North Lawndale College Prep
1615 S CHRISTIANA, Chicago, IL 60623 · Cook County
Establishment
- Type
- Food establishment (School)
- Inspected by
- Chicago Department of Public Health
- License / ID
- 1878486
- Status
- Risk 1 (High)
- Official record
- Chicago Department of Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 3 | 0 |
| 2025 | 1 | 1 | 0 |
| 2024 | 2 | 5 | 0 |
| 2023 | 1 | 0 | 0 |
| 2022 | 1 | 2 | 0 |
| 2021 | 1 | 4 | 0 |
| 2020 | 1 | 3 | 0 |
| 2019 | 1 | 1 | 0 |
| 2018 | 1 | 6 | 0 |
| 2017 | 2 | 3 | 2 |
| 2016 | 2 | 7 | 0 |
| 2015 | 1 | 2 | 0 |
| 2014 | 1 | 5 | 1 |
| 2013 | 1 | 4 | 0 |
| 2012 | 1 | 3 | 0 |
| 2011 | 2 | 15 | 0 |
| 2010 | 2 | 10 | 1 |
Inspections
-
Sep 16, 2026 Canvass · Pass — Risk 1 (High)
-
Severity not stated
INSECTS, RODENTS, & ANIMALS NOT PRESENT
OBSERVED 1/4" GAP AT BOTTOM OF NORTHWEST DOOR. INSTRUCTED MANAGER TO SEAL ALL OUTER OPENINGS ON DOORS TO PREVENT PEST ENTRY.
-
Severity not stated
FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
OBSERVED MILK CRATES USED AS SHELVING INSIDE WALK-IN FREEZER. INSTRUCTED MANAGER TO PROVIDE ADEQUATE SHELVING FOR STORAGE.
-
Severity not stated
PLUMBING INSTALLED; PROPER BACKFLOW DEVICES
OBSERVED NO HOT WATER AT LEFT SINK IN GIRLS" SECOND FLOOR WASHROOM AND RIGHT SINK IN BOYS' SECOND FLOOR WASHROOM. INSTRUCTED MANAGER TO REPAIR AND MAINTAIN.
-
Severity not stated
-
Sep 17, 2025 Canvass · Pass — Risk 1 (High)
-
Severity not stated
ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
OBSERVED NO HANDWASHING SIGNAGE IN RESTROOMS THROUGHOUT SCHOOL. INSTRUCTED PERSON IN CHARGE TO PROVIDE AND MAINTAIN HANDWASHING SIGNAGE AT ALL HANDSINKS.
-
Severity not stated
-
Oct 9, 2024 Canvass Re-Inspection · Pass — Risk 1 (High)
-
Severity not stated
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
6-201.11 OUT C 12/20/2024 OBSERVED MISSING AND DAMAGED FLOOR TILES IN THE IN THE KITCHEN ALONG THE SERVING LINE AND PREP TABLE. INSTRUCTED TO REPAIR TO CREATE A SMOOTH AND EASILY CLEANABLE SURFACE. MUST MAINTAIN AT ALL TIMES.
-
Severity not stated
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
6-201.13 OUT C 12/20/2024 OBSERVED BROKEN CEILING PANEL ABOVE FREEZER IN DINNING ROOM. MUST REPAIR OR REPLACE DAMAGED CEILING AND MAINTAIN.
-
Severity not stated
-
Sep 20, 2024 Canvass · Fail — Risk 1 (High)
-
Not serious
Priority Foundation
GARBAGE & REFUSE PROPERLY DISPOSED; FACILITIES MAINTAINED
OBSERVED OUTSIDE DUMPSTER WITH TWO BROKEN LIDS. INSTRUCTED TO CORRECT, REPLACE AND MAINTAIN TO ENSURE TIGHT FITTING LIDS. PRIORITY FOUNDATION VIOLATION #7-38-020(B). NO CITATION ISSUED."
