Parkland Village Campground
N6150 JULIANNA RD, Black River Falls, WI 54615 · Jackson County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Jackson County Public Health
- License / ID
- BROG-DHHKU5
- Status
- Permitted
- Phone
- (315) 420-5376
- Official record
- Jackson County Public Health inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 3 | 0 |
| 2025 | 1 | 6 | 2 |
Inspections
-
Jun 9, 2026 Routine · 3 non-critical
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
FIRST AID KIT -RESUSCITATION POCKET MASK
The first aid kit is missing a resuscitation pocket mask.
Correction: Provide a resuscitation pocket mask for the first aid kit.
Code ATCP 76.27(1)(b)8.- RESUSCITATION MASK
-
Not serious
Non-critical
VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT
The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.
Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.
Code ATCP 76.38(2)(a) - DRAIN COVER LOG
-
Not serious
Non-critical
-
Jun 19, 2025 Pre-inspection · 2 critical, 4 non-critical
-
Not serious
Non-critical
Corrected on site
SKIMMER POOL RECIRCULATION FLOW
Proportion of water recirculating from skimmer and main drain is [100%].
Correction: Adjust equipment so that proportion of water recirculating from skimmer and main drain is mostly from skimmer.
Code ATCP 76.11(2)(a) 2. b. - SKIMMER POOL RECIRCULATION FLOW
-
Not serious
Non-critical
CYANURATES 30 PPM LIMIT
The cyanuric acid concentration is 41 ppm.
Correction: Lower the water cyanuric acid concentration to 30 ppm or lower.
Code ATCP 76.14(5)(b)1 - MAXIMUM CYANURIC
-
Not serious
Non-critical
Corrected on site
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
POOL DECK-DEPTH MARKINGS MAINTAINED
Pool deck area not maintained so that depth markings along the edge of the pool are clearly visible and readable and in accordance with SPS 390.19.
Correction: Maintain pool deck area so that depth markings along the edge of the pool are clearly visible and readable. Depth markers shall be installed at the maximum and minimum water depths and at all points of slope change.
Code ATCP 76.33(1)(b)4. - DEPTH MARKINGS
-
Serious
Critical
Modification(s) made but no DSPS Approval available for them.
The operator modified a pool and did not submit pool construction plans to DSPS for review and approval. The high rate sand filter was replaced with a cartridge filter system and not previously reviewed and approved by DSPS.
Correction: Have WI-licensed architect or engineer submit pool construction (modification) plans to DSPS and obtain approval from DSPS for the construction of the pool.
Code ATCP 76.04 (2) - PLANS SUBMITTED TO DSPS FOR MODIFICATION, A
-
Serious
Critical
Corrected on site
HOSING - BACKFLOW PREVENTION DEVICE
The hose bib used to fill the pool was missing a backflow prevention device.
Correction: A backflow prevention device was installed during the inspection.
Code ATCP 76.33(1)(d)2. - BACKFLOW PREVENTION
-
Not serious
Non-critical
Corrected on site
Source: Jackson County Public Health. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.