RecordWell Data

Image Management Family Branch YMCA

8501 CAMPUS DR, Mt Pleasant, WI 53406 · Racine County

22cited violations
6serious tier
5inspections

Establishment

Type
Pool / recreational water (Pool - Complex with Features)
Inspected by
Central Racine County Health Department
License / ID
KHES-8XGN3W
Status
Permitted
Official record
Central Racine County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026162
2025120
2024164
2023280

Inspections

  1. Apr 7, 2026 Routine · 2 critical, 4 non-critical
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Gutter grate cracked in the SW corner of the pool

      Correction: Repair or replace gutter grate as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      REAGENTS REPLACED

      Test kit reagents not replaced as recommended by the manufacturer.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical

      SLIDES, RULES NOT PROVIDED

      Rules sign for a pool slide or waterslide is deteriorated and some words are no longer legible.

      Correction: Replace the rules sign for the pool slide or waterslide.

      Code ATCP 76.29(2)(a) - RULES FOR SLIDES

    • Not serious Non-critical

      POOL EQUIPMENT-PROPERLY MAINTAINED

      The pool equipment is not properly maintained. There is a severe leak from the pump.

      Correction: Repair the leak coming from the pump and maintain the pool equipment

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

    • Serious Critical

      NO PATRONS IN POOL, MAINTENANCE

      Patrons were in the pool during pool maintenance operations.

      Correction: Ensure that no patrons are in the pool while maintenance is occurring.

      Code ATCP 76.24(1) - NO PATRONS IN POOL DURING MAINTENANCE

    • Serious Critical

      RING BOUY

      A ring buoy not provided at the whirlpool area life guard chair.

      Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.

      Code ATCP 76.26(1)(b)2.a - RING BOUY

  2. Apr 28, 2025 Routine · 2 non-critical, 1 repeat
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Part of the gutter is cracked and missing near the lazy river and water slide..

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

  3. Apr 17, 2024 Routine · 4 critical, 2 non-critical
    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is 56.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Serious Critical Corrected on site

      MAXIMUM CHLORINE

      The maximum chlorine residual exceeds 10 ppm. The free chlorine was 11.42. The free chlorine was lowered to 7.17 during inspection.

      Correction: Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE

    • Serious Critical

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

    • Serious Critical

      CO ALARM-POOL AREA

      There is a fuel-burning device in the equipment room located in the indoor pool area pool but no functional CO alarm is provided in the indoor pool area.

      Correction: Provide a CO alarm in the pool area and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)2- CO ALARM POOL AREA

    • Serious Critical

      WATER ATTRACTIONS-WATERSLIDES 6 FEET OR HIGHER, INSPECTION

      A waterslide 6 feet or higher has not been inspected by an engineer or the signed report from the engineer is missing. The last inspection was conducted on 7/26/2017

      Correction: Have an engineer evaluate the waterslide for the structural stability and integrity of the slide and platform and maintain the signed report from the engineer.

      Code ATCP 76.37(2)(c) - WATERSLIDE INSPECTED BY ENGINEER

  4. Jun 9, 2023 Follow Up · 3 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      COMBINED CHLORINE

      The combined chlorine is 1.06.

      Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.

      Code ATCP 76.14(4)(e)

    • Not serious Non-critical Repeat

      MAXIMUM PATRON LOAD NOT POSTED

      The maximum patron load is not posted in the facility.

      Correction: Post the maximum patron load in accordance with ATCP 76.29(1)(d).

      Code [A] ATCP 76.29(1)(d)

    • Not serious Non-critical Repeat

      MONTHLY OPERATION REPORTS NOT SUBMITTED

      Monthly operation reports are not being kept in accordance with ATCP 76.32(1).

      Correction: Keep monthly operation reports in accordance with ATCP 76.32(1).

      Code [A] ATCP 76.32(1)

  5. May 19, 2023 Routine · 5 non-critical, 2 repeat
    • Not serious Non-critical Corrected on site

      pH OUT OF BALANCE

      The pH is 8.1. The pH was adjusted to 7.8 during inspection..

      Correction: Close the pool and do not reopen it until the pH falls between 7.2 and 7.8.

      Code ATCP 76.14(4)(c)

    • Not serious Non-critical

      COMBINED CHLORINE

      The combined chlorine is 1.06.

      Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.

      Code ATCP 76.14(4)(e)

    • Not serious Non-critical Repeat

      TELEPHONE NOT WORKING

      The emergency telephone does not work.

      Correction: Provide a functional emergency telephone immediately.

      Code [A] ATCP 76.26(2)

    • Not serious Non-critical

      MAXIMUM PATRON LOAD NOT POSTED

      The maximum patron load is not posted in the facility.

      Correction: Post the maximum patron load in accordance with ATCP 76.29(1)(d).

      Code [A] ATCP 76.29(1)(d)

    • Not serious Non-critical Repeat

      MONTHLY OPERATION REPORTS NOT SUBMITTED

      Monthly operation reports are not being kept in accordance with ATCP 76.32(1).

      Correction: Keep monthly operation reports in accordance with ATCP 76.32(1).

      Code [A] ATCP 76.32(1)

Source: Central Racine County Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.