-
Severity not stated
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
OBSERVED MISSING AND DAMAGED FLOOR TILES IN THE IN THE KITCHEN ALONG THE SERVING LINE AND PREP TABLE. INSTRUCTED TO REPAIR TO CREATE A SMOOTH AND EASILY CLEANABLE SURFACE. MUST MAINTAIN AT ALL TIMES.
-
Severity not stated
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
OBSERVED BROKEN CEILING PANEL ABOVE FREEZER IN DINNING ROOM. MUST REPAIR OR REPLACE DAMAGED CEILING AND MAINTAIN.
-
Not serious
Priority Foundation
-
Sep 11, 2023 Canvass · Pass — Risk 1 (High)
Result: Pass.
-
Sep 22, 2022 Canvass · Pass — Risk 1 (High)
-
Severity not stated
ADEQUATE HANDWASHING SINKS PROPERLY SUPPLIED AND ACCESSIBLE
OBSERVED NO HAND WASHING SIGNS IN ADULT RESTROOMS ON FIRST FLOOR. INSTRUCTED PERSON IN CHARGE TO PLACE AND MAINTAIN HANDWASHING SIGNAGE IN ALL RESTROOMS.
-
Severity not stated
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
OBSERVED ITEMS STORED ON FLOOR IN UPSTAIRS COMPUTER SERVER/IT ROOM. INSTRUCTED PERSON IN CHARGE TO ORGANIZE AND ELEVATE ALL ITEMS AT LEAST SIX INCHES FROM FLOOR FOR THE PREVENTION OF PEST HARBORAGE.
-
Severity not stated
-
Sep 10, 2021 Canvass · Pass w/ Conditions — Risk 1 (High)
-
Severity not stated
TOILET FACILITIES: PROPERLY CONSTRUCTED, SUPPLIED, & CLEANED
OBSERVED NO COVERED WASTE RECEPTACLES PROVIDED IN THE WOMEN'S WASHROOM. MUST PROVIDE AND MAINTAIN.
-
Severity not stated
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
OBSERVED DUST BUILD UP AND DEAD INSECTS INSIDE LIGHT SHIELDS COVERS IN LUNCHROOMS AND THROUGHOUT REAR STORAGE AREAS. MUST CLEAN AND MAINTAIN.
-
Severity not stated
ADEQUATE VENTILATION & LIGHTING; DESIGNATED AREAS USED
OBSERVED INADEQUATE LIGHTING IN REAR FOOD STORAGE ROOM. MUST PROVIDE ADEQUATE LIGHTING.
-
Not serious
Priority Foundation
SUMMARY REPORT DISPLAYED AND VISIBLE TO THE PUBLIC
OBSERVED PREVIOUS INSPECTION REPORT SUMMARY NOT POSTED IN VIEW OF CUSTOMERS. MANAGEMENT WAS GIVEN A COPY OF TODAY'S INSPECTION REPORT SUMMARY AND WAS INSTRUCTED TO POST IT IN VIEW OF ALL CUSTOMERS. PRIORITY FOUNDATION 7-42-010(B).
-
Severity not stated
-
Sep 17, 2020 Canvass · Pass — Risk 1 (High)
-
Severity not stated
FOOD-CONTACT SURFACES: CLEANED & SANITIZED
OBSERVED THE ICE BIN INTERIOR IN NEED OF CLEANING. INSTRUCTED TO REMOVE ICE, CLEAN AND MAINTAIN AT ALL TIMES.
-
Severity not stated
FOOD & NON-FOOD CONTACT SURFACES CLEANABLE, PROPERLY DESIGNED, CONSTRUCTED & USED
OBSERVED MILK CRATES BEING USED AS SHELVING THROUGHOUT THE WALK-IN FREEZER. MUST REMOVE AND PROVIDE SHELVING THAT IS 6" OFF THE FLOOR AND PROVIDES FLOOR ACCESSIBILITY TO ENSURE ADEQUATE FACILITY CLEANING.
