RecordWell Data

Country Inn & Suites - Pool

121 MERWIN WAY, Fond Du Lac, WI 54937 · Fond du Lac County

40cited violations
11serious tier
3inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Fond du Lac County Health Department
License / ID
JBIH-CNLSC9
Status
Permitted
Phone
(414) 704-4089
Official record
Fond du Lac County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20261186
20252225

Inspections

  1. Sep 28, 2026 Routine · 6 critical, 12 non-critical, 6 repeat
    • Not serious Non-critical

      LICENSE NOT POSTED

      The license is not posted for public view.

      Correction: Post the license where it can be viewed by the public.

      Code ATCP 76.05(7) - LICENSE POSTED

    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Skimmers not repaired or replaced as needed. The weir door is missing at the south skimmer.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      SPARE STRAINER BASKET OR SCREEN AVAILABLE

      Spare pump strainer not available

      Correction: Provide a spare strainer or screen

      Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN

    • Not serious Non-critical

      STRAINER BASKET NOT CLEANED DAILY

      The pump strainer is only cleaned once per week per pool maintenance staff. There is an accumulation of debris observed in the pump strainer basket.

      Correction: Clean the pump strainer basket daily.

      Code ATCP 76.11(2)(d) 3. - CLEANED

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      REAGENTS REPLACED

      Test kit reagents for Taylor R-0871 and R-0003 are expired.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical Repeat

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical Repeat

      ALKALINITY TEST

      Pool water not tested at least once a week for total alkalinity.

      Correction: Test pool water at least once a week for total alkalinity.

      Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY

    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING FREQUENCY OF TESTING

      The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual.

      Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.

      Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ

    • Not serious Non-critical

      RESPONSIBLE SUPERVISOR INTERLOCK TESTING

      Responsible supervisor is not ensuring that monthly interlock testing is done. No records available to indicate monthly interlock testing.

      Correction: Have the responsible supervisor ensure that monthly interlock tests are done.

      Code ATCP 76.21 (1)(c)5.- INTERLOCK TESTING

    • Not serious Non-critical Repeat

      OPERATING REPORTS-CHEMICAL TESTING

      The operator did not record the following on the operating report: Results for chemical testing.

      Correction: Record the following on the operating report, results for chemical testing.

      Code ATCP 76.32(1)(a) - CHEMICAL TESTING

    • Not serious Non-critical Repeat

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

    • Serious Critical

      PH

      The pH is 8.6.

      Correction: The establishment voluntarily closed the pool. Close the pool until the pH can be maintained at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical

      MAXIMUM CHLORINE

      The maximum chlorine residual exceeds 10 ppm.

      Correction: The establishment voluntarily closed the pool. Close the pool until the chlorine residual is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(f) - MAXIMUM FREE CHLORINE

    • Serious Critical

      RESPONSIBLE SUPERVISOR SAFETY EQUIPMENT

      Responsible supervisor is not ensuring that safety and rescue equipment not in place. The Shepherd[s crook is in disrepair.

      Correction: Have the responsible supervisor ensure that safety and rescue equipment is in place.

      Code ATCP 76.21 (1)(c)2. - MAINTAIN SAFETY AND RESCUE EQPT

    • Serious Critical

      RESPONSIBLE SUPERVISOR SANITATION AND TESTING

      Responsible supervisor is not ensuring that pool chemical testing is performed. No pool chemical testing records available for review.

      Correction: Have the responsible supervisor ensure that sanitation and testing duties are performed.

      Code ATCP 76.21 (1)(c)4. - SANITAITON AND TESTING

    • Serious Critical

      RESPONSIBLE SUPERVISOR RECORDS MAINTAIN

      Responsible supervisor is not ensuring that records are maintained. No pool chemical testing records are available for review.

      Correction: Have the responsible supervisor ensure that records are maintained.

      Code ATCP 76.21 (1)(c)7. - RECORDS MAINTENANCE

    • Serious Critical

      SHEPHERD'S CROOK PROVIDED

      The shepherd's crook is broken or disassembled.

      Correction: Provide a functional shepherd's crook.

      Code ATCP 76.26(1)(b)1.a. -SHEPHERED'S CROOK PROVIDED

  2. Oct 13, 2025 Follow Up · 1 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      POOL BASIN MAINTAINED CLEAN AND SANITARY

      Pool basin not maintained in a clean and sanitary condition. There is a build up of dirt and debris at the bottom of the pool.

      Correction: Maintained the pool basin in a clean and sanitary condition.

