RecordWell Data

Big Musky Bar And Resort - Trh

10211W BIG MUSKY RD, Hayward, WI 54843 · Sawyer County

7cited violations
5serious tier
1inspections

Establishment

Type
Lodging (Tourist Rooming House - 2 - 4 TRH)
Inspected by
Sawyer County Health & Human Services
License / ID
KOLN-DV4KS7
Status
Permitted
Phone
(715) 462-3782
Official record
Sawyer County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026175

Inspections

  1. Jun 23, 2026 Pre-inspection · 7 non-critical
    • Serious Critical

      Smoke alarms provided

      Smoke alarms are not provided within each individually keyed unit.

      Correction: Provide smoke alarms within each individually keyed unit at the locations specified in rule.

      Code ATCP 72.18(11)(a)

    • Serious Critical

      Smoke alarm maintained - working order; expiration

      The smoke alarm in the two bedroom cabin is expired

      Correction: Repair or replace the smoke alarm within 5 calendar days.

      Code ATCP 72.18(11)(e)

    • Serious Critical

      Carbon monoxide alarms provided

      A carbon monoxide alarm is not provided anywhere in the lodging facility that also contains a fuel-burning appliance.

      Correction: Provide carbon monoxide alarms at the locations specified in rule.

      Code ATCP 72.18(12)(a)

    • Serious Critical

      Carbon monoxide alarm maintained - working order; expiration

      The carbon monoxide alarm in 2 bedroom cabin, in the hallway, outside of the sleeping room cluster is expired.]

      Correction: Repair or replace the carbon monoxide alarm within 5 calendar days.

      Code ATCP 72.18(12)(h)

    • Serious Critical

      Bunk beds - guards not provided

      The upper bunk bed is not provided with permanently installed guards on the long side of the bunk bed.

      Correction: Provide guard and rotate the bed along the wall and provide access to the window for egress.

      Code ATCP 72.18(3)(d)4.

    • Not serious Priority Foundation

      Smoke alarm installed in each sleeping room

      A smoke alarm is not within each sleeping room. 3 bedroom cabin and 2 bedroom cabin does not have any smoke detectors in bedrooms.

      Correction: Provide a smoke alarm within each sleeping room.

      Code ATCP 72.18(11)(b)3.

    • Not serious Priority Foundation

      Building evacuation diagram (TRH) - posted or provided

      The building evacuation diagram is not conspicuously posted in each sleeping room or is not provided in the check-in materials.

      Correction: Post the building evacuation diagram in each sleeping room or provide in the check-in materials given to guests.

      Code ATCP 72.18(6)(b)1.

Source: Sawyer County Health & Human Services. History last read Oct 17, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.