-
Severity not stated
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
OBSERVED BROKEN COVING ALONG THE WALL IN THE DRY STORAGE ROOM. INSTRUCTED TO REPAIR AND MAINTAIN.
-
Severity not stated
-
Mar 27, 2019 Canvass · Pass — Risk 1 (High)
-
Severity not stated
PHYSICAL FACILITIES INSTALLED, MAINTAINED & CLEAN
EXTREME CLUTTER IN STORAGE ROOM 008 ACROSS FROM CAFETERIA. INSTD TO REMOVE CLUTTER/UNNECESSARRY ARTICLES AND ORGANIZE
-
Severity not stated
-
Feb 16, 2018 Canvass · Pass w/ Conditions — Risk 1 (High)
-
Not serious
Serious (Chicago's middle tier)
OUTSIDE GARBAGE WASTE GREASE AND STORAGE AREA; CLEAN, RODENT PROOF, ALL CONTAINERS COVERED
OBSERVED OUTSIDE GARBAGE DUMPSTER AREA NOT MAINTAINED.OBSERVED TRASH BAGS OVER FLOWING ABOVE RIM OF DUMPSTER AND LIDS WIDE OPEN,TRASH AND DEBRIS ON GROUND AROUND DUMPSTER.MUST PLACE TRASH BAGS AND DEBRIS IN DUMPSTER & KEEP LIDS CLOSED AND MAINTAIN.TRASH BAGS ,DEBRIS ARE INSIDE OF DUMPSTERS AND LIDS ARE TIGHT FITTING NOW.(NO CITATION ISSUED)
-
Not serious
Minor
FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
MUST CLEAN DEBRIS BUILD UP FROM INTERIOR PANEL OF ICE MACHINE,MICROWAVE AND TABLE IN LUNCHROOM.
-
Not serious
Minor
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
MUST CLEAN DEBRIS FROM FLOOR IN WALK IN COOLER AND EXCESSIVE BUILD ON FLOOR UNDER 3- COMP SINK.MUST REPAIR OR REPLACE DAMAGED FLOORING IN PREP AREA,DISH WASHING AREA,LUNCHROOM AND MISSING FLOOR TILE IN STAFF LOUNGE.
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
MUST REPAIR OR REPLACE STAINED CEILING TILES IN KITCHEN OFFICE,PREP AREA,MISSING AND STAINED CEILING TILES IN GROUND LEVEL (B&G) ,2ND FL. (B)TOILETROOMS,CEILING IN LUNCHROOM IN POOR REPAIR,LOOSE WALL BASE , MISSING WALL PANEL AND HOLE IN WALL NEAR MICROWAVE IN LUNCHROOM.MUST CLEAN WALLS NEAR 3- COMP SINK,CEILING & LIGHT SHILEDS IN LUNCHROOM.MUST SCRAPE PEELING PAINT ON UPPER WALL NEAR SKYLIGHT AT SERVING LINE AND VENTILATION UNIT IN LUNCHROOM ABOVE TABLES.
-
Not serious
Minor
LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
MUST PROVIDE SHATTER PROOF BULBS ABOVE SERVING LINE.
-
Not serious
Minor
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
MUST REPAIR OR REPLACE LOW HOT & COLD WATER PRESSURE AT HAND SINK IN PREP AREA.MUST ADJUST FAUCET HANDLES AT HAND SINKS TO STAY ON LONGER IN GROUND LEVEL (B & G),3RD FL.(G).
-
Not serious
Serious (Chicago's middle tier)
-
May 2, 2017 Canvass Re-Inspection · Pass — Risk 1 (High)
Result: Pass.
