage or modification.

      Correction: Operator must log daily inspection of equalizer covers to ensure no cracks, breaks, missing screws or other visible damage or defects are observed. If any of the above damage or defects are observed, the operator shall close the pool until a compliant drain cover has been installed. Equalizer drain covers will need to be replaced with compliant drain covers prior to the pool opening for the 26-27

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  3. Jul 2, 2024 Re-inspection 2 · 1 critical, 1 non-critical, 2 repeat
    • Not serious Non-critical Repeat Corrected on site

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers wiers doors are missing.

      Correction: Repair or replace skimmer, weirs or gutters as needed. Action Taken: 1 of the 3 missing wier doors were replaced during inspection.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Serious Critical Repeat

      TELEPHONE-OTHER TECHNOLOGIES,RELIABLE SERVICE CONNECTION

      Telephone does not have reliable service connection to connect with emergency response.

      Correction: Provide a reliable service connection for the communication technology.

      Code ATCP 76.26(2)(b)2. - TELEPHONE, OTHER TECHNOLOGIES, CONNECTI

  4. Jun 28, 2024 Re-inspection · 3 critical, 2 non-critical, 5 repeat
    • Not serious Non-critical Repeat Corrected on site

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers wiers doors are missing.

      Correction: Repair or replace skimmer, weirs or gutters as needed. Action Taken: 1 of the 3 missing wier doors were replaced during inspection.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      REAGENTS STORAGE CONTAINER

      The test kit regaents are not replaced as recommened by the manufacturer. The following reagent bottles in the on-site pool test kit have expired: R-0871 exp 4/2024 R-0002 exp 5/2024 & 6/2023 R-0007 exp 12/2020 R-0009 exp 4/2023 R-0004 exp 7/2023 R-0005 exp 9/2023 R-0006 exp 9/2023 R-0013 exp 9/2023 R-0012 exp 8/2023 R-0011L exp 12/2023 R-0010 exp 1/2024

      Correction: Remove and replace expired testing reagents.

      Code ATCP 76.17 (2)(a) - REAGENT STORAGE BOTTLES

    • Serious Critical Repeat

      TELEPHONE-OTHER TECHNOLOGIES,RELIABLE SERVICE CONNECTION

      Telephone does not have reliable service connection to connect with emergency response.

      Correction: Provide a reliable service connection for the communication technology.

      Code ATCP 76.26(2)(b)2. - TELEPHONE, OTHER TECHNOLOGIES, CONNECTI

    • Serious Critical Repeat

      CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE

      The emergency phone directly calls the non-emergency dispatch number rather than 911.

      Correction: Close the pool in the event of a nonfunctional emergency phone.

      Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE

    • Serious Critical Repeat

      CLOSING CRITERIA-GATE OR DOOR NOT EQUIPPED TO SELF-CLOSE, LATCH, LOCKABLE

      The pool gate is observed to be self-closing however, the latching mechanism can be opened with little effort by reaching through the gate. Mechanism observed to be able to be open with 1 finger.

      Correction: Close the pool in the event of a pool gate or door that is not equipped with a self-closing and latching mechanism.

      Code ATCP 76.30 (1)(i) - GATE OR DOOR NOT EQUIPPED TO SELF-CLOSE

  5. Jun 26, 2024 Routine · 3 critical, 2 non-critical
    • Not serious Non-critical Corrected on site

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers wiers doors are missing.

      Correction: Repair or replace skimmer, weirs or gutters as needed. Action Taken: 1 of the 3 missing wier doors were replaced during inspection.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      REAGENTS STORAGE CONTAINER

      The test kit regaents are not replaced as recommened by the manufacturer. The following reagent bottles in the on-site pool test kit have expired: R-0871 exp 4/2024 R-0002 exp 5/2024 & 6/2023 R-0007 exp 12/2020 R-0009 exp 4/2023 R-0004 exp 7/2023 R-0005 exp 9/2023 R-0006 exp 9/2023 R-0013 exp 9/2023 R-0012 exp 8/2023 R-0011L exp 12/2023 R-0010 exp 1/2024

      Correction: Remove and replace expired testing reagents.

      Code ATCP 76.17 (2)(a) - REAGENT STORAGE BOTTLES

    • Serious Critical

      TELEPHONE-OTHER TECHNOLOGIES,RELIABLE SERVICE CONNECTION

      Telephone does not have reliable service connection to connect with emergency response.

      Correction: Provide a reliable service connection for the communication technology.

      Code ATCP 76.26(2)(b)2. - TELEPHONE, OTHER TECHNOLOGIES, CONNECTI

    • Serious Critical

      CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE

      The emergency phone directly calls the non-emergency dispatch number rather than 911.

      Correction: Close the pool in the event of a nonfunctional emergency phone.

      Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE

    • Serious Critical

      CLOSING CRITERIA-GATE OR DOOR NOT EQUIPPED TO SELF-CLOSE, LATCH, LOCKABLE

      The pool gate is observed to be self-closing however, the latching mechanism can be opened with little effort by reaching through the gate. Mechanism observed to be able to be open with 1 finger.

