Image Management Family Branch YMCA

8501 CAMPUS DR, Mt Pleasant, WI 53406 · Racine County

14cited violations
3serious tier
5inspections

Establishment

Type
Pool / recreational water (Pool - Moderate)
Inspected by
Central Racine County Health Department
License / ID
KHES-8XGN7A
Status
Permitted
Phone
(262) 880-ance
Official record
Central Racine County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026131
2025110
2024132
2023270

Inspections

  1. Apr 7, 2026 Routine · 1 critical, 2 non-critical
    • Not serious Non-critical

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is 634 mV and water has not been tested manually.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      REAGENTS REPLACED

      Test kit reagents not replaced as recommended by the manufacturer.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Serious Critical

      RING BOUY

      A ring buoy not provided at the whirlpool lifeguard chair

      Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.

      Code ATCP 76.26(1)(b)2.a - RING BOUY

  2. Apr 28, 2025 Routine · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

  3. Apr 17, 2024 Routine · 2 critical, 1 non-critical
    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Serious Critical

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

    • Serious Critical

      CO ALARM-POOL AREA

      There is a fuel-burning device in the equipment room located in the indoor pool area pool but no functional CO alarm is provided in the indoor pool area.

      Correction: Provide a CO alarm in the pool area and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)2- CO ALARM POOL AREA

  4. Jun 9, 2023 Follow Up · 3 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      COMBINED CHLORINE

      The combined chlorine is 1.21.

      Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.

      Code ATCP 76.14(4)(e)

    • Not serious Non-critical Repeat

      MAXIMUM PATRON LOAD NOT POSTED

      The maximum patron load is not posted in the facility.

      Correction: Post the maximum patron load in accordance with ATCP 76.29(1)(d).

      Code [A] ATCP 76.29(1)(d)

    • Not serious Non-critical Repeat

      MONTHLY OPERATION REPORTS NOT SUBMITTED

      Monthly operation reports are not being kept in accordance with ATCP 76.32(1).

      Correction: Keep monthly operation reports in accordance with ATCP 76.32(1).

      Code [A] ATCP 76.32(1)

  5. May 19, 2023 Routine · 4 non-critical, 2 repeat
    • Not serious Non-critical

      COMBINED CHLORINE

      The combined chlorine is 1.21.

      Correction: Treat the pool with breakpoint chlorination using a chlorine product or a nonchlorinated oxidizer.

      Code ATCP 76.14(4)(e)

    • Not serious Non-critical Repeat

      TELEPHONE NOT WORKING

      The emergency telephone does not work..

      Correction: Provide a functional emergency telephone immediately. .

      Code [A] ATCP 76.26(2)

    • Not serious Non-critical

      MAXIMUM PATRON LOAD NOT POSTED

      The maximum patron load is not posted in the facility.

      Correction: Post the maximum patron load in accordance with ATCP 76.29(1)(d).

      Code [A] ATCP 76.29(1)(d)

    • Not serious Non-critical Repeat

      MONTHLY OPERATION REPORTS NOT SUBMITTED

      Monthly operation reports are not being kept in accordance with ATCP 76.32(1).

      Correction: Keep monthly operation reports in accordance with ATCP 76.32(1).

      Code [A] ATCP 76.32(1)

Source: Central Racine County Health Department. History last read Oct 16, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.