-
Apr 25, 2017 Canvass · Fail — Risk 1 (High)
-
Serious
Critical
FACILITIES TO MAINTAIN PROPER TEMPERATURE
OBSERVED WALK-IN COOLER IN POOR REPAIR, NOT HOLD AT 40'F AND BELOW, COOLER READING 60'F, INSTRUCTED TO RESTRICT USE, COOLER TAGGED, MUST FAX LETTER FOR RE-INSPECTION, ONCE REPAIR, CRITICAL VIOLATION: 7-38-005A
-
Serious
Critical
POTENTIALLY HAZARDOUS FOOD MEETS TEMPERATURE REQUIREMENT DURING STORAGE, PREPARATION DISPLAY AND SERVICE
OBSERVED POTENTIALLY HAZARDOUS FOODS STORED IN WALK-IN COOLER AT IMPROPER TEMPS, (2) ROLLS OF GROUND BEEF, COOKED CHICKEN, (4) BAGS OF ROAST BEEF, AND (1) BAG OF YOGURT, ALL READING BETWEEN 50'F-58'F, ALL PRODUCT DUMPED AND DENATURED AT A COST OF ABOUT $1,000.00 AND ABOUT 30 POUNDS, CRITICAL VIOLATION: 7-38-005A
-
Not serious
Serious (Chicago's middle tier)
PREVIOUS MINOR VIOLATION(S) CORRECTED 7-42-090
CONTINUED NON COMPLIANCE ON PREVIOUS ORDER ISSUED, DATED 05/12/2016, REPORT #1770612, VIOLATION LISTED BELOW: 34 FLOORS IN POOR REPAIR IN KITCHEN AREA, CRACKED FLOOR TILE NEEDS REPLACED, 35 WALLS IN POOR REPAIR IN DINING AREA, HOLES AND BROKEN PLASTER, INSTRUCTED TO REPAIR, AND BETTER MAINTAIN, SERIOUS VIOLATION: 7-42-090
-
Serious
Critical
-
May 12, 2016 Canvass Re-Inspection · Pass — Risk 1 (High)
-
Not serious
Minor
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
FLOORS IN POOR REPAIR IN KITCHEN AREA, CRACKED FLOOR TILE NEEDS REPLACED,
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
WALLS IN POOR REPAIR IN DINING AREA, HOLES AND BROKEN PLASTER, INSTRUCTED TO REPAIR, AND BETTER MAINTAIN,
-
Not serious
Minor
TOILET ROOM DOORS SELF CLOSING: DRESSING ROOMS WITH LOCKERS PROVIDED: COMPLETE SEPARATION FROM LIVING/SLEEPING QUARTERS
EMPLOYEES PERSONAL ITEMS STORED ON FOOD PRODUCT IN DRY STORAGE AREA, INSTRUCTED TO PROVIDE STORAGE SPACE TO STORE PERSONAL BELONGINGS,
-
Not serious
Minor
-
May 5, 2016 Canvass · Fail — Risk 1 (High)
-
Not serious
Serious (Chicago's middle tier)
NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
NO PEST CONTROL LOG BOOK AVAILABLE AT THIS TIME OF INSPECTION, INSTRUCTED TO HAVE UPON NEXT VISIT, SERIOUS VIOLATION 7-38-020.
-
Not serious
Minor
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
FLOORS IN POOR REPAIR IN KITCHEN AREA, CRACKED FLOOR TILE NEEDS REPLACED,
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
WALLS IN POOR REPAIR IN DINING AREA, HOLES AND BROKEN PLASTER, INSTRUCTED TO REPAIR, AND BETTER MAINTAIN,
-
Not serious
Minor
TOILET ROOM DOORS SELF CLOSING: DRESSING ROOMS WITH LOCKERS PROVIDED: COMPLETE SEPARATION FROM LIVING/SLEEPING QUARTERS
EMPLOYEES PERSONAL ITEMS STORED ON FOOD PRODUCT IN DRY STORAGE AREA, INSTRUCTED TO PROVIDE STORAGE SPACE TO STORE PERSONAL BELONGINGS,
-
Not serious
Serious (Chicago's middle tier)
-
Mar 27, 2015 Canvass · Pass — Risk 1 (High)
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
OBSERVED DAMAGED CEILING TILES ABOVE THE LAST TOILET IN THE GIRLS WASHROOM ON THE FIRST FLOOR; REPLACE DAMAGED CEILING TILE.
