Home2 Suites By Hilton
1301 WEST RD, Sturtevant, WI 53177 · Racine County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Central Racine County Health Department
- License / ID
- CDYA-CTHQRM
- Status
- Permitted
- Official record
- Central Racine County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2025 | 1 | 5 | 1 |
| 2024 | 2 | 8 | 2 |
| 2023 | 4 | 24 | 2 |
Inspections
-
Nov 25, 2025 Routine · 1 critical, 4 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
SKIMMER POOL RECIRCULATION FLOW
Proportion of water recirculating from skimmer and main drain is 50/50
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 58. Saturation index is -1
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
FIRST AID KIT-GAUZE ROLLER BANDAGES
The first aid kit is missing a gauze roller bandage.
Correction: Provide a gauze roller bandage for the first aid kit.
Code ATCP 76.27(1)(b)3.- GAUZE ROLLER BANDAGES
-
Not serious
Non-critical
FIRST AID KIT -RESUSCITATION POCKET MASK
The first aid kit is missing a resuscitation pocket mask.
Correction: Provide a resuscitation pocket mask for the first aid kit.
Code ATCP 76.27(1)(b)8.- RESUSCITATION MASK
-
Serious
Critical
Repeat
FIRST AID KIT-PROVIDED IN POOL AREA
The first aid kit is missing from the pool area, or within 25 feet of enclosure with signage posted in the enclosure telling where the first aid kit is. No sign is posted.
Correction: Provide a first aid kit in the pool area or, if the first aid kit is within 25 feet of the enclosure, post signage that tells where the first aid kit is located.
Code ATCP 76.27(1)(a) - FIRST AID KIT PRESENT
-
Not serious
Non-critical
Repeat
-
Nov 19, 2024 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
CYANURATES 30 PPM LIMIT
The cyanuric acid concentration is 53 PPM
Correction: Cyanuric acid is not needed in an indoor pool Discontinue use and lower the water cyanuric acid concentration to 30 ppm or lower by diluting the pool water with fresh water.
Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC
-
Not serious
Non-critical
Repeat
-
Nov 5, 2024 Routine · 2 critical, 5 non-critical, 3 repeat
-
Not serious
Non-critical
Corrected on site
SKIMMER POOL RECIRCULATION FLOW
Proportion of water recirculating from skimmer and main drain is 50/50.
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
Repeat
SAFETY DATA SHEET
A safety data sheet was not available for a Pool Shock, muriatic acid, Sodium hypochlorite, calcium hypochlorite, sodium bicarbonate, Water clarifier.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
CYANURATES 30 PPM LIMIT
The cyanuric acid concentration is 65PPM. This is an indoor pool that cyanuric acid is being added seperately.
Correction: Discontinue use of "Stabilitzer" also known cyanuric acid. Stabalizer is not needed for an indoor pool. Continue to drain basin and add fresh was to rmoved the concentration of cyanuric acid.
Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC
-
Not serious
Non-critical
Repeat
FIRST AID KIT-ELASTIC BANDAGE
The first aid kit is missing an elastic bandage, adhesive tape and 1 emergency blanket.
Correction: Provide missing components for the first aid kit.
Code ATCP 76.27(1)(b)6. - ELASTIC BANDAGE
-
Not serious
Non-critical
Repeat
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Serious
Critical
Corrected on site
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0.43PPM for chlorine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Chlorine levels were adjusted and holding at 2.27PPM. Reviewed testing method for Taylor kit to test chlorine levels.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
FIRST AID KIT-PROVIDED IN POOL AREA
There is no sign directing patrons of the location of the first aid kit.
Correction: Provide a first aid kit in the pool area or, if the first aid kit is within 25 feet of the enclosure, post signage that tells where the first aid kit is located.
Code ATCP 76.27(1)(a) - FIRST AID KIT PRESENT
-
Not serious
Non-critical
Corrected on site
-
Nov 29, 2023 Routine · 1 critical, 8 non-critical
-
Not serious
Non-critical
LICENSE NOT POSTED
The license is not posted for public view.
Correction: Post the license where it can be viewed by the public.
Code ATCP 76.05(7) - LICENSE POSTED
-
Not serious
Non-critical
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available for the pool pump.
Correction: Provide a spare strainer or screen
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
SAFETY DATA SHEET
A safety data sheet was not available for a Sodium hypochlorite and muriac acid.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
COMBINED CHLORINE PLAN ACTION LEVEL
No combined chlorine plan available onsite.
Correction: Draft the combined chlorine plan from the template provided during inspection.
Code ATCP 76.14(5)(e)2.a. - ACTION LEVEL LISTED
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
WHIRLPOOL, THERAPY POOL, EXERCISE POOL, ALKALINITY
Pool water not tested at least once a week for total alkalinity.
Correction: Test pool water at least once a week for total alkalinity.