      Correction: Close the pool in the event of a pool gate or door that is not equipped with a self-closing and latching mechanism.

      Code ATCP 76.30 (1)(i) - GATE OR DOOR NOT EQUIPPED TO SELF-CLOSE

  6. Sep 1, 2023 Re-inspection 2 · 5 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      BIOHAZARD KIT UNAVAILABLE

      No biohazard safety kit is located on the premises.

      Correction: Provide a biohazard safety kit at the first aid station.

      Code ATCP 76.27(2)

    • Not serious Non-critical Repeat

      MONTHLY OPERATION REPORTS NOT SUBMITTED

      Monthly operation reports are not being kept in accordance with ATCP 76.32(1). Pool testing log is not dated. The pool testing logs are not being submitted to the Health Department.

      Correction: Keep monthly operation reports in accordance with ATCP 76.32(1). Submit reports to the Health Department.

      Code [A] ATCP 76.32(1)

    • Not serious Non-critical Repeat

      RECORD RETENTION

      The following records are not available for review during inspection: A. The monthly operating reports required under sub. (1). B.. Each fecal accident report made under s. ATCP 76.31. C.. A copy of the most current version of ch. ATCP 76. D. Pool construction plans. E. The manufacturer’s pump performance curve, manual of instruction on filter operation, recommendations for operation and maintenance of all equipment, and instructions and other pertinent information on pool operation and maintenance. F. The most recent Federal centers for disease control recommendations for fecal accidents or other plan in response to fecal accidents. G. Daily inspections and operational tests as specified in s. ATCP 76.37. H. All records shall be kept at least 7 years, except that monthly reports, fecal accident reports, daily inspection results, and operational tests shall be kept for at least 2 years.

      Correction: Keep records in accordance with ATCP 76.32(3).

      Code [A] ATCP 76.32(3)

    • Not serious Non-critical Repeat

      EMERGENCY CONTACT PHONE NUMBERS NOT POSTED

      The address of the pool is not posted near the designated emergency phone.

      Correction: Post the emergency numbers near the designated emergency phone.

      Code [C] ATCP 76.26(2)

    • Not serious Non-critical Repeat

      FIRST AID SUPPLIES MISSING

      The eye wash that is in the kit expired 6/30/2023.

      Correction: Provide new eye wash solution for the kit. Provide all the items listed in ATCP 76.27(1) in the first aid kit.

      Code [C] ATCP 76.27(1)

  7. Aug 25, 2023 Re-inspection · 2 critical, 6 non-critical, 8 repeat
    • Not serious Non-critical Repeat

      PERMIT NOT POSTED

      The permit that is posted in a place visible to the public is expired.

      Correction: Post the current permit in public view.

      Code ATCP 76.05(7)

    • Not serious Non-critical Repeat

      BIOHAZARD KIT UNAVAILABLE

      No biohazard safety kit is located on the premises.

      Correction: Provide a biohazard safety kit at the first aid station.

      Code ATCP 76.27(2)

    • Not serious Non-critical Repeat

      MONTHLY OPERATION REPORTS NOT SUBMITTED

      Monthly operation reports are not being kept in accordance with ATCP 76.32(1). Pool testing log is not dated. The pool testing logs are not being submitted to the Health Department.

      Correction: Keep monthly operation reports in accordance with ATCP 76.32(1). Submit reports to the Health Department.

      Code [A] ATCP 76.32(1)

    • Not serious Non-critical Repeat

      RECORD RETENTION

      The following records are not available for review during inspection: A. The monthly operating reports required under sub. (1). B.. Each fecal accident report made under s. ATCP 76.31. C.. A copy of the most current version of ch. ATCP 76. D. Pool construction plans. E. The manufacturer’s pump performance curve, manual of instruction on filter operation, recommendations for operation and maintenance of all equipment, and instructions and other pertinent information on pool operation and maintenance. F. The most recent Federal centers for disease control recommendations for fecal accidents or other plan in response to fecal accidents. G. Daily inspections and operational tests as specified in s. ATCP 76.37. H. All records shall be kept at least 7 years, except that monthly reports, fecal accident reports, daily inspection results, and operational tests shall be kept for at least 2 years.

      Correction: Keep records in accordance with ATCP 76.32(3).

      Code [A] ATCP 76.32(3)

    • Not serious Non-critical Repeat

      EMERGENCY CONTACT PHONE NUMBERS NOT POSTED

      The address of the pool is not posted near the designated emergency phone.

      Correction: Post the emergency numbers near the designated emergency phone.

      Code [C] ATCP 76.26(2)

    • Not serious Non-critical Repeat

      FIRST AID SUPPLIES MISSING

      The eye wash that is in the kit expired 6/30/2023.

      Correction: Provide new eye wash solution for the kit. Provide all the items listed in ATCP 76.27(1) in the first aid kit.

      Code [C] ATCP 76.27(1)

    • Serious Critical Repeat

      CYANURIC ACID >30 PPM

      8/25/23: The cyanuric acid concentration is 80 ppm. 8/24/23: The cyanuric acid concentration is 90ppm.

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

    • Serious Critical Repeat

      SELF-CLOSING AND LATCHING GATES

      All gate doors require a key to exit the pool enclosure.

