Comfort Suites (pool)

300 N DIVISION ST, Stevens Point, WI 54481 · Portage County

14cited violations
3serious tier
3inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Portage County Health & Human Services
License / ID
CHES-DEGM37
Status
Permitted
Phone
(715) 544-0048
Official record
Portage County Health & Human Services inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20253143

Inspections

  1. Sep 2, 2025 Follow Up · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      AIR MOVEMENT

      Heating, ventilation, and exhaust equipment not maintained and operated to provide air movement to prevent any excessive condensation. Pool enclosure is extremely humid, condensation is observed on surfaces.

      Correction: Maintain heating, ventilation, and exhaust equipment to provide air movement to prevent any excessive condensation. A referral to building inspection department or fire department will be made.

      Code ATCP 76.33(4)(b) - AIR MOVEMENT

  2. Aug 12, 2025 Routine · 2 critical, 7 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not being maintained in operating condition. Meter is stuck.

      Correction: Adjust or repair the flowmeter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      BIOHAZARD KIT-AVAILABLE

      A biohazard kit is not available in the pool area.

      Correction: Provide a biohazard kit for the pool.

      Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE

    • Not serious Non-critical

      TOILET ROOMS-CLEAN

      Toilet room is not kept clean. Fixtures and flooring require cleaning.

      Correction: Keep the toilet rooms clean.

      Code ATCP 76.33 (2)(c)1. TOILET ROOM CLEAN

    • Not serious Non-critical

      SOAP-PROVIDED

      Soap is not provided in the bathroom shower.

      Correction: Provide soap in the bathroom shower.

      Code ATCP 76.33 (2)(e)1. - SOAP

    • Not serious Non-critical

      POOL BASIN MAINTAINED FREE OF DEFECTS

      Several pool wall tiles are missing.

      Correction: Replace missing pool wall tiles. Maintain the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

    • Not serious Non-critical

      AIR MOVEMENT

      Heating, ventilation, and exhaust equipment not maintained and operated to provide air movement to prevent any excessive condensation. Pool enclosure is extremely humid, condensation is observed on surfaces.

      Correction: Maintain heating, ventilation, and exhaust equipment to provide air movement to prevent any excessive condensation. A referral to building inspection department or fire department will be made.

      Code ATCP 76.33(4)(b) - AIR MOVEMENT

    • Not serious Non-critical

      ELECTRICAL GOOD REPAIR

      Pool light is not operational

      Correction: Repair pool light to operating condition.

      Code ATCP 76.33(4)(c) - GOOD REPAIR

    • Serious Critical

      HOSING - BACKFLOW PREVENTION DEVICE

      A backflow prevention device is not provided on hose bib in mechanical room.

      Correction: Provide a back flow preventer on hose bib.

      Code ATCP 76.33(1)(d)2. - BACKFLOW PREVENTION

    • Serious Critical

      CO ALARM-POOL AREA

      There is a fuel-burning device in the equipment room located in the indoor pool area pool but no functional CO alarm is provided in the indoor pool area.

      Correction: Provide a CO alarm in the pool area and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)2- CO ALARM POOL AREA

  3. Mar 20, 2025 Pre-inspection · 1 critical, 3 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not operational.

      Correction: Adjust or repair the flowmeter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      SAFETY DATA SHEET

      The safety data sheets are not available for pool chemicals (ex. sodium hypochlorite and sulfuric acid).

      Correction: Maintain safety data sheets for each chemical on site.

      Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS

    • Not serious Non-critical

      AIR MOVEMENT

      The ventilation system is not providing adequate air movement to prevent excessive condensation. Condensation is observed on surfaces in pool enclosure.

      Correction: Maintain heating, ventilation, and exhaust equipment to provide air movement to prevent any excessive condensation.

      Code ATCP 76.33(4)(b) - AIR MOVEMENT

    • Serious Critical

      HOSING - BACKFLOW PREVENTION DEVICE

      A backflow prevention device is not installed on the hosing located in pool mechanical room.

      Correction: Provide a backflow prevention device on hose.

      Code ATCP 76.33(1)(d)2. - BACKFLOW PREVENTION

Source: Portage County Health & Human Services. History last read Oct 19, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.