-
Not serious
Minor
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
MUST CORRECT THE FOLLOWING PLUMBING VIOLATIONS: THE FIRST FLOOR GIRLS WASHROOM HAS ONE SINK WITH NO HOT RUNNING WATER (FIRST SINK); RESTORE HOT RUNNING WATER TO THIS SINK. OBSERVED A LEAK AT THE HOT WATER FAUCET WHEN IN USE IN THE STAFF WASHROOM ON THE FIRST FLOOR NEAR ROOM 106; REPAIR LEAK AT FAUCET. NO VENTILATION OBSERVED OVER THE CONVECTION OVEN IN THE KITCHEN USED FOR COOKING; MUST PROVIDE PROPER VENTILATION. (IF OVEN IS BELOW 7.5KW OR 7500 WATTS, NO VENTILATION IS NEEDED; HOWEVER DOCUMENTATION MUST BE PROVIDED TO VERIFY).
-
Not serious
Minor
-
May 2, 2014 Canvass · Pass w/ Conditions — Risk 1 (High)
-
Serious
Critical
POTENTIALLY HAZARDOUS FOOD MEETS TEMPERATURE REQUIREMENT DURING STORAGE, PREPARATION DISPLAY AND SERVICE
LARGE, DEEP PAN OF COOKED RICE DATED YESTERDAY AT IMPROPER STORAGE TEMPERATURE OF 48.5F IN WALK-IN COOLER. INSTD MGR ON PROPER COOLING TECHNIQUES TO ENSURE PROPER TEMPERATURE. CITATION ISSUED 7-38-005A CRITICAL. APPROX 15LBS $50 VALUE
-
Not serious
Minor
FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
INTERIOR BOTTOM OF MILK/JUICE COOLER WITH RUSTY SURFACES AND ALUMINUM FOIL ON SHLEVES. INSTD TO REMOVE BOTH FOIL AND RUST SO AS SURFACES TO BE SMOOTH, EVEN, EASILY CLEANABLE SURFACE.
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
REPLACE MISSING DOOR ON STAFF TOILET ROOM 1ST FLOOR.
-
Not serious
Minor
LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
LIGHTS OUT IN 2ND FLOOR UTILITY SINK CLOSET AND 1ST FLOOR STORAGE CLOSET. REPLACE LIGHTS. NO LIGHTSHIELDS IN PREP AREA ABOVE SERVING LINE AND BY 3-COMPARTMENT SINK. PROVIDE SAME.
-
Not serious
Minor
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
BASEMENT STAFF TOILET AND BOYS HOT WATER FAUCET IN POOR REPAIR, LEAKING. REPAIR SAME.
-
Serious
Critical
-
Jan 29, 2013 Canvass · Pass — Risk 1 (High)
-
Not serious
Minor
FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
THE ICE MACHINE DOOR INTERIOR IS DIRTY; WASH, RINSE AND SANITIZE THE ICE MACHINE DOOR.
-
Not serious
Minor
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
THE FLOORS AND BASEBOARDS ALONG THE PERIMETER OF THE CAFETERIA DINING AND SERVING AREA ARE DIRTY AND SOME OLD ANT ACTIVITY WAS FOUND, CLEAN AND SEAL UP SAID AREAS TO PREVENT POSSIBLE HARBORAGE.
-
Not serious
Minor
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
THE KITCHEN PANTRY IS PACKED WITH ITEMS IN THE REAR AND DIFFICULT TO MONITOR AND CLEAN, REMOVE AND REORGANIZE THE ABOVE AREA. THE MOP AND CLEANING SUPPLY CLOSETS ARE DIRTY AND UNORGANIZED, MAINTAIN THE ABOVE AREAS ON A DAILY BASIS.
-
Not serious
Minor
FOOD (ICE) DISPENSING UTENSILS, WASH CLOTHS PROPERLY STORED
THE ICE SCOOP HOLDER IS DIRTY; WASH, RINSE AND SANITIZE THE ABOVE.
