Belmar Apartments
2113 RED ARROW TRL, Fitchburg, WI 53711 · Dane County
Establishment
- Type
- Pool / recreational water (Swimming Pool)
- Inspected by
- Public Health Madison & Dane County
- License / ID
- LICSWD-2017-00357
- Official record
- Public Health Madison & Dane County inspection reports
Year by year
| Year | Inspections | Violations | Serious |
|---|---|---|---|
| 2026 | 1 | 2 | 0 |
| 2025 | 2 | 26 | 0 |
| 2024 | 1 | 8 | 0 |
| 2023 | 2 | 19 | 0 |
| 2021 | 1 | 0 | 0 |
| 2019 | 2 | 0 | 0 |
| 2018 | 1 | 0 | 0 |
| 2017 | 2 | 0 | 0 |
Inspections
-
Jul 14, 2026 Routine Inspection · No Reinspection Required
-
Not serious
Action taken: PIC added pH increaser, po
Corrected on site
16a - pH (P)
The pH is 7.0 and yellow on the scale.
Correction: Maintain the pH between 7.2 and 7.8.
Code ATCP 76.14(5)(c)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf)
The log available lists installation date and is missing information such as as gallons per minute rating, life span, and receipts.
Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.
Code ATCP 76.38
-
Not serious
Action taken: PIC added pH increaser, po
Corrected on site
-
Sep 5, 2025 Re-Inspection · No Reinspection Required
-
Not serious
Action taken:
04c - SKIMMER BASKET/WEIR - Not Corrected
The weir door at the skimmer closest to the water fountain is broken.
Correction: Replace.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken: A sign stating maintenance
11b - CHEMICAL - STORAGE (P)(Pf) - Not Corrected
Door to chemical storage area is not marked to indicate entry is for authorized personnel only.
Correction: Provide signage on chemical storage areas and provide list of emergency numbers ATCP 76.12(2).
Code ATCP 76.12(2)
-
Not serious
Action taken: RI on 9/5: CC not tested,
Repeat
20c - WATER TESTING - POOLS (Pf) - Not Corrected
The water testing frequency for all chemicals are not in compliance with ATCP 76.18(1). Generally, the pool was tested only once per day for pH and chlorine in June and July. The records stop at 8/8 and then the most recent dates for pool testing ate 8/18 and 8/19. No testing documented for alkalinity, combined chlorine, and cyanuric acid.
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Action taken: Provide CPO prior to openi
23b - NO CPO (Pf) - Not Corrected
The facility is not staffed with a current certified pool operator when required. CPO required due to lack of active managerial control observed during the past seasons.
Correction: Acquire or train a certified pool operator for the facility.
Code ATCP 76.20(2)(a)
-
Not serious
Action taken: Pool maintenance aware of
31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED - Not Corrected
In pump room floor is damp and there is a slow leak observed at pipe containing water returning to pool basin after recirculation system.
Correction: Properly locate, install, maintain and repair equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken:
-
Aug 26, 2025 Routine Inspection · Reinspection Required
-
Not serious
Action taken:
04c - SKIMMER BASKET/WEIR
The weir door at the skimmer closest to the water fountain is broken.
Correction: Replace.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
05a - SKIMMER/MAIN DRAIN RATIO (Pf)
The skimmer to main drain flow ratio is not set correctly. Both valves are at the same setting and mostly open.
Correction: Readjust the flow so that on pool with skimmers, only 20% of the flow comes through the main drain and 80% comes through the skimmers. On a gutter pool, 75% of the required recirculation flow shall be through the gutter and 25% through the main drain. For reverse flow pools, 100% recirculation must be through gutter or skimmers.
Code ATCP 76.11(2)(a)
-
Not serious
Action taken:
11b - CHEMICAL - STORAGE (P)(Pf)
Door to chemical storage area is not marked to indicate entry is for authorized personnel only.
Correction: Provide signage on chemical storage areas and provide list of emergency numbers ATCP 76.12(2).
Code ATCP 76.12(2)
-
Not serious
Action taken: Sanitarian provided DATCP
13d - INTERLOCK DEMONSTRATION OF KNOWLEDGE AND DOCUMENTS (P)
Operator cannot demonstrate knowledge and/or provide documentation of interlock system per requirements in ATCP 76.13(1)(c).
Correction: Operator must be able to demonstrate knowledge and provide documentation of interlock system.
Code ATCP 76.13(1)(c)
-
Not serious
Action taken:
16a - pH (P)
The pH test yielded a very pink indicating more than 8.0 on the testing vial.
Correction: Maintain the pH between 7.2 and 7.8.