      Correction: Repair the door immediately so that it is self-closing and latching and does not require a key to exit.

      Code [A] ATCP 76.34(4)

  8. Aug 24, 2023 Routine · 5 critical, 11 non-critical, 7 repeat
    • Not serious Non-critical

      PERMIT NOT POSTED

      The permit that is posted in a place visible to the public is expired.

      Correction: Post the current permit in public view.

      Code ATCP 76.05(7)

    • Not serious Non-critical

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeter appears to be stuck and is not functioning.

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical Repeat

      BIOHAZARD KIT UNAVAILABLE

      No biohazard safety kit is located on the premises.

      Correction: Provide a biohazard safety kit at the first aid station.

      Code ATCP 76.27(2)

    • Not serious Non-critical

      EQUIPMENT NOT MAINTAINED

      1. Hand rails adjacent to the pool stairs are loose and not being maintained and repaired as necessary. 2. Hand rails at deep end of the pool are loose and bot being maintained and repaired as necessary. 3. The pool deck surface surrounding the pool has areas that are chipping or missing and not maintained or repaired as necessary.

      Correction: Repair and maintain all equipment pursuant to ATCP 76.33(1)(e).

      Code ATCP 76.33(1)(e)

    • Not serious Non-critical

      SIGNAGE - LETTERS TOO SMALL

      The letters on the pool rules signage are less than 1-inch in height.

      Correction: Reprint the sign in compliance with ATCP 76.29(1)(b).

      Code [A] ATCP 76.29(1)(b)

    • Not serious Non-critical Repeat

      MONTHLY OPERATION REPORTS NOT SUBMITTED

      Monthly operation reports are not being kept in accordance with ATCP 76.32(1). Pool testing log is not dated. The pool testing logs are not being submitted to the Health Department.

      Correction: Keep monthly operation reports in accordance with ATCP 76.32(1). Submit reports to the Health Department.

      Code [A] ATCP 76.32(1)

    • Not serious Non-critical Repeat

      RECORD RETENTION

      The following records are not available for review during inspection: A. The monthly operating reports required under sub. (1). B.. Each fecal accident report made under s. ATCP 76.31. C.. A copy of the most current version of ch. ATCP 76. D. Pool construction plans. E. The manufacturer’s pump performance curve, manual of instruction on filter operation, recommendations for operation and maintenance of all equipment, and instructions and other pertinent information on pool operation and maintenance. F. The most recent Federal centers for disease control recommendations for fecal accidents or other plan in response to fecal accidents. G. Daily inspections and operational tests as specified in s. ATCP 76.37. H. All records shall be kept at least 7 years, except that monthly reports, fecal accident reports, daily inspection results, and operational tests shall be kept for at least 2 years.

      Correction: Keep records in accordance with ATCP 76.32(3).

      Code [A] ATCP 76.32(3)

    • Not serious Non-critical Corrected on site

      SKIMMER BASKET OR WEIR MISSING

      Two weir doors are missing.

      Correction: Replace the missing equipment. Action Taken: One missing door was replaced.

      Code [B] ATCP 76.11(2)(b)

    • Not serious Non-critical

      RULES MISSING - GENERAL

      The following rules are missing from the posting: A. Do not enter the pool if you have a communicable disease or an open cut. B. Do not bring food, drink, gum or tobacco into the pool. C. Shower before entering the pool and after use of toilet facilities.

      Correction: Provide a sign in compliance with ATCP 76.29(1)(b).

      Code [B] ATCP 76.29(1)(b)

    • Not serious Non-critical

      EMERGENCY CONTACT PHONE NUMBERS NOT POSTED

      The address of the pool is not posted near the designated emergency phone.

      Correction: Post the emergency numbers near the designated emergency phone.

      Code [C] ATCP 76.26(2)

    • Not serious Non-critical Repeat

      FIRST AID SUPPLIES MISSING

      The eye wash that is in the kit expired 6/30/2023.

      Correction: Provide new eye wash solution for the kit. Provide all the items listed in ATCP 76.27(1) in the first aid kit.

      Code [C] ATCP 76.27(1)

    • Serious Critical Repeat

      CYANURIC ACID >30 PPM

      The cyanuric acid concentration is 90ppm.

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

    • Serious Critical

      pH OUT OF BALANCE

      The pH is < 7.0

      Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.

      Code ATCP 76.14(4)(c)

    • Serious Critical Repeat

      ALKALINITY OUT OF BALANCE

      The total alkalinity is 50

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

    • Serious Critical Repeat

      CHLORINE TOO LOW

      The chlorine residual was 0ppm at the time of the inspection.

      Correction: Close the pool and raise the chlorine residual to 1.5 to 2ppm chlorine before re-opening.

      Code [A] ATCP 76.14(4)(a)

    • Serious Critical

      SELF-CLOSING AND LATCHING GATES

      Both gate doors require a key to exit the pool enclosure.

      Correction: Repair the door immediately so that it is self-closing and latching and does not require a key to exit.

      Code [A] ATCP 76.34(4)

Source: City of Racine Public Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.