Pool / recreational water (Swimming Pool)
Inspected by
Public Health Madison & Dane County
License / ID
LICSWD-2020-00142
Official record
Public Health Madison & Dane County inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026120
2025140
2024150
2023130
2022200

Inspections

  1. Jul 10, 2026 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      09a - FLOW METER (P

      The flow meter is not functional.

      Correction: Repair, replace, or install the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      16d - COMBINED CHLORINE (Pf)

      The operator does not have a combined chlorine plan or is not following combined chlorine plan.

      Correction: Provide a plan with all components required under ATCP 76.14(5)(e)

      Code ATCP 76.14(5)(e)

  2. Jul 29, 2025 Routine Inspection · No Reinspection Required
    • Not serious Action taken:

      14e - WATER POTENTIAL ORP (Pf)

      The water potential was 619 mV at the time of the inspection.

      Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed to maintain the water potential between 650 to 900 mV.

      Code ATCP 76.14(5)(a)

    • Not serious Action taken:

      20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE (Pf)

      The water testing frequency for combined chlorine and cyanuric acid are not in compliance with ATCP 76.18(2).

      Correction: Perform water testing in accordance with ATCP 76.18(2).

      Code ATCP 76.18(2). Test combined chlorine level daily. Test cyan

    • Not serious Action taken:

      31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED

      There is some water leaking at the base of the pump.

      Correction: Properly locate, install, maintain and repair equipment.

      Code ATCP 76.33(1)(e)

    • Not serious Other

      34f - VGBA COVERS DOCUMENTATION (Pf)

      No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.

      Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.

      Code ATCP 76.38

  3. Jul 19, 2024 Routine Inspection · No Reinspection Required
    • Not serious Action taken: Operator replaced the flow Corrected on site

      09a - FLOW METER

      The flow meter is not functional.

      Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken:

      14e - WATER POTENTIAL ORP

      The water potential was 558 mV at the time of the inspection.

      Correction: Manually test the pool water and recalibrate the oxidation potential controller if needed to maintain the water potential between 650 to 900 mV.

      Code ATCP 76.14(6)(a)

    • Not serious Action taken: Operator closed the whirlp Corrected on site

      16b - CYANURIC ACID

      The cyanuric acid concentration is 90 ppm

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

    • Not serious Action taken:

      20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE

      The water testing frequency for combined chlorine and cyanuric acid are not in compliance with ATCP 76.18(2). Combined chlorine test reading on the log are not accurate and the cyanuric acid test is not being completed.

      Correction: Perform water testing in accordance with ATCP 76.18(2). For the whirlpool, test combined chlorine concentration daily and test the cyanuric acid concentration at least once a week.

      Code ATCP 76.18(2)

    • Not serious Action taken:

      31b - EQUIPMENT NOT MAINTAINED

      A seal on the whirlpool pump is leaking water.

      Correction: Repair and maintain all equipment.

      Code ATCP 76.33(1)(e)

  4. Aug 15, 2023 Routine Inspection · No Reinspection Required
    • Not serious Action taken: Corrected on site

      09a - FLOW METER

      The flow meter is not functional.

      Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.

      Code ATCP 76.11(5)

    • Not serious Action taken: Operator voluntarily close Corrected on site

      16b - CYANURIC ACID

      The cyanuric acid concentration is 90-100 ppm.

      Correction: Lower the concentration of cyanuric acid to 30 ppm or lower.

      Code ATCP 76.14(4)(b)

    • Not serious Action taken:

      20d - WATER TESTING - WHIRLPOOL, THERAPY, EXERCISE

      The water testing frequency for combined chlorine and cyanuric acid is not in compliance with ATCP 76.18(1) and ATCP 76.18(2).

      Correction: Perform water testing in accordance with ATCP 76.18(1) and ATCP 76.18(2). Test combined chlorine level daily. Test cyanuric acid level at least once a week.

      Code ATCP 76.18(1) and ATCP 76.18(2)

  5. Aug 18, 2022 Pre-Inspection · No Reinspection Required

    No violations cited.

  6. Aug 18, 2022 Routine Inspection · No Reinspection Required

    No violations cited.