Castle Rock Condo Hoa - Outdoor Swimming Pool

N6895 RIDGEWATER DR, Mauston, WI 53948 · Juneau County

59cited violations
23serious tier
7inspections

Establishment

Type
Pool / recreational water (Pool - Simple with Features)
Inspected by
Juneau County Health Department
License / ID
CDRY-9ZQLWZ
Status
Permitted
Phone
(608) 254-1470
Official record
Juneau County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20262155
202532515
20241103
2023190

Inspections

  1. Jun 25, 2026 Routine · 3 critical, 5 non-critical, 3 repeat
    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flow meter is not functional

      Correction: Adjust or repair the [ ].

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      REAGENTS REPLACED

      Test kit reagents not replaced as recommended by the manufacturer. The chemicals in the kit are from 2023

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical Repeat

      MINIMUM DISINFECTANT RESIDUAL

      The chloriene level at the time of inspection is at a 0.2 ppm

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      RING BOUY

      There is no rope to the ring bouy

      Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.

      Code ATCP 76.26(1)(b)2.a - RING BOUY

    • Serious Critical Repeat

      DRINKING FOUNTAIN PROVIDED

      There is no drinking fountain provided.

      Correction: Provide a drinking fountain within 300 feet walking distance.

      Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED

  2. Jun 25, 2026 Re-inspection · 2 critical, 5 non-critical, 7 repeat
    • Not serious Non-critical Repeat

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flow meter is not functional

      Correction: Adjust or repair the [ ].

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical Repeat

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical Repeat

      REAGENTS REPLACED

      Test kit reagents not replaced as recommended by the manufacturer. The chemicals in the kit are from 2023

      Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.

      Code ATCP 76.17 (2)(b) - REAGENTS REPLACED

    • Not serious Non-critical Repeat

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical Repeat

      RING BOUY

      There is no rope to the ring bouy

      Correction: Provide a ring buoy with rope a length not less than 1-1/2 times the maximum width of the pool or 50 feet, whichever is less.

      Code ATCP 76.26(1)(b)2.a - RING BOUY

    • Serious Critical Repeat

      DRINKING FOUNTAIN PROVIDED

      There is no drinking fountain provided.

      Correction: Provide a drinking fountain within 300 feet walking distance.

      Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED

  3. Aug 28, 2025 Re-inspection 2 · 1 critical, 2 non-critical, 3 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is at 40 ppm

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical Repeat

      DRINKING FOUNTAIN PROVIDED

      There is no drinking fountain provided. Te current fountian is not operational

      Correction: Provide a drinking fountain within 300 feet walking distance.

      Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED

  4. Aug 26, 2025 Re-inspection · 7 critical, 4 non-critical, 11 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is at 40 ppm

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical Repeat

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is at 491 mV

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical Repeat

      OPERATOR RESPONSIBILITIES

      The operator has not been responsible for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality pursuant.

      Correction: Provide a pool operator who is responsible and providing active managerial control for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality.

      Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical Repeat

      CHEMICAL STORAGE ACCESS RESTRICTED

      Chemical storage area access not restricted to authorized personnel. The door to the room is left unlocked and open

      Correction: Restrict access to chemical storage area to only authorized personnel.

      Code ATCP 76.12 (2)(d) - ACCESS RESTRICTED

    • Serious Critical Repeat

      MINIMUM DISINFECTANT RESIDUAL

      Chloriene is at 0.2 ppm at the time of inspection

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical Repeat

      TELEPHONE ACCESSIBLE

      A telephone or other approved communication technology capable of connecting to emergency services is not working or not present.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

    • Serious Critical Repeat

      FIRST AID KIT-PROVIDED IN POOL AREA

      The first aid kit is missing from the pool area, or within 25 feet of enclosure with signage posted in the enclosure telling where the first aid kit is.

      Correction: Provide a first aid kit in the pool area or, if the first aid kit is within 25 feet of the enclosure, post signage that tells where the first aid kit is located.