Code ATCP 76.14(5)(c)
-
Not serious
Action taken:
16c - ALKALINITY (Pf)
The total alkalinity is 210ppm.
Correction: Maintain the total alkalinity between 60 and 180 ppm.
Code ATCP 76.14(5)(d)
-
Not serious
Action taken: Sanitarian provided DATCP
16d - COMBINED CHLORINE (Pf)
The operator does not have a combined chlorine plan.
Correction: Provide a plan with all components required under ATCP 76.14(5)(e)
Code ATCP 76.14(5)(e)
-
Not serious
Action taken:
Repeat
20c - WATER TESTING - POOLS (Pf)
The water testing frequency for all chemicals are not in compliance with ATCP 76.18(1). Generally, the pool was tested only once per day for pH and chlorine in June and July. The records stop at 8/8 and then the most recent dates for pool testing ate 8/18 and 8/19. No testing documented for alkalinity, combined chlorine, and cyanuric acid.
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Action taken: Provide CPO prior to openi
23b - NO CPO (Pf)
The facility is not staffed with a current certified pool operator when required. CPO required due to lack of active managerial control observed during the past seasons.
Correction: Acquire or train a certified pool operator for the facility.
Code ATCP 76.20(2)(a)
-
Not serious
Action taken: Schedule reopening inspect
23d - NO RESPONSIBLE SUPERVISOR (P)
No responsible supervisor is available or performing duties as required in 76.21 including ensuring safety and rescue equipment is in place, sanitation and water testing is performed, monthly interlock testing is performed, records are maintained, chemical safety training is provided to staff, and the pool is closed pursuant to ATCP 76.30.
Correction: The pool must be closed until a responsible supervisor is available to fulfill the responsibilities.
Code ATCP 76.21
-
Not serious
Action taken: 1. Ring buoy removed from
26h - RESCUE EQUIPMENT - ACCESSIBLE, GOOD REPAIR, SIZED (P)
1. Ring buoy is on site but not readily accessible as it's floating in the pool. 2. The mounted Shepherd's Crook does not meet size specifications and is not long enough to reach the deepest part of the pool.
Correction: Mount properly sized [equipment], position in a conspicuous place that is readily accessible, and maintain in good repair.
Code ATCP 76.26(1)
-
Not serious
Action taken: Sanitarian provided varian
26m - TELEPHONE - NO CONNECTION TO EMERGENCY SERVICES (P)
The pool phone is a push button phone that connects direct with 911.
Correction: Provide a telephone capable of connecting with emergency services at all times during pool operation or apply for a variance.
Code ATCP 76.26(2)(a)
-
Not serious
Action taken: Maintenance staff located
Repeat
Corrected on site
26s - BLANKETS MISSING (Pf)
Only 1 emergency blankets is available in the pool area.
Correction: Provide 2 conventional or emergency blankets in the pool area.
Code ATCP 76.27(1)(3)
-
Not serious
Action taken:
Repeat
26t - BIOHAZARD SAFETY KIT (Pf)
No biohazard safety kit is located at the first aid station or on the premises.
Correction: Provide a biohazard safety kit with the items listed in ATCP 76.27(2)(b) at the first aid station or on the premise. 1. Scoop and spatula. 2. Sanitizing hand wipes. 3. Sanitizing surface wipes. 4. Neoprene gloves. 5. Paper toweling. 6. Biohazard disposal bag at least 24"X24". 7. Twist tie or other effective means to close the bag. 8. Biohazard sorbent. 9. Storage case.
Code ATCP 76.27(2)
-
Not serious
Any of the following conditions or situa
28a - CLOSING CRITERIA (P)
The pool was not closed by the operator or responsible supervisor under the following condition: see condition c and f in the code reference section below.
Correction: Ensure that the closing criteria are adhered to under the listed below and post signage indicating closure.
Code ATCP 76.30
-
Not serious
Action taken: Plan to repair prior to op
29b - BASIN MAINTENANCE AND REPAIR
Several tiles are missing by 4 foot mark on vertical edge of length of pool furthest away from entry.
Correction: Maintain the pool basin in a clean, sanitary condition and free from cracks and defects.
Code ATCP 76.33(1)(a)
-
Not serious
Action taken: Maintenance staff turned o
Corrected on site
29g - DRINKING FOUNTAIN (P)
The drinking fountain does not have adequate flow to provide water.
Correction: Repair/clean the drinking fountain.
Code ATCP 76.33(1)(g)
-
Not serious
Action taken: Pool maintenance aware of
31b - EQUIPMENT NOT LOCATED/INSTALLED/MAINTAINED/ REPAIRED
In pump room floor is damp and there is a slow leak observed at pipe containing water returning to pool basin after recirculation system.