      Code ATCP 76.33(1)(a)3 - POOL BASIN NOT CLEAN AND SANITARY

  3. Sep 24, 2025 Routine · 5 critical, 16 non-critical
    • Not serious Non-critical

      STAFF TRAINED IN SAFETY DATA SHEETS

      Staff are not trained in the use of the safety data sheet for chemicals and where they are located.

      Correction: Train staff in the use of the safety data sheet and where they are located.

      Code ATCP 76.12 (4)(b)3 - STAFF TRAINED IN SAFETY DATA SHEETS

    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      REAGENTS REPLACED

      Test kit reagents are expired and not replaced as recommended by the manufacturer.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      ALKALINITY TEST

      Pool water not tested at least once a week for total alkalinity.

      Correction: Test pool water at least once a week for total alkalinity.

      Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY

    • Not serious Non-critical

      ELECTRONIC MONITORING FREQUENCY OF TESTING

      The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual.

      Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.

      Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ

    • Not serious Non-critical

      OPERATOR REQUIRED

      The pool is not under the supervision of an operator.

      Correction: Provide an operator for the pool.

      Code ATCP 76.20(1)(a) - OPERATOR REQUIRED

    • Not serious Non-critical

      FIRST AID KIT ITEMS

      The first aid kit is present but missing items such as adhesive bandages, disposable gloves, instant cold packs, adhesive bandages, and adhesive tape.

      Correction: Replace the missing items in the first aid kit.

      Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS

    • Not serious Non-critical

      BIOHAZARD KIT ITEMS

      The biohazard kit is present but locked in the pump room, as well as missing items such as a scoop and spatula, biohazard sorbent, and disposable gloves.

      Correction: Replace the missing items in the biohazard kit and make the kit avaliable for use.

      Code ATCP 76.27(2)(b) - BIOHAZARD KIT ITEMS

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      OPERATING REPORTS-CHEMICAL TESTING

      There is no chemical testing being done or records being kept for results of chemical testing.

      Correction: Record the following on the operating report, results for chemical testing.

      Code ATCP 76.32(1)(a) - CHEMICAL TESTING

    • Not serious Non-critical

      OPERATING REPORTS-BACKWASH

      The operator did not record the following on the operating report: The dates on which backwashing was completed.

      Correction: Record the following on the operating report, the dates when backwashing was completed.

      Code ATCP 76.32(1)(b) - BACKWASH

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY

      A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:

      Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises.

      Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-CDC FECAL INCIDENTS

      The most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents was not permanently maintained on premises:

      Correction: Maintain a copy of the most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents that is consistent with the United States centers for disease control and prevention’s fecal accident response recommendations on the premises.

      Code ATCP 76.32(3)(a)8. - CDC FECAL RESPONSE GUIDELINES

    • Not serious Non-critical

      POOL BASIN MAINTAINED CLEAN AND SANITARY

      Pool basin not maintained in a clean and sanitary condition. There is a build up of dirt and debris at the bottom of the pool.

      Correction: Maintained the pool basin in a clean and sanitary condition.

      Code ATCP 76.33(1)(a)3 - POOL BASIN NOT CLEAN AND SANITARY

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers in regards to drain cover replacement. There is an invoice avaliable, but it does not contain all the required information about the drain covers such as life span and installation date.

      Correction: Maintain a log that can be used to evaluate the drain covers, that shows make and model of drain cover, installation date, as well as lifespan of the drain covers.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

    • Serious Critical

      OPERATOR KNOWLEDGE-MONTHLY TESTING

      Establishment is not able to describe how monthly testing is performed for the chemical interlock.

      Correction: Ensure that operator can describe how monthly testing is performed.

      Code ATCP 76.13 (1)(c)2.d - MONTHLY TESTING

    • Serious Critical

      INTERLOCK CHALLENGE TEST

      Once monthly challenge testing of the chemical feeder system has not been conducted to assess the interlock.

      Correction: Challenge test the chemical feeder system monthly to assess the interlock.

      Code ATCP 76.13 (1)(c)3. - INTERLOCK MONTHLY TEST

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant level is 0.6 for free chlorine.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      RESPONSIBLE SUPERVISOR FOR POOL

      The pool does not have a responsible supervisor.

      Correction: Provide a responsible supervisor for the pool.

      Code ATCP 76.21 (1)(a) - RESPONSIBLE SUPERVISOR REQUIRED

    • Serious Critical

      CO ALARM-POOL EQUIPMENT ROOM

      There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.

      Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.

      Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM

Source: Fond du Lac County Health Department. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.