      Code ATCP 76.27(1)(a) - FIRST AID KIT PRESENT

    • Serious Critical Repeat

      CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE

      The Responsible Supervisor or operator has not closed the pool due to a nonfunctional emergency phone.

      Correction: Close the pool in the event of a nonfunctional emergency phone.

      Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE

    • Serious Critical Repeat

      DRINKING FOUNTAIN PROVIDED

      There is no drinking fountain provided. Te current fountian is not operational

      Correction: Provide a drinking fountain within 300 feet walking distance.

      Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED

    • Serious Critical Repeat

      GATES AND DOORS-SELF-CLOSING

      The gate or door does not self-close. The gate located at the back of the pool does not close and latch by itself

      Correction: Provide a self-closing gate or door.

      Code ATCP 76.34(4)(a)(1m)(a) -SELF-CLOSING

  5. Jun 30, 2025 Routine · 7 critical, 4 non-critical, 4 repeat
    • Not serious Non-critical Repeat

      ALKALINITY

      The total alkalinity is at 40 ppm

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      ELECTRONIC MONITORING WATER POTENTIAL

      The water potential ("ORP") is at 491 mV

      Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.

      Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL

    • Not serious Non-critical

      OPERATOR RESPONSIBILITIES

      The operator has not been responsible for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality pursuant.

      Correction: Provide a pool operator who is responsible and providing active managerial control for equipment shut-down, backwashing, daily maintenance and vacuuming, and maintenance of water quality.

      Code ATCP 76.20(1)(b) - OPERATOR RESPONSIBILITIES

    • Not serious Non-critical Repeat

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Serious Critical

      CHEMICAL STORAGE ACCESS RESTRICTED

      Chemical storage area access not restricted to authorized personnel. The door to the room is left unlocked and open

      Correction: Restrict access to chemical storage area to only authorized personnel.

      Code ATCP 76.12 (2)(d) - ACCESS RESTRICTED

    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Chloriene is at 0.2 ppm at the time of inspection

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical Repeat

      TELEPHONE ACCESSIBLE

      A telephone or other approved communication technology capable of connecting to emergency services is not working or not present.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

    • Serious Critical Repeat

      FIRST AID KIT-PROVIDED IN POOL AREA

      The first aid kit is missing from the pool area, or within 25 feet of enclosure with signage posted in the enclosure telling where the first aid kit is.

      Correction: Provide a first aid kit in the pool area or, if the first aid kit is within 25 feet of the enclosure, post signage that tells where the first aid kit is located.

      Code ATCP 76.27(1)(a) - FIRST AID KIT PRESENT

    • Serious Critical

      CLOSING CRITERIA-NO FUNCTIONAL EMERGENCY PHONE

      The Responsible Supervisor or operator has not closed the pool due to a nonfunctional emergency phone.

      Correction: Close the pool in the event of a nonfunctional emergency phone.

      Code ATCP 76.30 (1)(g) - FUNCTIONAL EMERGENCY PHONE

    • Serious Critical

      DRINKING FOUNTAIN PROVIDED

      There is no drinking fountain provided. Te current fountian is not operational

      Correction: Provide a drinking fountain within 300 feet walking distance.

      Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED

    • Serious Critical

      GATES AND DOORS-SELF-CLOSING

      The gate or door does not self-close. The gate located at the back of the pool does not close and latch by itself

      Correction: Provide a self-closing gate or door.

      Code ATCP 76.34(4)(a)(1m)(a) -SELF-CLOSING

  6. Jun 28, 2024 Routine · 3 critical, 7 non-critical
    • Not serious Non-critical

      SKIMMERS-ADJUSTED

      Skimmers not adjusted to ensure vigorous skimming.

      Correction: Adjust skimmers to maintain vigorous skimming .

      Code ATCP 76.11(2)(a) 1. - SKIMMERS ADJUSTED

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not operational

      Correction: Adjust or repair the flowmeter

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      ALKALINITY

      The total alkalinity is 30

      Correction: Maintain the total alkalinity of the water between 60 and 180 ppm as calcium carbonate or be able to demonstrate to the department or its agent that another level of total alkalinity produces chemically balanced water.

