Browns Lake Resort Village
2501 S BROWNS LAKE RD, Burlington, WI 53105 · Racine County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Central Racine County Health Department
- License / ID
- HSAT-7QWDQE
- Status
- Permitted
- Phone
- (262) 697-8200 ext. 19
- Official record
- Central Racine County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 6 | 2 |
| 2025 | 1 | 4 | 2 |
| 2024 | 1 | 7 | 1 |
| 2023 | 1 | 5 | 0 |
Inspections
-
Aug 12, 2026 Admin Follow Up · 1 critical, 2 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
TELEPHONE-EMERGENCY NUMBERS AND ADDRESS
A sign providing the facility's address is not attached or posted near telephone.
Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.
Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED
-
Not serious
Non-critical
Repeat
POOL DECK-DEPTH MARKINGS MAINTAINED
The depth markings on the pool deck are beginning to fade.
Correction: Maintain pool deck area so that depth markings along the edge of the pool are clearly visible and readable.
Code ATCP 76.33(1)(b)4. - DEPTH MARKINGS
-
Serious
Critical
Repeat
WATER APPROVED SOURCE
The annual water testing is not available for review.
Correction: Provide the water testing results to the health department.
Code ATCP 76.19(2) - SOURCE WATER
-
Not serious
Non-critical
Repeat
-
Aug 4, 2026 Routine · 1 critical, 2 non-critical
-
Not serious
Non-critical
TELEPHONE-EMERGENCY NUMBERS AND ADDRESS
A sign providing the facility's address is not attached or posted near telephone.
Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.
Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED
-
Not serious
Non-critical
POOL DECK-DEPTH MARKINGS MAINTAINED
The depth markings on the pool deck are beginning to fade.
Correction: Maintain pool deck area so that depth markings along the edge of the pool are clearly visible and readable.
Code ATCP 76.33(1)(b)4. - DEPTH MARKINGS
-
Serious
Critical
WATER APPROVED SOURCE
The annual water testing is not available for review.
Correction: Provide the water testing results to the health department.
Code ATCP 76.19(2) - SOURCE WATER
-
Not serious
Non-critical
-
Aug 7, 2025 Routine · 2 critical, 2 non-critical, 3 repeat
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The turnover rate is 6.22 hours..
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate; less than 6 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
Corrected on site
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided. A sign was provided by the health department during inspection.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
Repeat
WATER APPROVED SOURCE
Pool supply water is not from an approved source. Annual well test is not available for review.
Correction: Use water from an approved source.
Code ATCP 76.19(2) - SOURCE WATER
-
Serious
Critical
RESPONSIBLE SUPERVISOR RECORDS MAINTAIN
Responsible supervisor is not ensuring that records are maintained. Monthly testing logs are not being submitted to the health department.
Correction: Have the responsible supervisor ensure that records are maintained. Submit the monthly testing logs to the health department by the 10th day of the following month.
Code ATCP 76.21 (1)(c)7. - RECORDS MAINTENANCE
-
Not serious
Non-critical
Repeat
-
Jul 11, 2024 Routine · 1 critical, 6 non-critical
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Pool turn over rate was 7 hours.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate to not exceed 6 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
CYANURATES 30 PPM LIMIT
The cyanuric acid concentration is 45.
Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.
Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
Corrected on site
TELEPHONE-EMERGENCY NUMBERS AND ADDRESS
The facility address was not posted near telephone. Temporary address sign was posted during inspection.
Correction: Provide a list of emergency numbers and facility address, attached or posted near telephone or other telecommunication technology device.
Code ATCP 76.26(2)(d) - TELEPHONE, EMERGENCY NUMBERS POSTED
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY
A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:
Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.
Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY
-
Serious
Critical
WATER APPROVED SOURCE
Pool supply water is not from an approved source. No annaul well water test was available to reivew. .
Correction: Well water shall be tested annually and report provided.
Code ATCP 76.19(2) - SOURCE WATER
-
Not serious
Non-critical
-
Jul 7, 2023 Routine · 5 non-critical
-
Not serious
Non-critical
RECIRCULATION RATE NOT MET - POOLS
The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours. Pool turnover rate was 7.5 hours at time of inspection.
Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(a)
-
Not serious
Non-critical
pH OUT OF BALANCE
The pH is 7.9. Pool was retest 2 hours later at 7.0.
Correction: pH shall fall between 7.2 and 7.8. Montior chemicals until normal levels are reached. Close pool if pH falls below 6.8 or above 8.0.
Code ATCP 76.14(4)(c)
-
Not serious
Non-critical
RECORD RETENTION
Bacteria coliform test for well water is not available for review.
Correction: Keep records in accordance with ATCP 76.32(3).
Code [A] ATCP 76.32(3)
-
Not serious
Non-critical
BACKFLOW - HOSE BIBBS
The hose bibb by the maintenance building is not protected against backsiphonage.
Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.
Code [A] ATCP 76.33(1)(d)
-
Not serious
Non-critical
CRACKS OR PITTING IN THE POOL BASIN
There are cracks and pieces missing in the pool gutter.
Correction: Repair the pool so it is finished and easily cleanable.
Code [B] ATCP 76.33(1)(a)
-
Not serious
Non-critical
Source: Central Racine County Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.