Turning Rivers - Pool
N885 YOUTH CAMP RD, Campbellsport, WI 53010 · Fond du Lac County
Establishment
- Type
- Pool / recreational water (Pool - Moderate with Features)
- Inspected by
- Fond du Lac County Health Department
- License / ID
- DVOF-AAJQ4Y
- Status
- Permitted
- Phone
- (920) 904-6060 ext. Jason
- Official record
- Fond du Lac County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 6 | 4 |
| 2024 | 2 | 1 | 0 |
| 2023 | 1 | 6 | 0 |
Inspections
-
Jun 16, 2026 Routine · 4 critical, 2 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter on the pool is not being maintained in operating condition. The flow meter is stuck.
Correction: Adjust or repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
CHEMICAL STORAGE LOCATION
Acid and Chlorine not stored in clean, dry, well-ventilated, locked area away from flammables, incompatible chemicals and heat sources.
Correction: Store all chemicals in clean, dry, well-ventilated, locked area away from flammables, incompatible chemicals and heat sources.
Code ATCP 76.12 (2)(b) - CHEMICAL STORAGE LOCATION
-
Serious
Critical
CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS
Chlorine is not stored separately from sulfuric.
Correction: Store oxidizers separately from acids.
Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS
-
Serious
Critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 610 mV and water has not been tested manually.
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Serious
Critical
BIOHAZARD KIT-AVAILABLE
A biohazard kit is not available.
Correction: Provide a biohazard kit for the pool.
Code ATCP 76.27(2)(a) - BIOHAZ KIT AVAILABLE
-
Not serious
Non-critical
-
Aug 19, 2024 Re-inspection · No items found
No violations cited.
-
Jul 31, 2024 Follow Up · 1 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
CHLORINE TOO LOW
The chlorine residual was 0.4 ppm at the time of the inspection.
Correction: Close the pool and raise the chlorine residual to 1.0 ppm before re-opening.
Code [A] ATCP 76.14(4)(a)
-
Not serious
Non-critical
Repeat
-
Aug 29, 2023 Routine · 6 non-critical
-
Not serious
Non-critical
SKIMMERS NOT FUNCTIONING
All if the skimmer are not functioning and does not have vigorous skimming action. There are numerous plant and trash debris in the skimmers.
Correction: Clean and maintain the skimmers so that they are clean. Readjust the flow through the skimmers to maintain vigorous skimming action through all skimmers.
Code ATCP 76.11(2)(a)
-
Not serious
Non-critical
OUT OF SOAP
The soap dispensers in the men's shower stalls were removed.
Correction: Provide soap in permanently installed soap dispensing devices at all showers.
Code ATCP 76.33(2)(e)
-
Not serious
Non-critical
HAZARDOUS PROJECTION ON PART OF WATER ATTRACTION
The 3'6" depth marking tile at the pool edge on the west side of the pool is cracked creating a hazardous sharp edge.
Correction: Repair the depth marking tile.
Code ATCP 76.36(1)(b)
-
Not serious
Non-critical
CHLORINE TOO LOW
The chlorine residual was 0.26 ppm at the time of the inspection.
Correction: Close the pool and raise the chlorine residual to 1.0 ppm before re-opening.
Code [A] ATCP 76.14(4)(a)
-
Not serious
Non-critical
IN NEED OF CLEANING
About 25% of the surface area of the pool basin has algae growth and discoloration.
Correction: Keep the facility in a clean condition pursuant to ATCP 76.33(1)(a).
Code [A] ATCP 76.33(1)(a)
-
Not serious
Non-critical
CRACKS OR PITTING IN THE POOL BASIN
There are cracks in the pool basin near the water slide areas.
Correction: Repair the pool basin so it is finished and easily cleanable.
Code [B] ATCP 76.33(1)(a)
-
Not serious
Non-critical
Source: Fond du Lac County Health Department. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.