      Code ATCP 76.14(5)(d) - ALKALINITY

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      POSTING SIGNAGE- NO PROLONGED BREATH HOLDING

      Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.

      Correction: Provide signage or provide other communication warning against prolonged breath holding.

      Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING

    • Not serious Non-critical

      POOL EQUIPMENT-PROPERLY MAINTAINED

      The hand rails areound the pool are loose and can be easily removed.

      Correction: Maintain the hand rails.

      Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT

    • Serious Critical

      CHEMICAL STORAGE, SEPARATION OF OXIDIZERS AND ACIDS

      Chemicals are all stored directly touching eachother.

      Correction: Store oxidizers separately from acids.

      Code ATCP 76.12 (2)(c) - CHEMICAL SEPARATION OXIDIZERS, ACIDS

    • Serious Critical

      TELEPHONE ACCESSIBLE

      A telephone or other approved communication technology capable of connecting to emergency services is not working or not present.

      Correction: Provide a working telephone or other technology capable of connecting with emergency services.

      Code ATCP 76.26(2)(a) - TELEPHONE ACCESSIBLE

    • Serious Critical

      FIRST AID KIT-PROVIDED IN POOL AREA

      The first aid kit is missing from the pool area, or within 25 feet of enclosure with signage posted in the enclosure telling where the first aid kit is.

      Correction: Provide a first aid kit in the pool area or, if the first aid kit is within 25 feet of the enclosure, post signage that tells where the first aid kit is located.

      Code ATCP 76.27(1)(a) - FIRST AID KIT PRESENT

  7. Jun 27, 2023 Routine · 9 non-critical, 3 repeat
    • Not serious Non-critical

      FLOWMETER, VALVES AND GAUGES NOT FUNCTIONAL

      The flowmeter was not functioning.

      Correction: Repair or replace the specified equipment so an accurate reading can be recorded.

      Code ATCP 76.11(5)

    • Not serious Non-critical

      ALKALINITY OUT OF BALANCE

      The total alkalinity is 50.

      Correction: Maintain the total alkalinity between 60 and 180 ppm.

      Code ATCP 76.14(4)(d)

    • Not serious Non-critical

      WATER POTENTIAL OUT OF RANGE

      The water potential was 921 mV at the time of the inspection.

      Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed.

      Code ATCP 76.14(5)(a)

    • Not serious Non-critical

      WATER TESTING FREQUENCY - POOLS

      The water testing frequency for combined chlorine, alkalinity and cyanuric acid is not in compliance with ATCP 76.18(1).

      Correction: Perform water testing in accordance with ATCP 76.18(1).

      Code ATCP 76.18(1)

    • Not serious Non-critical

      BIOHAZARD KIT UNAVAILABLE

      No biohazard safety kit is located on the premises.

      Correction: Provide a biohazard safety kit at the first aid station.

      Code ATCP 76.27(2)

    • Not serious Non-critical Repeat

      TELEPHONE NOT WORKING

      The emergency telephone does not work.

      Correction: Provide a functional emergency telephone immediately.

      Code [A] ATCP 76.26(2)

    • Not serious Non-critical

      FIRST AID KIT UNAVAILABLE

      A first aid kit is not available in the pool area.

      Correction: Provide a first aid kit in the pool area.

      Code [A] ATCP 76.27(1)

    • Not serious Non-critical Repeat

      DRINKING FOUNTAIN NOT FUNCTIONAL

      The drinking fountain is not functional.

      Correction: Repair the drinking fountain.

      Code [A] ATCP 76.33(1)(g)

    • Not serious Non-critical Repeat

      SELF-CLOSING AND LATCHING GATES

      The door or gate to the pool enclosure is not self-closing or latching.

      Correction: Repair the door immediately so that it is self-closing and latching.

      Code [A] ATCP 76.34(4)

Source: Juneau County Health Department. History last read Oct 11, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.