Americinn
1225 JANESVILLE, Fort Atkinson, WI 53538 · Jefferson County
Establishment
- Type
- Pool / recreational water (Pool - Simple)
- Inspected by
- Jefferson County Health Department / Watertown
- License / ID
- TKUK-CVTP9J
- Status
- Permitted
- Official record
- Jefferson County Health Department / Watertown inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 6 | 0 |
| 2025 | 1 | 6 | 0 |
| 2024 | 1 | 3 | 1 |
| 2023 | 1 | 0 | 0 |
Inspections
-
Jan 7, 2026 Routine · 6 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Not serious
Non-critical
OPERATING REPORTS-BACKWASH
The operator did not record the following on the operating report: The dates on which backwashing was completed.
Correction: Record the following on the operating report, the dates when backwashing was completed.
Code ATCP 76.32(1)(b) - BACKWASH
-
Not serious
Non-critical
OPERATING REPORTS-INTERLOCK TESTING
The operator did not record the following on the operating report: Dates of interlock tests, results and comments.
Correction: Record the following on the operating report, dates of interlock tests, results and comments.
Code ATCP 76.32(1)(d) - INTERLOCK TEST
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-PUMP CURVE
The manufacturer’s pump performance curve diagram was not permanently maintained on premises:
Correction: Maintain a copy of the manufacturer’s pump performance curve diagram on the premises.
Code ATCP 76.32(3)(a)3. - PUMP CURVE
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. [Describe].
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
Repeat
-
Jan 21, 2025 Routine · 6 non-critical, 1 repeat
-
Not serious
Non-critical
Repeat
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
Flow meter is not in working order.
Correction: Repair the flow meter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
SAFETY DATA SHEET
A safety data sheet was not available for the chemicals used in the pools.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
ALKALINITY TEST
Pool water not tested at least once a week for total alkalinity.
Correction: Test pool water at least once a week for total alkalinity.
Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY
-
Not serious
Non-critical
Repeat
-
Feb 7, 2024 Routine · 1 critical, 2 non-critical
-
Not serious
Non-critical
FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED
The flow meter for the whirlpool is not in working order.
Correction: Repair or replace the flowmeter.
Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED
-
Not serious
Non-critical
VGBA DRAIN COVER INFO-INSTALLATION DATE
The VGBA log or other proof does not indicate drain cover installation date.
Correction: Indicate in the log of drain cover installation date.
Code ATCP 76.38(2)(b)5. - INSTALL DATE
-
Serious
Critical
TELEPHONE ACCESSIBLE
Phone present in the pool room dials the front desk and not 911.
Correction: Provide a working telephone or other technology capable of connecting with emergency services.
Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE
-
Not serious
Non-critical
-
Sep 19, 2023 Pre-inspection · No items found
No violations cited.
Source: Jefferson County Health Department / Watertown. History last read Oct 5, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.