Van Buren Place Apartment Homes
1351 O'KEEFFE AVE, Sun Prairie, WI 53590 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- LICSWD-2020-00142
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 0 |
| 2025 | 1 | 4 | 0 |
| 2024 | 1 | 5 | 0 |
| 2023 | 1 | 3 | 0 |
| 2022 | 2 | 0 | 0 |
Inspections
-
Jul 10, 2026 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
09a - FLOW METER (P
The flow meter is not functional.
Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
16d - COMBINED CHLORINE (Pf)
The operator does not have a combined chlorine plan or is not following combined chlorine plan.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken:
-
Jul 29, 2025 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
14e - WATER POTENTIAL ORP (Pf)
The water potential was 619 mV at the time of the inspection.
Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed to maintain the water potential between 650 to 900 mV.
Code ATCP 76.14(5)(a)
-
Not serious
Action taken:
20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE (Pf)
The water testing frequency for combined chlorine and cyanuric acid are not in compliance with ATCP 76.18(2).
Correction: Perform water testing in accordance with ATCP 76.18(2).
Code ATCP 76.18(2). Test combined chlorine level daily. Test cyan
-
Not serious
Action taken:
31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED
There is some water leaking at the base of the pump.
Correction: Properly locate, install, maintain and repair equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf)
No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.
Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.
Code ATCP 76.38
-
Not serious
Action taken:
-
Jul 19, 2024 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: Operator replaced the flow
Corrected on site
09a - FLOW METER
The flow meter is not functional.
Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken:
14e - WATER POTENTIAL ORP
The water potential was 558 mV at the time of the inspection.
Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed to maintain the water potential between 650 to 900 mV.
Code ATCP 76.14(6)(a)
-
Not serious
Action taken: Operator closed the whirlp
Corrected on site
16b - CYANURIC ACID
The cyanuric acid concentration is 90 ppm
Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.
Code ATCP 76.14(4)(b)
-
Not serious
Action taken:
20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE
The water testing frequency for combined chlorine and cyanuric acid are not in compliance with ATCP 76.18(2). Combined chlorine test reading on the log are not accurate and the cyanuric acid test is not being completed.
Correction: Perform water testing in accordance with ATCP 76.18(2). For the whirlpool, test combined chlorine concentration daily and test the cyanuric acid concentration at least once a week.
Code ATCP 76.18(2)
-
Not serious
Action taken:
31b - EQUIPMENT NOT MAINTAINED
A seal on the whirlpool pump is leaking water.
Correction: Repair and maintain all equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken: Operator replaced the flow
Corrected on site
-
Aug 15, 2023 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
Corrected on site
09a - FLOW METER
The flow meter is not functional.
Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken: Operator voluntarily close
Corrected on site
16b - CYANURIC ACID
The cyanuric acid concentration is 90-100 ppm.
Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.
Code ATCP 76.14(4)(b)
-
Not serious
Action taken:
20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE
The water testing frequency for combined chlorine and cyanuric acid is not in compliance with ATCP 76.18(1) and ATCP 76.18(2).
Correction: Perform water testing in accordance with ATCP 76.18(1) and ATCP 76.18(2). Test combined chlorine level daily. Test cyanuric acid level at least once a week.
Code ATCP 76.18(1) and ATCP 76.18(2)
-
Not serious
Action taken:
Corrected on site
-
Aug 18, 2022 Pre-Inspection · No Reinspection Required
No violations cited.
-
Aug 18, 2022 Routine Inspection · No Reinspection Required
No violations cited.