Correction: Properly locate, install, maintain and repair equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Action taken:
32d - CARBON MONOXIDE ALARMS (P)
There is no carbon monoxide alarm in pool equipment room where there is a fuel burning appliance.
Correction: Install functioning carbon monoxide alarms as applicable.
Code ATCP 76.33(4)(d)
-
Not serious
Action taken:
34e - POOL CLOSED SIGN
There is no sign on the premises that indicates that the pool is closed. Maintenance staff locked entry gate with spiral combination lock.
Correction: Provide a sign that communicates to the public that the pool is closed.
Code ATCP 76.34(5)
-
Not serious
Other
34f - VGBA COVERS DOCUMENTATION (Pf)
No documentation is available on site for VGBA main drain and/or equalizer covers showing make, model, gallons per minute rating, life span, and installation date.
Correction: Maintain documentation (log, receipts, or affidavits from a pool service company) of VGBA covers for main drain and equalizers on site and available for review during inspection. Documentation shall include the following: 1. Make 2. Model 3. Gallons per minute rating. 4. Life span. 5. Installation date.
Code ATCP 76.38
-
Not serious
Action taken:
-
Aug 7, 2024 Routine Inspection · No Reinspection Required
-
Not serious
Action taken:
06a - SPARE STRAINER BASKET
A spare strainer basket for the skimmers is not located on site.
Correction: Provide a spare basket or screen.
Code ATCP 76.11(2)(d)
-
Not serious
Action taken:
09a - FLOW METER
A flow meter is not installed in the pump room.
Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken: PIC trained employee to te
Corrected on site
20c - WATER TESTING - POOLS
The water testing frequency for alkalinity and combined chlorine is not in compliance.
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Action taken: PIC printed address to pos
Corrected on site
26o - EMERGENCY NUMBERS AND ADDRESS
The emergency numbers and the facility's location are not posted near the designated emergency phone.
Correction: Post the emergency numbers near the designated emergency phone.
Code ATCP 76.26(2)
-
Not serious
Action taken:
26r - BLANKETS MISSING
Only one blanket provided in the first aid kit.
Correction: Provide 2 durable blankets in the pool area.
Code ATCP 76.27(1)
-
Not serious
Action taken:
26s - BIOHAZARD SAFETY KIT
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Action taken: PIC has plans to repair.
31b - EQUIPMENT NOT MAINTAINED
In pump room water is leaking from sand filter and chlorine pump is dripping.
Correction: Repair and maintain all equipment.
Code ATCP 76.33(1)(e)
-
Not serious
Other
41a - MISCELLANEOUS
There is concrete chipping away and a loose tile at the equalizer at the 4'6" mark across from the patron pool entry.
Correction: Deck areas shall be maintained in good repair.
Code ATCP 76.33(1)(b)
-
Not serious
Action taken:
-
Aug 18, 2023 Re-Inspection · No Reinspection Required
-
Not serious
Action taken:
06a - SPARE STRAINER BASKET - Not Corrected
A spare strainer basket for the skimmers is not located on site.
Correction: Provide a spare basket or screen.
Code ATCP 76.11(2)(d)
-
Not serious
Action taken: Send testing logs to sanit
Repeat
20c - WATER TESTING - POOLS - Not Corrected
The water testing frequency for combined chlorine is not in compliance with ATCP 76.18(1), the reagent is not available onsite.
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Action taken:
26s - BIOHAZARD SAFETY KIT - Not Corrected
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Action taken: (1) Repair prior to openin
29b - BASIN DEFECTS - Not Corrected
(1) The pool basin is is exhibiting pitting and paint chipping. (2) ~ 20 blue tiles are missing from the vertical basin ledge.
Correction: Repair the pool basin so it is finished and easily cleanable.
Code ATCP 76.33(1)(a)
-
Not serious
Other
Repeat
34e - VGBA COVERS - Not Corrected
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model and replacement date. There is a carbon copy invoice in the pump room dated 5/2023 that suggests new drains were purchased and installed this season. The PIC informed that the drains were replaced at the start of this season and that the pump was replaced in the last 5 years.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Aug 15, 2023 Routine Inspection · Reinspection Required
-
Not serious
Action taken:
06a - SPARE STRAINER BASKET
A spare strainer basket for the skimmers is not located on site.
Correction: Provide a spare basket or screen.
Code ATCP 76.11(2)(d)
-
Not serious
Action taken:
Repeat
09a - FLOW METER
The flow meter is not functional. The bobber is stuck.
Correction: Repair or replace the flowmeter so an accurate rate of flow can be recorded.
