La Crosse Country Club
300 MARCOU, Onalaska, WI 54650 · La Crosse County
Establishment
- Type
- Pool / recreational water (Combination)
- Inspected by
- La Crosse County Health Department
- License / ID
- HSAT-7QWEY8
- Status
- Permitted
- Phone
- (608) 781-5837
- Official record
- La Crosse County Health Department inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 2 | 13 | 4 |
| 2025 | 1 | 9 | 2 |
| 2024 | 1 | 6 | 1 |
| 2023 | 1 | 5 | 0 |
Inspections
-
Aug 18, 2026 Re-inspection · 1 critical, 1 repeat
-
Serious
Critical
Repeat
DRINKING FOUNTAIN PROVIDED
There is no drinking fountain provided. Drinking fountain has been removed. A water cooler with cups was placed on the pool deck during inspection, but was not available for a portion of the inspection.
Correction: Provide a drinking fountain within 300 feet walking distance.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Serious
Critical
Repeat
-
Jul 7, 2026 Routine · 3 critical, 9 non-critical, 2 repeat
-
Not serious
Non-critical
Repeat
Corrected on site
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Current GPM is at 570, which does not allow the pool to turn over water every 6 hours. Flow adjusted to maintain a GPM of at least 603 during inspection.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate and ensure that the GPM maintains at or above 600 GPM at all times.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
SAFETY DATA SHEET
A safety data sheet was not available for any of the chemicals used in the pool area.
Correction: Maintain a safety data sheet for each chemical on site.
Code ATCP 76.12 (4)(b)1. - SAFETY DATA SHEETS
-
Not serious
Non-critical
INTERLOCK-LOG KEPT
A log of the monthly interlock tests is not being kept.
Correction: Keep a log of monthly interlock tests.
Code ATCP 76.13 (1)(c)4 - INTERLOCK, LOG KEPT
-
Not serious
Non-critical
Repeat
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
COMBINED CHLORINE TEST
Chlorine is used and pool water is not tested at least twice a week for the combined chlorine level. Combined chlorine testing is not being done.
Correction: Test pool water at least twice a week for the combined chlorine level.
Code ATCP 76.18(1)(b) - WATER TESTED COMBINED CHLORINE,
-
Not serious
Non-critical
ALKALINITY TEST
Pool water not tested at least once a week for total alkalinity.
Correction: Test pool water at least once a week for total alkalinity.
Code ATCP 76.18(1)(c) - WATER TESTED ALKALINITY
-
Not serious
Non-critical
CYANURIC TEST
Cyanuric acid is used in the pool basin and the cyanuric acid concentration is not tested at least once a week.
Correction: Test water for the cyanuric acid at least once a week.
Code ATCP 76.18(1)(d) - WATER TESTED CYANURIC
-
Not serious
Non-critical
FECAL, VOMIT, BLOOD, DOCUMENT CHEMICAL CONCENTRATIONS AT TIME OF EVENT
For a fecal, blood or vomit incident, the date, time, and chemical concentrations when the event occurred were not documented. Fecal incident occurred within the last month, and it was not documented how the fecal matter was cleaned.
Correction: Document date, time, and chemical concentrations when the event occurred. Record the date and time of the event, and the free available chlorine or bromine.
Code ATCP 76.31(2)(a) - CHEMICAL CONCENTRATIONS AT TIME OF EVENT
-
Not serious
Non-critical
VGBA-DRAIN COVER INFO-DOCUMENTS-DRAIN COVER LOG PRESENT
The operator does not have a log that can be used to evaluate the drain covers, and there is no alternative form of proof available about drain cover replacement.
Correction: Maintain a log that can be used to evaluate the drain covers, or keep receipts or affidavits that show make and model of drain cover.
Code ATCP 76.38(2)(a) - DRAIN COVER LOG
-
Serious
Critical
Corrected on site
PH
The pH is 8.0. pH corrected to 7.8.
Correction: Maintain the pH at 7.2 to 7.8. Recommend keeping pH between 7.4-7.6. Note: *it is strongly encouraged to use a pH meter with an accuracy greater than 0.1 or better.
