Kairos Cottage LLC
2333 DIXON ST, Stevens Point, WI 54481 · Portage County
Establishment
- Type
- Lodging (Tourist Rooming House - 1 TRH)
- Inspected by
- Portage County Health & Human Services
- License / ID
- CHES-CS5L22
- Status
- Permitted
- Phone
- (608) 438-6597
- Official record
- Portage County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 6 | 2 |
| 2023 | 1 | 0 | 0 |
Inspections
-
May 14, 2026 Routine · 6 non-critical
-
Serious
Critical
Carbon monoxide alarms provided
A carbon monoxide alarm is not provided anywhere in the lodging facility that also contains a fuel-burning appliance.
Correction: Provide carbon monoxide alarms at the locations specified in rule.
Code ATCP 72.18(12)(a)
-
Serious
Critical
Basement or ground floor sleeping room - 2 exits provided
The basement bedroom used for sleeping is not provided with at least 2 separate exits.
Correction: Provide at least 2 separate exits from the basement or ground floor used for sleeping or discontinue sleeping from that floor.
Code ATCP 72.18(4)(ar)
-
Not serious
Priority Foundation
Smoke alarm installed on each floor
A smoke alarm is not provided on each floor level. The lower level and upper level loft do not have smoke alarms.
Correction: Provide a smoke alarm on each floor level to include a basement or ground floor and at the top of any stairway but excluding crawl spaces and unfinished attics.
Code ATCP 72.18(11)(b)1.
-
Not serious
Priority Foundation
Smoke alarm installed outside each separate sleeping area
A smoke alarm is not provided outside of each separate sleeping area, within 21 feet of any door to a sleeping room. The upper level loft does not have a smoke alarm.
Correction: Provide a smoke alarm outside of each separate sleeping area, within 21 feet of any door to a sleeping room.
Code ATCP 72.18(11)(b)2.
-
Not serious
Priority Foundation
Smoke alarm installed in each sleeping room
A smoke alarm is not within each sleeping room. The main level bedroom and upper loft does not have a smoke alarm.
Correction: Provide a smoke alarm within each sleeping room.
Code ATCP 72.18(11)(b)3.
-
Not serious
Priority Foundation
Building evacuation diagram (TRH) - posted or provided
A building evacuation diagram is not posted in each sleeping room or is not provided in the check-in materials.
Correction: Provide a building evacuation diagram in each sleeping room or provide in the check-in materials given to guests.
Code ATCP 72.18(6)(b)1.
-
Serious
Critical
-
May 24, 2023 Pre-inspection · No items found
No violations cited.
Source: Portage County Health & Human Services. History last read Oct 19, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.