-
Not serious
Minor
-
Mar 22, 2012 Canvass · Pass w/ Conditions — Risk 1 (High)
-
Not serious
Serious (Chicago's middle tier)
CERTIFIED FOOD MANAGER ON SITE WHEN POTENTIALLY HAZARDOUS FOODS ARE PREPARED AND SERVED
A certified food service manager must be present in all establishments at which potentially hazardous food is prepared or served. KITCHEN MANAGER ON SITE HAS NO VALID CITY OF CHICAGO FOOD SANITATION CERTIFICATE AS REQUIRED. SHOWED A STATE OF ILLINOIS CERTIFICATE ISSUED IN 2009; INSTRUCTED TO OBTAIN A CITY OF CHICAGO CERTIFICATE.
-
Not serious
Minor
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. FLOOR NEEDS CLEANING IN ROOM 205A TO REMOVE TRASH AND OTHER ITEMS.
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
The walls and ceilings shall be in good repair and easily cleaned. REPLACE MISSING WALL COVING AT ONE WALL NEAR EXIT DOOR OF LUNCHROOM. SEAL HOLE IN WALL OF BOYS WASHROOM ON SECOND FLOOR BY WINDOW AND REPLACE MISSING CEILING TILE IN SAME WASHROOM.
-
Not serious
Serious (Chicago's middle tier)
-
May 4, 2011 Canvass Re-Inspection · Pass — Risk 1 (High)
-
Not serious
Minor
FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
Inspector Comments: All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair.MUST REPAIR OR REPLACE WORN DOOR GASKET ON MILK COOLER,MISSING LOCK ON STALL TOILET ROOM DOOR IN 3RD FL. GIRL'S.
-
Not serious
Minor
FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
Inspector Comments: All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN INTERIOR OF ICE MACHINE PANEL,OFFICE 1- COMP VANITY & MICRO WAVE,LIGHT SHIELD IN 3RD FL. STAFF,MDF ROOM MICROWAVE,STAFF LOUNGE MICROWAVE & REFRIGERATOR.
-
Not serious
Minor
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
Inspector Comments: The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST REPAIR OR REPLACE DRY FOOD STORAGE AREA FLOOR TILES DAMAGED,LUNCH ROOM.MUST CLEAN FLOOR IN BOILER ROOM,ROOM 205A & 108B.
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
Inspector Comments: The walls and ceilings shall be in good repair and easily cleaned.MUST REPAIR OR REPLACE DAMAGED WALLS ,LOOSE & MISSING WALL BASES IN LUNCH ROOM & BASEMENT STAFF TOILET ROOM,CEILING TILES STAINED & MISSING IN BASEMENT MEN'S & 3RD FL. GIRL'S.MUST SCRAPE & PAINT PEELING PAINT ON WALLS & VENTS IN LUNCH ROOM,BASEMENT STAFF (W),3RD & 1ST FL. STAFF TOILET ROOM.
-
Not serious
Minor
LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
Inspector Comments: All rooms in which food or drink is prepared, or in which utensils are washed, shall be lighted so that a minimum of 50-foot candles of light is available on all work surfaces.MUST REPLACE BURNT OUT BULB IN 3RD FL. STAFF TOILET ROOM.
-
Not serious
Minor
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
Inspector Comments: Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health.MUST REPAIR OR REPLACE LEAKY TOILET IN 3RD FL. (G) & BASEMENT STAFF (W).NO HOT RUNNING WATER AT HAND SINK IN 3RD FL (STAFF).
-
Not serious
Minor
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
Inspector Comments: All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST ELEVATE ARTICLES OFF OF FLOOR IN BOILER ROOM.
