Coratel Inn & Suites

W10090 HWY 54 E, Black River Falls, WI 54615 · Jackson County

27cited violations
4serious tier
4inspections

Establishment

Type
Pool / recreational water (Pool - Simple)
Inspected by
Jackson County Public Health
License / ID
BROG-B8GUFM
Status
Permitted
Official record
Jackson County Public Health inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026162
2025171
20242141

Inspections

  1. Feb 16, 2026 Re-inspection · 2 critical, 4 non-critical, 1 repeat
    • Not serious Non-critical Repeat

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Weir door missing on skimmer.

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is 195 mV.

      Correction: Maintain water potential between 650−900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      BIOHAZARD KIT-BIOHAZARD DISPOSAL BAG

      The biohazard kit is missing a biohazard disposal bag.

      Correction: For the biohazard kit, provide a biohazard disposal bag.

      Code ATCP 76.27(2)(b)6 - DISPOSAL BAG

    • Not serious Non-critical

      VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT

      The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.

      Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.

      Code ATCP 76.38(2)(a) - DRAIN COVER LOG

    • Serious Critical

      PH

      The pH is >8.4.

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

    • Serious Critical

      TELEPHONE-OTHER TECHNOLOGIES,RELIABLE SERVICE CONNECTION

      Phone observed to be out of order.

      Correction: Provide a reliable service connection for the communication technology.

      Code ATCP 76.26(2)(b)2. - TELEPHONE, OTHER TECHNOLOGIES, CONNECTI

  2. Apr 21, 2025 Routine · 1 critical, 6 non-critical, 2 repeat
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      Weir doors missing on pool.

      Correction: Replace weir doors that are missing.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not maintained. Flowmeter is not working.

      Correction: Replace or repair the flowmeter.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Corrected on site

      TELEPHONE-OTHER TECHNOLOGIES, POWER SUPPLY

      Emergency phone does not work.

      Correction: Staff replaced phone during inspection. New phone does work.

      Code ATCP 76.26(2)(b)1. - TELEPHONE, OTHER TECHNOLOGIES, POWER

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION

      The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. The most recent replacement of main drain and equalizer cover (2019 - staff thought) is not recorded.

      Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.

      Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER

    • Serious Critical

      RING BOUY

      A ring buoy not provided.

      Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.

      Code ATCP 76.26(1)(b)2.a - RING BOUY

  3. Mar 18, 2024 Re-inspection · 4 non-critical, 4 repeat
    • Not serious Non-critical Repeat

      PIPING LABELED, TAGGED OR CODED

      The piping is not labeled, tagged or color-coded. Direction of flow is not indicated on the piping.

      Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.

      Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED

    • Not serious Non-critical Repeat

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical Repeat

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Not serious Non-critical Repeat

      POOL EQUIPMENT-REPAIRED AS NECESSARY

      The pool equipment is not repaired as necessary. There as screws exposed and not securely fastened on the pool equalizer cover, one rail to the pool ladder is loose and not properly tightened in place.

      Correction: The pool equipment is not repaired as necessary.

      Code ATCP 76.33(1)(e)4. - EQPT REPAIRED AS NEEDED

  4. Mar 12, 2024 Routine · 1 critical, 9 non-critical
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter to the pool recirculation system is not being maintained in operating condition.

      Correction: Adjust or repair the pools flowmeter so that the turnover rate can not be calculated.

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      PIPING LABELED, TAGGED OR CODED

      The piping is not labeled, tagged or color-coded. Direction of flow is not indicated on the piping.

      Correction: Ensure that the piping is labeled, tagged or color-coded to indicate valves, piping and direction of water flow.

      Code ATCP 76.11(5m)(a) - PIPING NOT LABELED,TAGGED, CODED

    • Not serious Non-critical

      COMBINED CHLORINE PLAN PRESENT

      The operator has not developed and implemented a plan to minimize combined chlorine in the pool.

      Correction: Develop and implement a plan to minimize combined chlorine in the pool.

      Code ATCP 76.14(5)(e)1. - PLAN PRESENT

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      ALKALINITY TEST

      Pool water not tested at least once a week for total alkalinity.

      Correction: Test pool water at least once a week for total alkalinity.

      Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY

    • Not serious Non-critical

      FIRST AID KIT ITEMS

      The first aid kit is present but missing items. The first aid kit is missing adhesive tape and cold packs.

      Correction: Replace the missing items in the first aid kit.

      Code ATCP 76.27(1)(b) - FIRST AID KIT ITEMS

    • Not serious Non-critical

      OPERATING REPORTS-BACKWASH

      The operator did not record the following on the operating report: The dates on which backwashing was completed.

      Correction: Record the following on the operating report, the dates when backwashing was completed.

      Code ATCP 76.32(1)(b) - BACKWASH

    • Not serious Non-critical

      OPERATING REPORTS-INTERLOCK TESTING

      The operator did not record the following on the operating report: Dates of interlock tests, results and comments.

      Correction: Record the following on the operating report, dates of interlock tests, results and comments.

      Code ATCP 76.32(1)(d) - INTERLOCK TEST

    • Not serious Non-critical

      POOL EQUIPMENT-REPAIRED AS NECESSARY

      The pool equipment is not repaired as necessary. There as screws exposed and not securely fastened on the pool equalizer cover, one rail to the pool ladder is loose and not properly tightened in place.

      Correction: The pool equipment is not repaired as necessary.

      Code ATCP 76.33(1)(e)4. - EQPT REPAIRED AS NEEDED

    • Serious Critical

      PH

      The pH is 8.36.

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

Source: Jackson County Public Health. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.