RecordWell Data

North Fond Du Lac Swim Pool-large Pool

125 MCKINLEY ST, North Fond Du Lac, WI 54937 · Fond du Lac County

6cited violations
1serious tier
3inspections

Establishment

Type
Pool / recreational water (Pool - Moderate with Features)
Inspected by
Fond du Lac County Health Department
License / ID
HSAT-7QXKHQ
Status
Permitted
Phone
(920) 929-3765
Official record
Fond du Lac County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026110
2025111
2023140

Inspections

  1. Aug 17, 2026 Routine · 1 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      Both flowmeters are not in working condition and cannot be read to determine the flowrate.

      Correction: Adjust or repair the flowmeters.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

  2. Jul 31, 2025 Routine · 1 critical
    • Serious Critical Corrected on site

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is 0.6 for Free Chlorine.

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Establishment incresased chlorine levels and retested the pool at 2.07 Free Chlorine.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

  3. Jun 19, 2023 Routine · 4 non-critical
    • Not serious Non-critical

      RECIRCULATION RATE NOT MET - POOLS

      The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.

      Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.

      Code ATCP 76.11(4)(a)

    • Not serious Non-critical Corrected on site

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeeter is not maintained and is not in working order.

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical

      MSDS AVAILABILITY

      Material safety data sheets are not available for all chemicals used in the facility.

      Correction: Provide material safety data sheets for all chemicals used in the facility.

      Code ATCP 76.12(4)(b)

    • Not serious Non-critical

      BACKFLOW - HOSE BIBBS

      The hose bibb in the pump room and under the water fountain is not provided with a backflow preventer.

      Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.

      Code [A] ATCP 76.33(1)(d)