RecordWell Data

River Hills Apartments

40 OVERLOOK DR, Fond Du Lac, WI 54937 · Fond du Lac County

27cited violations
2serious tier
5inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Fond du Lac County Health Department
License / ID
JBIH-C2NRCE
Status
Permitted
Phone
(920) 267-6411
Official record
Fond du Lac County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026191
2025181
20233100

Inspections

  1. Aug 28, 2026 Routine · 1 critical, 8 non-critical, 2 repeat
    • Not serious Non-critical

      SKIMMERS MAINTAINED CLEAN

      Skimmer baskets not maintained clean. There is an accumuluations of old plant debris in all skimmers.

      Correction: Maintain the skimmers in clean condition.

      Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN

    • Not serious Non-critical

      STRAINER BASKET NOT CLEANED DAILY

      The pump strainer is not cleaned regularly and has an accumulation of debris in it.

      Correction: Clean the pump strainer daily.

      Code ATCP 76.11(2)(d) 3. - CLEANED

    • Not serious Non-critical

      CYANURATES 30 PPM LIMIT

      The cyanuric acid concentration is 56 PPM.

      Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.

      Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity tested at 54 PPM.

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is 611 mV and water has not been tested manually.

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      REAGENTS REPLACED

      Taylor test kit reagent R-0002 is expired and not replaced as recommended by the manufacturer.

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical Repeat

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical Repeat

      CYANURIC TEST

      Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.

      Correction: Test water for the cyanuric acid at least once a week.

      Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC

    • Serious Critical Corrected on site

      MINIMUM DISINFECTANT RESIDUAL

      Minimum disinfectant or sanitizer level is 0.42 PPM for free chorine.

      Correction: During the inspectoin, the establishment closed the pool and consulted with their pool company for corrective action. Following the pool company instructions, the establishment shocked the pool at about 3:30pm. The disinfectant level was increased to 5.17 PPM after shocking the pool. Per pool company, the pool may reopen after 1 hour of shocking. Since the disinfectant level was increased to 5.17

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

  2. Aug 7, 2025 Routine · 1 critical, 7 non-critical
    • Not serious Non-critical

      SKIMMERS-ADJUSTED

      Skimmers not adjusted to ensure vigorous skimming.

      Correction: Adjust skimmers to maintain vigorous skimming .

      Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED

    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      The skimmer floating weir door is missing for the two skimmers on the east side of the pool.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      CYANURIC TEST

      Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.

      Correction: Test water for the cyanuric acid at least once a week.

      Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC

    • Not serious Non-critical Corrected on site

      FILES MAINTAINED PERMANENT-ATCP 76 CURRENT COPY

      A copy of the most current version of ch. ATCP 76 was not permanently maintained on premises:

      Correction: Maintain a copy of the most current version of ch. ATCP 76 on premises. Emailed the most recent copy of ATCP 76 to the operator.

      Code ATCP 76.32(3)(a)1. - CURRENT ATCP 76 COPY

    • Not serious Non-critical Corrected on site

      FILES MAINTAINED PERMANENT-CDC FECAL INCIDENTS

      The most recent United States centers for disease control and prevention recommendations for fecal accidents.

      Correction: Maintain a copy of the most recent United States centers for disease control and prevention recommendations for fecal accidents or another plan in response to fecal accidents that is consistent with the United States centers for disease control and prevention’s fecal accident response recommendations on the premises. Provided the most recent copy of the CDC fecal incident response guidelines and C

      Code ATCP 76.32(3)(a)8. - CDC FECAL RESPONSE GUIDELINES

    • Serious Critical

      OPERATOR KNOWLEDGE-FLOW INTERLOCK FUNCTION

      The person responsible is not able to describe how the system flow sensing interlock functions.

      Correction: Ensure that operator can describe how the system flow sensing interlock functions.

      Code ATCP 76.13 (1)(c)2.c - HOW FLOW INTERLOCK FUNCTIONS

  3. Jun 29, 2023 Follow Up · No items found

    No violations cited.

  4. Jun 23, 2023 Follow Up · 5 non-critical, 5 repeat
    • Not serious Non-critical Repeat

      PERMIT NOT POSTED

      The permit is not posted in a place visible to the public.

      Correction: Post the permit in public view.

      Code ATCP 76.05(7)

    • Not serious Non-critical Repeat

      TEST KIT NOT APPROVED

      Clorox Pool Smart Strips are being used by the facility to determine chemistry adjustments and this is NOT an approved test kit.

      Correction: Replace the test kit with one from the approved list.

      Code ATCP 76.17(1)

    • Not serious Non-critical Repeat

      RECORD RETENTION

      DSPS Conditional Approval documentation for VGBA grate is not available for review.

      Correction: Keep records in accordance with ATCP 76.32(3).

      Code [A] ATCP 76.32(3)

    • Not serious Non-critical Repeat

      DRINKING FOUNTAIN NOT FUNCTIONAL

      The drinking fountain is shut off and not available to guest on due to lack of good repair.

      Correction: Repair the drinking fountain.

      Code [A] ATCP 76.33(1)(g)

    • Not serious Non-critical Repeat

      RULES MISSING - GENERAL

      The following rules are missing from the posting: 1, 3, 6 and 7.

      Correction: Provide a sign in compliance with ATCP 76.29(1)(b).

      Code [B] ATCP 76.29(1)(b)

  5. Jun 8, 2023 Routine · 5 non-critical
    • Not serious Non-critical

      PERMIT NOT POSTED

      The permit is not posted in a place visible to the public.

      Correction: Post the permit in public view.

      Code ATCP 76.05(7)

    • Not serious Non-critical

      TEST KIT NOT APPROVED

      Clorox Pool Smart Strips are being used by the facility to determine chemistry adjustments and this is NOT an approved test kit.

      Correction: Replace the test kit with one from the approved list.

      Code ATCP 76.17(1)

    • Not serious Non-critical

      RECORD RETENTION

      DSPS Conditional Approval documentation for VGBA grate is not available for review.

      Correction: Keep records in accordance with ATCP 76.32(3).

      Code [A] ATCP 76.32(3)

    • Not serious Non-critical

      DRINKING FOUNTAIN NOT FUNCTIONAL

      The drinking fountain is shut off and not available to guest on due to lack of good repair.

      Correction: Repair the drinking fountain.

      Code [A] ATCP 76.33(1)(g)

    • Not serious Non-critical

      RULES MISSING - GENERAL

      The following rules are missing from the posting: 1, 3, 6 and 7.

      Correction: Provide a sign in compliance with ATCP 76.29(1)(b).

      Code [B] ATCP 76.29(1)(b)

Source: Fond du Lac County Health Department. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.