North Fond Du Lac Swim Pool-large Pool
125 MCKINLEY ST, North Fond Du Lac, WI 54937 · Fond du Lac County
Establishment
- Type
- Pool / recreational water (Pool - Moderate with Features)
- Inspected by
- Fond du Lac County Health Department
- License / ID
- HSAT-7QXKHQ
- Status
- Permitted
- Phone
- (920) 929-3765
- Official record
- Fond du Lac County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 1 | 0 |
| 2025 | 1 | 1 | 1 |
| 2023 | 1 | 4 | 0 |
Inspections
-
Aug 17, 2026 Routine · 1 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
Both flowmeters are not in working condition and cannot be read to determine the flowrate.
Correction: Adjust or repair the flowmeters.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
-
Jul 31, 2025 Routine · 1 critical
-
Serious
Critical
Corrected on site
MINIMUM DISINFECTANT RESIDUAL
Minimum disinfectant or sanitizer level is 0.6 for Free Chlorine.
Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A. Establishment incresased chlorine levels and retested the pool at 2.07 Free Chlorine.
Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL
-
Serious
Critical
Corrected on site
-
Jun 19, 2023 Routine · 4 non-critical
-
Not serious
Non-critical
RECIRCULATION RATE NOT MET - POOLS
The swimming pool or combination pool has a maximum turnover rate of greater than 6 hours.
Correction: Immediately adjust or repair the equipment to operate at a proper turnover rate.
Code ATCP 76.11(4)(a)
-
Not serious
Non-critical
Corrected on site
FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL
The flowmeeter is not maintained and is not in working order.
Correction: Repair or replace the specified equipment so an accurate reading can be recorded.
Code ATCP 76.11(5)
-
Not serious
Non-critical
MSDS AVAILABILITY
Material safety data sheets are not available for all chemicals used in the facility.
Correction: Provide material safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Non-critical
BACKFLOW - HOSE BIBBS
The hose bibb in the pump room and under the water fountain is not provided with a backflow preventer.
Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.
Code [A] ATCP 76.33(1)(d)
-
Not serious
Non-critical
Source: Fond du Lac County Health Department. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.