Americinn Of Green Bay-spa
None, WI · Brown County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- Brown County Health & Human Services
- Status
- Permitted
- Official record
- Brown County Health & Human Services inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 3 | 1 |
| 2025 | 2 | 3 | 2 |
| 2024 | 1 | 1 | 0 |
Inspections
-
Mar 4, 2026 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Repeat
-
Feb 26, 2026 Routine · 1 critical, 1 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter is not being maintained in operating condition.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Free chlorine was observed at 0 PPM.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Not serious
Non-critical
-
Jan 24, 2025 Follow Up · No items found
No violations cited.
-
Jan 23, 2025 Routine · 2 critical, 1 non-critical
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 40
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Serious
Critical
PH
The pH is <7.0
Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
CLOSING CRITERIA-FAILURE TO MEET 76.16
The Responsible Supervisor or operator has not closed the pool after failure to comply with the water quality requirements. Chlorine was observed at 0.4 PPM.
Correction: Close the pool in the event of failure to comply with the water quality requirements pursuant to s. ATCP 76.16.
Code ATCP 76.30 (1)(b) - FAILURE TO MEET ATCP 76.16
-
Not serious
Non-critical
-
Jan 31, 2024 Routine · 1 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
Pressure gauge and flow meter are non functioning.
Correction: Repair or replace flow meter and pressure gauge.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
Source: Brown County Health & Human Services. History last read Oct 4, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.