Code ATCP 76.11(5)
-
Not serious
Action taken: Pool closed.
14a - CHLORINE TOO LOW
The chlorine residual was 0.6 at the time of the inspection.
Correction: Close the pool and raise the chlorine residual. Call inspector to schedule a reopening inspection.
Code ATCP 76.14(4)(a)
-
Not serious
Action taken:
20b - TEST KIT REAGENT STORAGE
Several of the test kit reagents are expired. The reagents required to test alkalinity are not all available onsite.
Correction: Keep reagents in original containers.
Code ATCP 76.17(2)
-
Not serious
Action taken:
Repeat
20c - WATER TESTING - POOLS
The water testing frequency for chlorine, pH, alkalinity, combined chlorine, and cyanuric acid is not in compliance with ATCP 76.18(1). There are days where the pool is open and the pool is not tested. If tested the pool is tested for pH and chlorine once a day only. The test for chlorine is not performed according to the test kit instructions. The water is not tested for alkalinity, combined chlorine, or cyanuric acid.
Correction: Perform water testing in accordance with ATCP 76.18(1).
Code ATCP 76.18(1)
-
Not serious
Action taken: Demonstrate proper water t
23d - NO RESPONSIBLE SUPERVISOR
No responsible supervisor is available. The pool is not meeting water testing requirements. The person in charge has not been trained on water testing.
Correction: The pool must be closed until a responsible supervisor is available to fulfill the responsibilities.
Code ATCP 76.21
-
Not serious
Action taken:
26a - PATRON LOAD - POOLS
The maximum patron load is not posted. The pool rule signage has a spot for writing patron which is blank.
Correction: Calculate and post the maximum patron load in compliance with ATCP 76.25(2).
Code ATCP 76.25(2)(a)
-
Not serious
Action taken: Most items found and provi
26q - FIRST AID KIT - SUPPLIES MISSING
Several items (cold pack, expired eye wash, gloves, resuscitation pocket face mask) are missing or are expired from the first aid kit.
Correction: Provide all the items listed in ATCP 76.27(1) in the first aid kit.
Code ATCP 76.27(1)
-
Not serious
Action taken: Blankets found in pool she
Corrected on site
26r - BLANKETS MISSING
2 durable blankets are not available in the pool area.
Correction: Provide 2 durable blankets in the pool area.
Code ATCP 76.27(1)
-
Not serious
Action taken:
26s - BIOHAZARD SAFETY KIT
No biohazard safety kit is located on the premises.
Correction: Provide a biohazard safety kit at the first aid station.
Code ATCP 76.27(2)
-
Not serious
Action taken: Repair prior to opening ne
29b - BASIN DEFECTS
(1) The pool basin is is exhibiting pitting and paint chipping. (2) ~ 20 blue tiles are missing from the vertical basin ledge.
Correction: Repair the pool basin so it is finished and easily cleanable.
Code ATCP 76.33(1)(a)
-
Not serious
Action taken:
29g - DRINKING FOUNTAIN
The drinking fountain is not functional.
Correction: Repair/clean the drinking fountain.
Code ATCP 76.33(1)(g)
-
Not serious
Action taken:
34d - POOL CLOSED SIGN
There is no sign on the premises that indicates that the pool is closed. Pool was closed due to inspection findings, a chain lock was used to close the fence.
Correction: Provide a sign that communicates to the public that the pool is closed.
Code ATCP 76.34(5)
-
Not serious
Other
Repeat
34e - VGBA COVERS
No documentation is available on site for VGBA main drain and/or equalizer covers showing make/model and replacement date. There is a carbon copy invoice in the pump room dated 5/2023 that suggests new drains were purchased and installed this season. The PIC informed that the drains were replaced at the start of this season and that the pump was replaced in the last 5 years.
Correction: Maintain documentation of VGBA covers for main drain and equalizers on site and available for review during inspection. Replace covers when lifespan is up.
Code ATCP 76.11(2)(b)
-
Not serious
Action taken:
-
Aug 24, 2021 Routine Inspection · No Reinspection Required
No violations cited.
-
Aug 23, 2019 Re-Inspection · No Reinspection Required
No violations cited.
-
Aug 21, 2019 Routine Inspection · Reinspection Required
No violations cited.
-
Jun 20, 2018 Routine Inspection · No Reinspection Required
No violations cited.
-
Jul 13, 2017 Re-Inspection · No Reinspection Required
No violations cited.
-
Jun 20, 2017 Pre-Inspection · No Reinspection Required
No violations cited.
Source: Public Health Madison & Dane County. History last read Oct 1, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.