Code ATCP 76.14(5)(c) - PH
-
Serious
Critical
DRINKING FOUNTAIN PROVIDED
There is no drinking fountain provided. Drinking fountain has been removed. A water cooler with cups was placed on the pool deck during inspection, but was not available for a portion of the inspection.
Correction: Provide a drinking fountain within 300 feet walking distance.
Code ATCP 76.33(1)(g)1. DRINKING FOUNTAIN PROVIDED
-
Serious
Critical
VGBA-EXISTING POOLS, PUMP CURVE AND DRAIN COVER INFO
The operator of an existing pool does not have the pump curve or drain cover specifications. Drain cover specifications and pump curve are not kept on site for review.
Correction: Obtain a pump curve and information that describes make, model and gpm rating for the drain covers.
Code ATCP 76.38(1)(b) - PUMP CURVE
-
Not serious
Non-critical
Repeat
Corrected on site
-
Jul 18, 2025 Routine · 2 critical, 7 non-critical
-
Not serious
Non-critical
RECIRCULATION (TURNOVER) RATE NOT MET
The recirculation (turnover) rate has not been met. Current gallons per minute flow rate for the large pool is 475 gpm, which is not enough to maintain the 6 hour turnover.
Correction: Immediately adjust or repair equipment to operate at a proper turnover rate of at least 600 gpm to achieve a turnover rate of at least 6 hours.
Code ATCP 76.11(4)(c) - RECIRCULATION RATE
-
Not serious
Non-critical
COMBINED CHLORINE PLAN PRESENT
The operator has not developed and implemented a plan to minimize combined chlorine in the pool. The previous plan that was implemented was not available for reivew.
Correction: Develop and implement a plan to minimize combined chlorine in the pool.
Code ATCP 76.14(5)(e)1. - PLAN PRESENT
-
Not serious
Non-critical
RESPONSIBLE SUPERVISOR INTERLOCK TESTING
Records to show interlock testing were not available for review at time of inspection. Responsible supervisor indicated over the phone that these records are maintained digitally.
Correction: Have the responsible supervisor ensure that monthly interlock tests are done and recorded.
Code ATCP 76.21 (1)(c)5.- INTERLOCK TESTING
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-EQUIPMENT (EXCEPT FILTER) OPERATION AND MAINTENANCE
Instructions for operation and maintenance of all equipment were not permanently maintained on premises. Responsible supervisor indicated via phone that all records are available on the computer, but could not be reviewed during inspection.
Correction: Maintain instructions for operation and maintenance of all equipment on the premises.
Code ATCP 76.32(3)(a)6. - EQUIPMENT MANUALS
-
Not serious
Non-critical
FILES MAINTAINED PERMANENT-VGBA DRAIN COVER DOCUMENTATION
The Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation was not permanently maintained on premises.
Correction: Maintain Virginia Graeme Baker Act main drain and equalizer cover replacement receipts or similar documentation on the premises.
Code ATCP 76.32(3)(a)9. - VGBA DRAIN COVER
-
Not serious
Non-critical
SHOWER, TOILET, DRESSING FACILITIES-MAINTAINED
The front right shower in both the boys and girls locker rooms do not have a good water flow. Water only trickles out of the faucets and is not good for showering.
Correction: Maintain the shower, toilet and dressing facilities in good repair.
Code ATCP 76.33 (2)(a)1. - GOOD REPAIR
-
Not serious
Non-critical
POOL EQUIPMENT-PROPERLY MAINTAINED
The pool equipment is not properly maintained. The pool ladder to the right of the guard chair at the 4 ft end and to the left of the guard chair the 10 ft end are loose.
Correction: Maintain the pool equipment and tighten the ladders.
Code ATCP 76.33(1)(e)3. - MAINTENANCE OF POOL EQPT
-
Serious
Critical
CHEMICAL STORAGE ACCESS RESTRICTED
Chemical storage area door is not kept locked during open swim hours.
Correction: Restrict access to chemical storage area to only authorized personnel.