Code ATCP 76.18(2)(c) - ALKALINITY, WHIRL, EX, THERAPY
-
Not serious
Non-critical
FIRST AID KIT-ELASTIC BANDAGE
The first aid kit is missing an elastic bandage.
Correction: Provide an elastic bandage for the first aid kit.
Code ATCP 76.27(1)(b)6. - ELASTIC BANDAGE
-
Not serious
Non-critical
Corrected on site
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises. Pump curve was found and added to pool binder during inspection.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Serious
Critical
OPERATOR KNOWLEDGE-MONTHLY TESTING
The person responsible is not able to describe how monthly testing is performed.
Correction: Ensure that operator can describe how monthly testing is performed. Work with pool company to draft a procedure on how to test the interlock. Interlock shall be tested on a monthly basis and documented on page 1 of the monthly report.
Code ATCP 76.13 (1)(c)2.d - MONTHLY TESTING
-
Not serious
Non-critical
-
Oct 10, 2023 Follow Up · 3 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
INDOOR POOL WATER TEMPERATURE
The temperature of the indoor pool water is 68 degrees Fahrenheit.
Correction: Adjust the temperature to bring it within permissible limits pursuant to ATCP 76.19(4)(b).
Code ATCP 76.19(4)(b)
-
Not serious
Non-critical
Repeat
SPARE STRAINER BASKET - REQUIREMENT
A spare strainer basket for the recirculation pump is not located on site.
Correction: Provide a spare basket for the recirculation pump.
Code [A] ATCP 76.11(2)(d)
-
Not serious
Non-critical
Repeat
RECORD RETENTION
Pool records (#5, #6, #7) were not available for review.
Correction: Keep records in accordance with ATCP 76.32(3). All records shall be available onsite for inspection.
Code [A] ATCP 76.32(3)
-
Not serious
Non-critical
Repeat
-
Oct 9, 2023 Follow Up · 3 non-critical
-
Not serious
Non-critical
INDOOR POOL WATER TEMPERATURE
The temperature of the indoor pool water is 68 degrees Fahrenheit.
Correction: Adjust the temperature to bring it within permissible limits pursuant to ATCP 76.19(4)(b).
Code ATCP 76.19(4)(b)
-
Not serious
Non-critical
SPARE STRAINER BASKET - REQUIREMENT
A spare strainer basket for the recirculation pump is not located on site.
Correction: Provide a spare basket for the recirculation pump.
Code [A] ATCP 76.11(2)(d)
-
Not serious
Non-critical
RECORD RETENTION
Pool records (#5, #6, #7) were not available for review.
Correction: Keep records in accordance with ATCP 76.32(3). All records shall be available onsite for inspection.
Code [A] ATCP 76.32(3)
-
Not serious
Non-critical
-
Oct 5, 2023 Pre-inspection · 1 critical, 8 non-critical
-
Not serious
Non-critical
RECIRCULATION RATE NOT MET - POOLS
The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.
Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(a)
-
Not serious
Non-critical
CHEMICAL LABELING
Bulk tanks for the chlorine and muriac acid are not labeled according to ATCP 76.12(1).
Correction: Label the chemical containers according to ATCP 76.12(1).
Code ATCP 76.12(1)
-
Not serious
Non-critical
MSDS AVAILABILITY
Material safety data sheets are not available for all chemicals used in the facility.
Correction: Provide material safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Non-critical
BIOHAZARD KIT UNAVAILABLE
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Non-critical
RECORD RETENTION
Pool records were not available for review.
Correction: Keep records in accordance with ATCP 76.32(3). All records shall be available onsite for follow up inspection.
Code [A] ATCP 76.32(3)
-
Not serious
Non-critical
SELF-CLOSING AND LATCHING GATES
The door to the pool enclosure is sticking and therefore not self-closing .
Correction: Repair the door immediately so that it is self-closing and latching.
Code [A] ATCP 76.34(4)
-
Not serious
Non-critical
BLANKETS MISSING
2 durable blankets are not available in the pool area.
Correction: Provide 2 durable blankets in the pool area.
Code [B] ATCP 76.27(1)
-
Not serious
Non-critical
FIRST AID SUPPLIES MISSING
Cold pack is missing from the first aid kit.
Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit.
Code [C] ATCP 76.27(1)
-
Serious
Critical
EMERGENCY CONTACT PHONE NUMBERS NOT POSTED
1. The address of the facility is not posted near the designated emergency phone. 2. The emergency phone is dialing out to the "national 911 answering service" not to Racine County Dispatch.
Correction: 1. Post the address of the facility near the designated emergency phone. 2. Work with the phone company to link emergency phone to dial to Racine County Dispatch. This must be corrected prior to releasing the permit.
Code [C] ATCP 76.26(2)
-
Not serious
Non-critical
Source: Central Racine County Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.