RecordWell Data

Yukon Trails Campground Outdoor Wading Pool

N2330 COUNTY ROAD HH, Lyndon Station, WI 53944 · Juneau County

23cited violations
8serious tier
7inspections

Establishment

Type
Pool / recreational water (Pool - Moderate with Features)
Inspected by
Juneau County Health Department
License / ID
HSAT-7QWPGS
Status
Permitted
Phone
(608) 666-3261
Official record
Juneau County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
20262124
2025344
2024170
2023100

Inspections

  1. Jun 23, 2026 Re-inspection · 2 critical, 4 non-critical, 6 repeat
    • Not serious Non-critical Repeat

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical Repeat

      POOL WATER TESTED PEAK PATRON LOAD, PH AND SANITIZER

      Pool water not tested for pH and disinfectant at least one other time during the day’s peak patron load.

      Correction: Test pool water for pH and disinfectant at least one time during the day’s peak patron load.

      Code ATCP 76.18(1)(a)2 - WATER TESTED, SANITIZER, PH, PEAK LOAD P

    • Not serious Non-critical Repeat

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical Repeat

      ALKALINITY TEST

      Pool water not tested at least once a week for total alkalinity.

      Correction: Test pool water at least once a week for total alkalinity.

      Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY

    • Serious Critical Repeat

      MINIMUM DISINFECTANT RESIDUAL

      Chlorine is at 0.0

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical Repeat

      PH

      The pH is above 8.0, taking 4 drops of acid demand

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

  2. Jun 22, 2026 Routine · 2 critical, 4 non-critical, 2 repeat
    • Not serious Non-critical

      INTERLOCK-LOG KEPT

      A log of the monthly interlock tests is not being kept.

      Correction: Keep a log of monthly interlock tests.

      Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT

    • Not serious Non-critical

      POOL WATER TESTED PEAK PATRON LOAD, PH AND SANITIZER

      Pool water not tested for pH and disinfectant at least one other time during the day’s peak patron load.

      Correction: Test pool water for pH and disinfectant at least one time during the day’s peak patron load.

      Code ATCP 76.18(1)(a)2 - WATER TESTED, SANITIZER, PH, PEAK LOAD P

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      ALKALINITY TEST

      Pool water not tested at least once a week for total alkalinity.

      Correction: Test pool water at least once a week for total alkalinity.

      Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY

    • Serious Critical Repeat

      MINIMUM DISINFECTANT RESIDUAL

      Chlorine is at 0.0

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical Repeat

      PH

      The pH is above 8.0, taking 4 drops of acid demand

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

  3. Jun 27, 2025 Re-inspection 2 · No items found

    No violations cited.

  4. Jun 26, 2025 Re-inspection · 2 critical
    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Choloriene is at 0.0 at the time of inspection

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      PH

      The pH is well above 8.0

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

  5. Jun 25, 2025 Routine · 2 critical
    • Serious Critical

      MINIMUM DISINFECTANT RESIDUAL

      Choloriene is at 0.0 at the time of inspection

      Correction: Close the pool until disinfectant level is in compliance with ATCP 76.14 Table A.

      Code ATCP 76.14(5)(a) - MINIMUM DISINFECTANT RESIDUAL

    • Serious Critical

      PH

      The pH is well above 8.0

      Correction: Maintain the pH at 7.2 to 7.8. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.

      Code ATCP 76.14(5)(c) - PH

  6. Jun 20, 2024 Routine · 7 non-critical
    • Not serious Non-critical

      SKIMMERS REPAIRED OR REPLACED AS NEEDED

      There are no skimmer doors present on the kiddie pool

      Correction: Repair or replace skimmer, weirs or gutters as needed.

      Code ATCP 76.11(2)(b) 2. - SKIMMERS REPAIRED OR REPLACED

    • Not serious Non-critical

      FLOWMETER, VALVE, OR GAUGE NOT MAINTAINED

      The flowmeter is not operational

      Correction: Adjust or repair the flowmeter

      Code ATCP 76.11(5)(a) - FLOWMETER, VALVE, GAUGE NOT MAINTAINED

    • Not serious Non-critical

      POOL WATER TESTED BEFORE OPENING, PH AND SANITIZER

      there are multiple days where the kiddie pool has not been tested for chlorine

      Correction: Test pool water for pH and disinfectant or sanitizer residual daily before the pool is open to the public or before the pool is in use.

      Code ATCP 76.18(1)(a)1 - POOL TESTED SANITIZER AND PH, BEFORE OPE

    • Not serious Non-critical

      COMBINED CHLORINE TEST

      Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level.

      Correction: Test pool water at least twice a week for the combined chlorine level.

      Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,

    • Not serious Non-critical

      ALKALINITY TEST

      Pool water not tested at least once a week for total alkalinity.

      Correction: Test pool water at least once a week for total alkalinity.

      Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY

    • Not serious Non-critical

      CYANURIC TEST

      Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.

      Correction: Test water for the cyanuric acid at least once a week.

      Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC

    • Not serious Non-critical

      POOL BASIN MAINTAINED FREE OF DEFECTS

      The pool tiles are in need of replacement as some are cracked and others are missing.

      Correction: Maintained the pool basin free of cracks or other defects, and repaired or refinished as necessary to maintain it in a cleanable condition.

      Code ATCP 76.33(1)(a)2 - POOL BASIN GOOD REPAIR

  7. Jun 15, 2023 Routine · No items found

    No violations cited.

Source: Juneau County Health Department. History last read Oct 11, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.