Lakewood Villages Home Owners

42950, 42910, 42850 LAKEWOODS DR, Cable, WI 54821 · Bayfield County

15cited violations
1serious tier
3inspections

Establishment

Type
Lodging (Hotel and Motel - 31 - 99 Rooms)
Inspected by
Bayfield County Health Department
License / ID
BHEP-8FLKZK
Status
Permitted
Official record
Bayfield County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026161
2025110
2024180

Inspections

  1. Sep 9, 2026 Routine · 6 non-critical
    • Serious Critical

      Carbon monoxide alarm maintained - working order; expiration

      The carbon monoxide alarm in living room is not expired [replaced in accordance with the manufacturer’s date of expiration.]

      Correction: Repair or replace the carbon monoxide alarm within 5 calendar days.

      Code ATCP 72.18(12)(h)

    • Not serious Priority Foundation

      Bunk beds - guards 5" above mattress

      The top of the guard was less than 5 inches above the top of the mattress of the upper bunk bed in Hemlock unit

      Correction: Reconstruct the top guard or install a thinner mattress to provide at least 5 inches above the top of the mattress.

      Code ATCP 72.18(3)(d)4.a.

    • Not serious Priority Foundation

      Building evacuation diagram (TRH) - posted or provided

      The building evacuation diagram is not conspicuously posted in each sleeping room or is not provided in the check-in materials.

      Correction: Post the building evacuation diagram in each sleeping room or provide in the check-in materials given to guests.

      Code ATCP 72.18(6)(b)1.

    • Not serious Priority Foundation

      Guest-provided sanitization - sanitizer provided

      A chemical sanitizer for utensils is not provided.

      Correction: The chemical sanitizer must be available or made available upon request.

      Code ATCP 72.20(6)(e)4.

    • Not serious Non-critical

      Equipment and furnishings - maintained clean

      Thejetted tub locatedHemlock - unit designated in notes, is not clean. Hair in the inlet and dirt/scum around the jets

      Correction: All furnishings and equipment and shall be kept clean.

      Code ATCP 72.20(4)(a)

    • Not serious Non-critical

      Nonabsorbent mattress cover or mattress surface

      The mattressin all buildings had missing protectors. Provide units with a nonabsorbent mattress protectors that covers the entire sleeping surface.

      Correction: Provide a nonabsorbent mattress protector that covers the entire sleeping surface or have an easily cleanable nonabsorbent mattress surface.

      Code ATCP 72.20(8)(d)

  2. Sep 9, 2025 Routine · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated door(s) are propped open or are open at time of inspection.

      Correction: Except for fire doors on magnetic closures controlled by a central activation of the fire alarm system, fire doors must be self-closing and closed completely at all times. Please post on ALL fire doors that they are Not to be propped open.

      Code [C] ATCP 72.14 (1)

  3. Jun 12, 2024 Routine · 8 non-critical
    • Not serious Non-critical

      SMOKE DETECTORS - REQUIREMENT

      Smoke detectors are absent or not in working order in units 112 (smoke detector needed in between bedrooms), 213 (upstairs), 217, 113 (replace old smoke detector upstairs, 116 (in living area as there is a pull out), .

      Correction: Provide operational smoke detectors in all sleeping rooms and required locations, prior to next rental guests.

      Code ATCP 72.14 (2) (c)

    • Not serious Non-critical

      CARBON MONOXIDE DETECTORS - REQUIREMENT

      A carbon monoxide detector is not provided in the following units 203 (upstairs), 105, 213 (upstairs),214 (upstairs), 215 (upstairs), 217, [in units, outside of each separate sleeping area (identify area) in the immediate vicinity of the sleeping rooms and/or in sleeping rooms, where a fuel-burning appliance is located].

      Correction: Provide carbon monoxide detectors in all required locations, prior to next rental guests.

      Code [A] ATCP 72.145 (3)

    • Not serious Non-critical

      ROOMS IN A CLEAN CONDITION

      112 needs lady bugs in back bedroom cleaned up.

      Correction: Maintain all sleeping rooms in a clean and sanitary condition, prior to next rental guests.

      Code [A] ATCP 72.15 (2)

    • Not serious Non-critical Corrected on site

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated door outside unit 105 is propped open at time of inspection.

      Correction: Except for fire doors on magnetic closures controlled by a central activation of the fire alarm system, fire doors must be self-closing and closed completely at all times.

      Code [C] ATCP 72.14 (1)

    • Not serious Non-critical

      GENERAL MAINTENANCE

      Railing on 214 deck rails loose. Recommend tightening bolts. Check other decks as well..

      Correction: Maintained establishment in a manner conducive to the health, comfort and safety of its guests.

      Code [C] ATCP 72.15 (1)

    • Not serious Non-critical

      MATTRESS PAD PROVIDED/SUFFICIENT SIZE

      Mattress pad does not completely cover mattress or is missing.

      Correction: Provide a mattress pad that completely covers the mattress.

      Code [H] ATCP 72.11 (5)

    • Not serious Non-critical

      FIRE EXTINGUISHERS - MAINTAINED

      Extinguishers are overdue for service.

      Correction: Replace or have professionally refilled and pressure tested. Annual pressure testing required with record maintained.

      Code [M] ATCP 72.14 (1)

    • Not serious Non-critical

      VENTILATION REQUIREMENTS

      Ventilation is not provided in unit in the back bathroom of unit 308. Closet with mirror door in the unit 220 is off track and needs to be repaired. .

      Correction: Provide exhaust ventilation in rooms and rest-room in accordance with the state building code.

      Code [S] ATCP 72.14 (1)

Source: Bayfield County Health Department. History last read Oct 2, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.