Comfort Suites (pool)
300 N DIVISION ST, Stevens Point, WI 54481 · Portage County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Portage County Health & Human Services
- License / ID
- CHES-DEGM37
- Status
- Permitted
- Phone
- (715) 544-0048
- Official record
- Portage County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2025 | 3 | 14 | 3 |
Inspections
-
Sep 2, 2025 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
AIR MOVEMENT
Heating, ventilation, and exhaust equipment not maintained and operated to provide air movement to prevent any excessive condensation. Pool enclosure is extremely humid, condensation is observed on surfaces.
Correction: Maintain heating, ventilation, and exhaust equipment to provide air movement to prevent any excessive condensation. A referral to building inspection department or fire department will be made.
Code ATCP 76.33(4)(b) - AIR MOVEMENT
-
Not serious
Non-critical
Repeat
-
Aug 12, 2025 Routine · 2 critical, 7 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not being maintained in operating condition. Meter is stuck.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
BIOHAZARD KIT-AVAILABLE
A biohazard kit is not available in the pool area.
Correction: Provide a biohazard kit for the pool.
Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE
-
Not serious
Non-critical
TOILET ROOMS-CLEAN
Toilet room is not kept clean. Fixtures and flooring require cleaning.
Correction: Keep the toilet rooms clean.
Code ATCP 76.33 (2)(c)1. TOILET ROOM CLEAN
-
Not serious
Non-critical
SOAP-PROVIDED
Soap is not provided in the bathroom shower.
Correction: Provide soap in the bathroom shower.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Not serious
Non-critical
POOL BASIN MAINTAINED FREE OF DEFECTS
Several pool wall tiles are missing.
Correction: Replace missing pool wall tiles. Maintain the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.
Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR
-
Not serious
Non-critical
AIR MOVEMENT
Heating, ventilation, and exhaust equipment not maintained and operated to provide air movement to prevent any excessive condensation. Pool enclosure is extremely humid, condensation is observed on surfaces.
Correction: Maintain heating, ventilation, and exhaust equipment to provide air movement to prevent any excessive condensation. A referral to building inspection department or fire department will be made.
Code ATCP 76.33(4)(b) - AIR MOVEMENT
-
Not serious
Non-critical
ELECTRICAL GOOD REPAIR
Pool light is not operational
Correction: Repair pool light to operating condition.
Code ATCP 76.33(4)(c) - GOOD REPAIR
-
Serious
Critical
HOSING - BACKFLOW PREVENTION DEVICE
A backflow prevention device is not provided on hose bib in mechanical room.
Correction: Provide a back flow preventer on hose bib.
Code ATCP 76.33(1)(d)2. - BACKFLOW PREVENTION
-
Serious
Critical
CO ALARM-POOL AREA
There is a fuel-burning device in the equipment room located in the indoor pool area pool but no functional CO alarm is provided in the indoor pool area.
Correction: Provide a CO alarm in the pool area and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)2- CO ALARM POOL AREA
-
Not serious
Non-critical
-
Mar 20, 2025 Pre-inspection · 1 critical, 3 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flowmeter is not operational.
Correction: Adjust or repair the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
SAFETY DATA SHEET
The safety data sheets are not available for pool chemicals (ex. sodium hypochlorite and sulfuric acid).
Correction: Maintain safety data sheets for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
AIR MOVEMENT
The ventilation system is not providing adequate air movement to prevent excessive condensation. Condensation is observed on surfaces in pool enclosure.
Correction: Maintain heating, ventilation, and exhaust equipment to provide air movement to prevent any excessive condensation.
Code ATCP 76.33(4)(b) - AIR MOVEMENT
-
Serious
Critical
HOSING - BACKFLOW PREVENTION DEVICE
A backflow prevention device is not installed on the hosing located in pool mechanical room.
Correction: Provide a backflow prevention device on hose.
Code ATCP 76.33(1)(d)2. - BACKFLOW PREVENTION
-
Not serious
Non-critical
Source: Portage County Health & Human Services. History last read Oct 19, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.