Green Ridge Condos

1412 WINDSOR WAY, Mt Pleasant, WI 53406 · Racine County

15cited violations
8serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Central Racine County Health Department
License / ID
HSAT-7QX873
Status
Permitted
Phone
(262) 886-9653
Official record
Central Racine County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026120
20252106
2024132

Inspections

  1. Feb 13, 2026 Routine · 1 non-critical
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      There are missing wiers on some of the skimmer baskets

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      The Main Drain Covers (Aegis 3030AEC) are expired as of 10/29/2024. Current cover is in good shape.

      Correction: Replace the maindrain cover with the make and model number listed above. Send copy of receipt and signed affitdavit.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

  2. Feb 26, 2025 Follow Up · 2 critical, 2 non-critical, 4 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. The turnover rate is 6.54 hours.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of less than 6 hours.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical Repeat

      POOL EQUIPMENT-PROPERLY MAINTAINED

      The pool equipment is not properly maintained.The fittings on both of the pool filters have a leak leading to excess water on the pump room floor and pool deck.

      Correction: Maintain the pool equipment. Repair or replace the fittings to prevent the leak.

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

    • Serious Critical Repeat

      RESPONSIBLE SUPERVISOR RECORDS MAINTAIN

      Responsible supervisor is not ensuring that records are maintained. Monthly pool testing is not being submitted to the health department.

      Correction: Have the responsible supervisor ensure that records are maintained. Submit monthly pool testing by the 10th day of the foolowing month.

      Code ATCP 76.21 (1)(c)7. - RECORDS MAINTENANCE

    • Serious Critical Repeat

      HAZARDOUS CONDITION

      There is a hazardous condition at the pool. The VGBA main drain covers are expired as of 10/29/2024; the covers are intact and installed correctly.

      Correction: Correct the hazardous condition. Replace the VGBA main drain covers by the time of the next routine inspection.

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  3. Feb 25, 2025 Routine · 4 critical, 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. The turnover rate is 6.54 hours.

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of less than 6 hours.

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Not serious Non-critical

      POOL EQUIPMENT-PROPERLY MAINTAINED

      The pool equipment is not properly maintained.The fittings on both of the pool filters have a leak leading to excess water on the pump room floor and pool deck.

      Correction: Maintain the pool equipment. Repair or replace the fittings to prevent the leak.

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

    • Serious Critical

      PH

      The pH is 8.2. The pool is closed until the pH measures at 7.2 to 7.8.

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical

      MAXIMUM BROMINE

      The maximum total bromine exceeds 10 ppm. The total bromine was 15.8 ppm. The pool is closed until the bromine is lowered to between 3-10 ppm.

      Correction: Close the pool until the total bromine residual is in compliance with Table ATCP 76.14 Table A.

      Code ATCP 76.14(5)(g) -MAXIMUM BROMINE

    • Serious Critical Repeat

      RESPONSIBLE SUPERVISOR RECORDS MAINTAIN

      Responsible supervisor is not ensuring that records are maintained. Monthly pool testing is not being submitted to the health department.

      Correction: Have the responsible supervisor ensure that records are maintained. Submit monthly pool testing by the 10th day of the foolowing month.

      Code ATCP 76.21 (1)(c)7. - RECORDS MAINTENANCE

    • Serious Critical

      HAZARDOUS CONDITION

      There is a hazardous condition at the pool. The VGBA main drain covers are expired as of 10/29/2024; the covers are intact and installed correctly.

      Correction: Correct the hazardous condition. Replace the VGBA main drain covers by the time of the next routine inspection.

      Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA

  4. Feb 28, 2024 Routine · 2 critical, 1 non-critical
    • Not serious Non-critical

      RECIRCULATION (TURNOVER) RATE NOT MET

      The recirculation (turnover) rate has not been met. The turnover rate is 7.26 hours..

      Correction: Immediately adjust or repair equipment to operate at a proper turnover rate [6 hours].

      Code ATCP 76.11(4)(c) - RECIRCULATION RATE

    • Serious Critical

      RESPONSIBLE SUPERVISOR RECORDS MAINTAIN

      Responsible supervisor is not ensuring that records are maintained. Monthly testing reports are not being submitted by the 10th day of the following month.

      Correction: Have the responsible supervisor ensure that records are maintained and submitted to the health department.

      Code ATCP 76.21 (1)(c)7. - RECORDS MAINTENANCE

    • Serious Critical

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

Source: Central Racine County Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.