Breezy Hill Campground-whirlpool
N4177 CEARNS LN, Fond Du Lac, WI 54937 · Fond du Lac County
Establishment
- Type
- Pool / recreational water (Pool - Moderate)
- Inspected by
- Fond du Lac County Health Department
- License / ID
- DVOF-A7XL63
- Status
- Permitted
- Phone
- (920) 477-2300
- Official record
- Fond du Lac County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 3 | 24 | 8 |
| 2025 | 1 | 2 | 0 |
| 2023 | 1 | 3 | 0 |
Inspections
-
Sep 4, 2026 Follow Up · 3 critical, 5 non-critical, 8 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS-ADJUSTED
Skimmers not adjusted to ensure vigorous skimming.
Correction: Adjust skimmers to maintain vigorous skimming .
Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The whirlpool turnover rate is at 1.2, when it should be at 0.5.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is 35 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN ACTION LEVEL
The combined chlorine level is at 0.6 ppm. The action level is 0.4 ppm, therefore, the combined chlorine action plan is not being followed.
Correction: Follow the combined chlorine plan to implement the corrective action level.
Code ATCP 76.14(5)(e)2.a. - ACTION LEVEL LISTED
-
Not serious
Non-critical
Repeat
SOAP-PROVIDED
Soap not provided in permanently-installed dispensing device in the men's and women's shower rooms.
Correction: Provide soap in a permanently-installed dispensing device.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Serious
Critical
Repeat
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 1.15 PPM for the free chlorine concentration.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Repeat
PH
The pH is 6.5.
Correction: Maintain the pH at 7.2 to 7.8. Close the whirlpool until the pH is between the 7.2 to 7.8 range. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
Repeat
HAZARDOUS CONDITION
According to the VGBA log, the drain cover is expired and needs to be replaced. The drain cover was installed on 5/27/2021 and had a 5 year life span.
Correction: Replace the drain cover and add the installation details into the VGBA log. Until then, pool can remain open as long as operator creates a log documenting a daily inspection of the drain cover to ensure no cracks, breaks, missing screws or other visible damage or detects are observed, and to close if any of the above damage or defects are observed, then must remain closed until a compliant drain c
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
Repeat
-
Sep 4, 2026 Follow Up · 2 critical, 5 non-critical, 7 repeat
-
Not serious
Non-critical
Repeat
SKIMMERS-ADJUSTED
Skimmers not adjusted to ensure vigorous skimming.
Correction: Adjust skimmers to maintain vigorous skimming .
Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED
-
Not serious
Non-critical
Repeat
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The whirlpool turnover rate is at 1.2, when it should be at 0.5.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Repeat
ALKALINITY
The total alkalinity is 35 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN ACTION LEVEL
The combined chlorine level is at 0.6 ppm. The action level is 0.4 ppm, therefore, the combined chlorine action plan is not being followed.
Correction: Follow the combined chlorine plan to implement the corrective action level.
Code ATCP 76.14(5)(e)2.a. - ACTION LEVEL LISTED
-
Not serious
Non-critical
Repeat
SOAP-PROVIDED
Soap not provided in permanently-installed dispensing device in the men's and women's shower rooms.
Correction: Provide soap in a permanently-installed dispensing device.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Serious
Critical
Repeat
PH
The pH is 6.5.
Correction: Maintain the pH at 7.2 to 7.8. Close the whirlpool until the pH is between the 7.2 to 7.8 range. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
Repeat
HAZARDOUS CONDITION
According to the VGBA log, the drain cover is expired and needs to be replaced. The drain cover was installed on 5/27/2021 and had a 5 year life span.
Correction: Replace the drain cover and add the installation details into the VGBA log. Until then, pool can remain open as long as operator creates a log documenting a daily inspection of the drain cover to ensure no cracks, breaks, missing screws or other visible damage or detects are observed, and to close if any of the above damage or defects are observed, then must remain closed until a compliant drain c
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
Repeat
-
Sep 3, 2026 Routine · 3 critical, 6 non-critical
-
Not serious
Non-critical
SKIMMERS-ADJUSTED
Skimmers not adjusted to ensure vigorous skimming.
Correction: Adjust skimmers to maintain vigorous skimming .
Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. The whirlpool turnover rate is at 1.2, when it should be at 0.5.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
Corrected on site
PIPING LABELED, TAGGED OR CODED
The piping in the pump room is not labeled, tagged or color-coded with the direction of water flow and what water it carries (from skimmers, to inlets, etc.).
Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow and what water it carries.
Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED
-
Not serious
Non-critical
ALKALINITY
The total alkalinity is 35 ppm.
Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.
Code ATCP 76.14(5)(d) - ALKALINITY
-
Not serious
Non-critical
COMBINED CHLORINE PLAN ACTION LEVEL
The combined chlorine level is at 0.6 ppm. The action level is 0.4 ppm, therefore, the combined chlorine action plan is not being followed.
Correction: Follow the combined chlorine plan to implement the corrective action level.
Code ATCP 76.14(5)(e)2.a. - ACTION LEVEL LISTED
-
Not serious
Non-critical
SOAP-PROVIDED
Soap not provided in permanently-installed dispensing device in the men's and women's shower rooms.
Correction: Provide soap in a permanently-installed dispensing device.
Code ATCP 76.33 (2)(e)1. - SOAP
-
Serious
Critical
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 1.15 PPM for the free chlorine concentration.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
PH
The pH is 6.5.
Correction: Maintain the pH at 7.2 to 7.8. Close the whirlpool until the pH is between the 7.2 to 7.8 range. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
HAZARDOUS CONDITION
According to the VGBA log, the drain cover is expired and needs to be replaced. The drain cover was installed on 5/27/2021 and had a 5 year life span.
Correction: Replace the drain cover and add the installation details into the VGBA log. Until then, pool can remain open as long as operator creates a log documenting a daily inspection of the drain cover to ensure no cracks, breaks, missing screws or other visible damage or detects are observed, and to close if any of the above damage or defects are observed, then must remain closed until a compliant drain c
Code ATCP 76.34(1) - HAZARDOUS CONDITION AT POOL AREA
-
Not serious
Non-critical
-
Aug 4, 2025 Routine · 2 non-critical
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
DEATH, INJURY, ILLNESS REPORTS
The operator does not have a written form or procedure on reporting an incident resulting in death, serious injury, or illness that requires emergency medical services.
Correction: Report any incident resulting in death, serious injury, or illness that requires assistance from emergency medical personnel, by the end of the next working day following the incident by phone, email, or fax to the department or its agent.
Code ATCP 76.32(2) - DII REPORTS
-
Not serious
Non-critical
-
Jun 19, 2023 Routine · 3 non-critical, 1 repeat
-
Not serious
Non-critical
Corrected on site
ALKALINITY OUT OF BALANCE
The total alkalinity is 241 ppm.
Correction: Maintain the total alkalinity between 60 and 180 ppm.
Code ATCP 76.14(4)(d)
-
Not serious
Non-critical
WATER TESTING FREQUENCY - POOLS
The water testing frequency for alkalinity (1x a week) and combine chlorine (2x a week) are not in compliance with ATCP 76.18(1).
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Non-critical
Repeat
Corrected on site
RECORD RETENTION
Invoice for the spa main drains were not available for review.
Correction: Keep records in accordance with ATCP 76.32(3).
Code [A] ATCP 76.32(3)
-
Not serious
Non-critical
Corrected on site
Source: Fond du Lac County Health Department. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.