Code ATCP 76.12 (2)(d) - ACCESS RESTRICTED
-
Serious
Critical
RESPONSIBLE SUPERVISOR RECORDS MAINTAIN
Records are not available on site for review at the time of inspection. Missing pool testing records for combined chlorine, alkalinity, and cyanuric acid. Responsible supervisor indicated over the phone that these records are maintained digitally.
Correction: Have the responsible supervisor ensure that records are maintained.
Code ATCP 76.21 (1)(c)7. - RECORDS MAINTENANCE
-
Not serious
Non-critical
-
Jul 15, 2024 Routine · 1 critical, 5 non-critical
-
Not serious
Non-critical
SKIMMERS MAINTAINED CLEAN
Center main drain cover is blocked with sand and leaf litter.
Correction: Maintain the drain covers in clean condition.
Code ATCP 76.11(2)(b) 1. - SKIMMERS CLEAN
-
Not serious
Non-critical
REAGENTS REPLACED
Test kit reagents not replaced as recommended by the manufacturer. The R-0870 DPD Powder has a best by date of 6/2024.
Correction: Discard expired reagents. Replace test kit reagents as recommended by the manufacturer.
Code ATCP 76.17 (2)(b) - REAGENTS REPLACED
-
Not serious
Non-critical
LIFEGUARD, ATTENDANT STAFFING PLAN-DIAGRAM, LIFEGUARD CHAIRS
The lifeguard and attendant staffing plan is missing diagrams for maximum patron load for open swim, swim lessons, and swim meets. Currently there is only one diagram for the average patron load swim.
Correction: Provide a diagram that shows location of lifeguard chairs for all of the activities listed above, in the lifeguard and attendant staffing plan.
Code ATCP 76.22(1)(b)7.d - LIFEGUARD CHAIRS
-
Not serious
Non-critical
FIRST AID KIT-INSTANT COLD PACKS
The first aid kit is missing instant cold packs.
Correction: Provide instant cold packs for the first aid kit.
Code ATCP 76.27(1)(b)9. - INSTANT COLD PACKS
-
Not serious
Non-critical
POSTING SIGNAGE- NO PROLONGED BREATH HOLDING
Signage or other communication warning against prolonged breath-holding is not posted or otherwise provided.
Correction: Provide signage or provide other communication warning against prolonged breath holding. Provide signage that is in at least 1 inch high lettering.
Code ATCP 76.29(1)(f) - NO PROLONGED BREATH HOLDING
-
Serious
Critical
Corrected on site
CO ALARM-POOL EQUIPMENT ROOM
There is a fuel-burning device in the equipment room but no functional CO alarm in the equipment room. A functioning CO detector was provided in the equipment room during this inspection.
Correction: Provide a CO alarm in the equipment room and install per manufacturer's instructions.
Code ATCP 76.33(4)(d)1. -CO ALARM EQPT ROOM
-
Not serious
Non-critical
-
Jun 20, 2023 Routine · 5 non-critical
-
Not serious
Non-critical
Corrected on site
CHEMICAL LABELING
Clear sprayer in pump room is not labeled according to ATCP 76.12(1). Container labeled during inspection.
Correction: Label the chemical container according to ATCP 76.12(1).
Code ATCP 76.12(1)
-
Not serious
Non-critical
MSDS AVAILABILITY
Material safety data sheets are not available for all chemicals used in the facility.
Correction: Provide material safety data sheets for all chemicals used in the facility.
Code ATCP 76.12(4)(b)
-
Not serious
Non-critical
REAGENTS STORED IN ORIGINAL CONTAINERS
R-0003 in Taylor FAS-DPD test kit expired 03/2023.
Correction: Replace expired reagents.
Code ATCP 76.17(2)
-
Not serious
Non-critical
DRINKING FOUNTAIN NOT FUNCTIONAL
The drinking fountain is not functional and has been removed from the pool enclosure.
Correction: Replace the drinking fountain.
Code [A] ATCP 76.33(1)(g)
-
Not serious
Non-critical
BLANKETS MISSING
Only one durable blankets is available in the pool area.
Correction: Provide 2 durable blankets in the pool area.
Code [B] ATCP 76.27(1)
-
Not serious
Non-critical
Corrected on site
Source: La Crosse County Health Department. History last read Oct 11, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.