-
Not serious
Minor
-
Apr 26, 2011 Canvass · Fail — Risk 1 (High)
-
Not serious
Serious (Chicago's middle tier)
NO EVIDENCE OF RODENT OR INSECT OUTER OPENINGS PROTECTED/RODENT PROOFED, A WRITTEN LOG SHALL BE MAINTAINED AVAILABLE TO THE INSPECTORS
All necessary control measures shall be used to effectively minimize or eliminate the presence of rodents, roaches, and other vermin and insects on the premises of all food establishments, in food-transporting vehicles, and in vending machines.OBSERVED EVIDENCE OF MORE THAN 150 RODENT DROPPINGS SCATTERED IN VARIOUS AREAS SUCH AS BEHIND WALK IN FREEZER,STORAGE ROOM 008,OFFICE CONFERENCE ROOM,MDF ROOM,ROOM 205A,2ND FL. TEACHERS LOUNGE,ROOM 108 A & B.ALSO A DEAD MOUSE ON FLOOR IN BOILER ROOM & BAG OF POISON ON FLOOR UNDER RAMP IN BOILER ROOM.MUST REMOVE DROPPINGS & POISON,CLEAN & SANITIZE AREAS.RECOMMENDED TO HAVE A PEST CONTROL OPERATOR TO SERVICE PREMISES ON OR AFTER 4/26/11.
-
Not serious
Minor
FOOD AND NON-FOOD CONTACT SURFACES PROPERLY DESIGNED, CONSTRUCTED AND MAINTAINED
All food and non-food contact equipment and utensils shall be smooth, easily cleanable, and durable, and shall be in good repair.MUST REPAIR OR REPLACE WORN DOOR GASKET ON MILK COOLER,MISSING LOCK ON STALL TOILET ROOM DOOR IN 3RD FL. GIRL'S.
-
Not serious
Minor
FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
All food and non-food contact surfaces of equipment and all food storage utensils shall be thoroughly cleaned and sanitized daily.MUST CLEAN INTERIOR OF ICE MACHINE PANEL,OFFICE 1- COMP VANITY & MICRO WAVE,LIGHT SHIELD IN 3RD FL. STAFF,MDF ROOM MICROWAVE,STAFF LOUNGE MICROWAVE & REFRIGERATOR.
-
Not serious
Minor
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair.MUST REPAIR OR REPLACE DRY FOOD STORAGE AREA FLOOR TILES DAMAGED,LUNCH ROOM.MUST CLEAN FLOOR IN BOILER ROOM,ROOM 205A & 108B.
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
The walls and ceilings shall be in good repair and easily cleaned.MUST REPAIR OR REPLACE DAMAGED WALLS ,LOOSE & MISSING WALL BASES IN LUNCH ROOM & BASEMENT STAFF TOILET ROOM,CEILING TILES STAINED & MISSING IN BASEMENT MEN'S & 3RD FL. GIRL'S.MUST SCRAPE & PAINT PEELING PAINT ON WALLS & VENTS IN LUNCH ROOM,BASEMENT STAFF (W),3RD & 1ST FL. STAFF TOILET ROOM.
-
Not serious
Minor
LIGHTING: REQUIRED MINIMUM FOOT-CANDLES OF LIGHT PROVIDED, FIXTURES SHIELDED
All rooms in which food or drink is prepared, or in which utensils are washed, shall be lighted so that a minimum of 50-foot candles of light is available on all work surfaces.MUST REPLACE BURNT OUT BULB IN 3RD FL. STAFF TOILET ROOM.
-
Not serious
Minor
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health.MUST REPAIR OR REPLACE LEAKY TOILET IN 3RD FL. (G) & BASEMENT STAFF (W).NO HOT RUNNING WATER AT HAND SINK IN 3RD FL (STAFF).
-
Not serious
Minor
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
All parts of the food establishment and all parts of the property used in connection with the operation of the establishment shall be kept neat and clean and should not produce any offensive odors.MUST ELEVATE ARTICLES OFF OF FLOOR IN BOILER ROOM.
-
Not serious
Serious (Chicago's middle tier)
-
Nov 8, 2010 Canvass · Pass — Risk 1 (High)
-
Not serious
Minor
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST CLEAN FLOORS IN STORAGE ROOMS/CLOSETS, MDF ROOM, ROOM 205A AND TEACHERS LOUNGE 209.
