Abbey Court Apartments
2101 ABBEY COURT, Onalaska, WI 54650 · La Crosse County
Establishment
- Type
- Pool / recreational water (Swimming)
- Inspected by
- La Crosse County Health Department
- License / ID
- MWAS-BR3KLF
- Status
- Permitted
- Phone
- (608) 498-4498
- Official record
- La Crosse County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 1 |
| 2025 | 1 | 0 | 0 |
| 2024 | 1 | 6 | 1 |
| 2023 | 1 | 5 | 0 |
Inspections
-
Jun 4, 2026 Routine · 1 critical, 1 non-critical
-
Not serious
Non-critical
ELECTRONIC MONITORING FREQUENCY OF TESTING
The pool, with an electronic monitoring device, has not been manually tested at least once a day with an approved test kit for pH and disinfectant or sanitizer residual. Chemicals are tested on all week days but no records or testing done on the weekends when maintainance has time off. Front desk staff or other staff must still test chorine and pH levels each morning of the weekend when the pools are open.
Correction: Manually test the pool at least once a day for pH and disinfectant or sanitizer residual with an approved test kit.
Code ATCP 76.18(3)(a) - ELECTRONIC MONITORING TEST FREQ
-
Serious
Critical
Corrected on site
DRINKING FOUNTAIN PROVIDED
Drinking water fountain available is not providing water. GFCI outlet was tripped, reset during inspection
Correction: Provide a drinking fountain within 300 feet walking distance.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Not serious
Non-critical
-
Jun 4, 2025 Routine · No items found
No violations cited.
-
Jun 6, 2024 Routine · 1 critical, 5 non-critical
-
Not serious
Non-critical
SPARE STRAINER BASKET OR SCREEN AVAILABLE
Spare strainer or screen not available
Correction: Provide a spare strainer or screen
Code ATCP 76.11(2)(d) 2. - SPARE STRAINER OR SCREEN
-
Not serious
Non-critical
ELECTRONIC MONITORING WATER POTENTIAL
The water potential ("ORP") is 588 mV and water has not been tested manually. Probes are in need of replacement, replacement already on hand and ready to be replaced
Correction: Maintain water potential between 650−900 mV, and manually test the water if the water potential reads below 650 mV or above 900 mV.
Code ATCP 76.14(6)(a) - OXIDATION POTENTIAL
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-FILTER OPERATION MANUAL
The manual of instruction on filter operation was not permanently maintained on premises
Correction: Maintain the manual of instruction on filter operation on premises.
Code ATCP 76.32(3)(a)5. - FILTER MANUAL
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-EQUIPMENT (EXCEPT FILTER) OPERATION AND MAINTENANCE
Instructions for operation and maintenance of all equipment were not permanently maintained on premises: missing for water heater, chemtrol, pumps, etc. Pump performance curves available
Correction: Maintain instructions for operation and maintenance of all equipment on the premises.
Code ATCP 76.32(3)(a)6. - EQUIPMENT MANUALS
-
Not serious
Non-critical
Corrected on site
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises. Cannot find logs, drains are not expired (due 6/26/2030) per county records.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Serious
Critical
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Not serious
Non-critical
-
Jun 13, 2023 Routine · 5 non-critical, 1 repeat
-
Not serious
Non-critical
WATER TESTING FREQUENCY - POOLS
The water testing frequency for chlorine and pH is not in compliance with ATCP 76.18(1), must be tested on the weekend.
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Non-critical
SHOWERS NOT MAINTAINED
The outdoor shower and shower in whirlpool room are not functioning properly, they do not turn on.
Correction: Repair the showers so they are in compliance with ATCP 76.33(2)(b).
Code ATCP 76.33(2)(b)
-
Not serious
Non-critical
Repeat
BACKFLOW - HOSE BIBBS
Neither hose bibb on the pool deck is not protected against backsiphonage.
Correction: Install a hose bibb atmospheric vacuum breaker that meets the ASSE 1011 standard on the hose bibb.
Code [A] ATCP 76.33(1)(d)
-
Not serious
Non-critical
BLANKETS MISSING
2 durable blankets are not available in the pool area.
Correction: Provide 2 durable blankets in the pool area.
Code [B] ATCP 76.27(1)
-
Not serious
Non-critical
FIRST AID SUPPLIES MISSING
Multiple items are missing from the first aid kit, these include: Elastic bandage, eye wash (current bottle expired 2021), tweezers.
Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit.
Code [C] ATCP 76.27(1)
-
Not serious
Non-critical
Source: La Crosse County Health Department. History last read Oct 11, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.