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
The walls and ceilings shall be in good repair and easily cleaned. MUST REPAIR WALLS INSIDE MDF ROOM.
-
Not serious
Minor
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR/REPLACE FAUCETS IN BOYS WASHROOM AT HAND SINKS NEAR KITCHEN/NORTH AREA.
-
Not serious
Minor
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
MUST REMOVE UNNECESSARY ARTICLES THRU-OUT ROOM 308A AND 208B, CLEAN AND ORGANIZE TO PREVENT PEST HARBORAGE. ARTICLES MUST BE OFF FLOORS, AWAY FROM WALLS.
-
Not serious
Minor
-
Mar 22, 2010 Canvass · Pass w/ Conditions — Risk 1 (High)
-
Serious
Critical
HAND WASHING FACILITIES: WITH SOAP AND SANITARY HAND DRYING DEVICES, CONVENIENT AND ACCESSIBLE TO FOOD PREP AREA
Adequate and convenient hand washing facilities shall be provided for all employees. NO SANITARY HAND DRYING DEVICES/PAPER TOWELS IN ANY STUDENTS WASHROOMS THRU-OUT BUILDING. INSTRUCTED MUST PROVIDE PAPER TOWELS AT ALL TIMES. CITATION ISSUED 7-38-030 CRITICAL.
-
Not serious
Minor
FOOD AND NON-FOOD CONTACT EQUIPMENT UTENSILS CLEAN, FREE OF ABRASIVE DETERGENTS
All utensils shall be thoroughly cleaned and sanitized after each usage. MUST CLEAN-SANITIZE; MICROWAVE OVEN AND COOLER INSIDE TEACHER'S LOUNGE.
-
Not serious
Minor
FLOORS: CONSTRUCTED PER CODE, CLEANED, GOOD REPAIR, COVING INSTALLED, DUST-LESS CLEANING METHODS USED
The floors shall be constructed per code, be smooth and easily cleaned, and be kept clean and in good repair. MUST REPLACE MISSING AND BROKEN FLOOR TILES IN LUNCHROOM, AND CLEAN FLOORS THRU-OUT BUILDING, UNDER, BEHIND EQUIPMENT AT CORNERS AND ALONG WALLS.
-
Not serious
Minor
WALLS, CEILINGS, ATTACHED EQUIPMENT CONSTRUCTED PER CODE: GOOD REPAIR, SURFACES CLEAN AND DUST-LESS CLEANING METHODS
The walls and ceilings shall be in good repair and easily cleaned. MUST REPAIR WALLS WHERE NEEDED THRU-OUT BUILDING, AND SEAL OPENINGS TO PREVENT PEST ENTRY.
-
Not serious
Minor
VENTILATION: ROOMS AND EQUIPMENT VENTED AS REQUIRED: PLUMBING: INSTALLED AND MAINTAINED
Ventilation: All plumbing fixtures, such as toilets, sinks, washbasins, etc., must be adequately trapped, vented, and re-vented and properly connected to the sewer in accordance with the plumbing chapter of the Municipal Code of Chicago and the Rules and Regulations of the Board of Health. MUST REPAIR BASEMENT WASHROOMS FAUCETS AND PROVIDE ADEQUATE WATER PRESSURE, SAME SINKS.
-
Not serious
Minor
PREMISES MAINTAINED FREE OF LITTER, UNNECESSARY ARTICLES, CLEANING EQUIPMENT PROPERLY STORED
EXCESSIVE CLUTTER THRU-OUT CLOSETS AND STORAGE ROOMS, MUST CLEAN, ORGANIZE, REMOVE UNNECESSARY ARTICLES AND STORED ARTICLES OFF FLOORS, AWAY FROM WALLS TO PREVENT PEST HARBORAGE.
-
Serious
Critical
Source: Chicago Department of Public Health. History last read Oct 8, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.