4608 ROYAL, Eau Claire, WI 54701 · Eau Claire County

13cited violations
0serious tier
6inspections

Establishment

Type
Lodging (Hotel and Motel - 31 - 99 Rooms)
Inspected by
Eau Claire City-County Health Department
License / ID
HSAT-7QXFGW
Status
Permitted
Phone
(715) 583-8818
Official record
Eau Claire City-County Health Department inspection reports

Other public records for this business

Year by year

YearInspectionsViolationsSerious
2026110
2025130
2024370
2023120

Inspections

  1. Mar 27, 2026 Routine · 1 non-critical
    • Not serious Priority Foundation

      Fire rated doors - closed

      The fire rated door of laundry room is not maintained closed.

      Correction: Keep the fire rated door closed unless interconnected with fire alarm system.

      Code ATCP 72.18(9)(c)3.

  2. Apr 25, 2025 Routine · 3 non-critical, 1 repeat
    • Not serious Non-critical

      ROOM RATES POSTED

      Room rates not posted in sleeping rooms.

      Correction: Provide room rate information in each room.

      Code SS 97.638 (1)

    • Not serious Non-critical Corrected on site

      UTENSIL SANITIZATION-ICE BUCKETS

      Guest ice buckets are not being washed, rinsed and sanitized between guest periods.

      Correction: Guest ice buckets must be washed, rinsed and sanitized in an approved manner before being provided for use by a different guest. Usually liners are provided but hotel is out, so they will wash, rinse and sanitize buckets between each guest for now.

      Code [B] ATCP 72.11 (3)(a)

    • Not serious Non-critical Repeat Corrected on site

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated door to laundry room is propped open or are open at time of inspection.

      Correction: Except for fire doors on magnetic closures controlled by a central activation of the fire alarm system, fire doors must be self-closing and closed completely at all times. Fire door closed.

      Code [C] ATCP 72.14 (1)

  3. May 3, 2024 Re-inspection 2 · 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      PLUMBING CROSS-CONNECTIONS

      The following cross connection observed under the ice machine one of the drain lines is going directly into the catch cup.

      Correction: Provide an air gap or other approved backflow/backsiphonage protection device.

      Code [A] ATCP 72.10 (4)

    • Not serious Non-critical Repeat

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated door is propped open or are at time of inspection.

      Correction: Except for fire doors on magnetic closures controlled by a central activation of the fire alarm system, fire doors must be self-closing and closed completely at all times.

      Code [C] ATCP 72.14 (1)

  4. Apr 22, 2024 Routine · 3 non-critical, 1 repeat
    • Not serious Non-critical

      PLUMBING CROSS-CONNECTIONS

      The following cross connection observed under the ice machine one of the drain lines is going directly into the catch cup.

      Correction: Provide an air gap or other approved backflow/backsiphonage protection device.

      Code [A] ATCP 72.10 (4)

    • Not serious Non-critical Repeat

      CARBON MONOXIDE DETECTORS - REQUIREMENT

      A carbon monoxide detector is not provided in the lobby where there is a gas fire place and in the laundry room where there is a gas dryer.

      Correction: Provide carbon monoxide detectors in all required locations.

      Code [A] ATCP 72.145 (3)

    • Not serious Non-critical

      FIRE RATED DOORS – IMPROPERLY OPERATED

      Required fire rated door is propped open or are at time of inspection.

      Correction: Except for fire doors on magnetic closures controlled by a central activation of the fire alarm system, fire doors must be self-closing and closed completely at all times.

      Code [C] ATCP 72.14 (1)

  5. Feb 5, 2024 Re-inspection · 2 non-critical, 2 repeat
    • Not serious Non-critical Repeat

      CARBON MONOXIDE DETECTORS - REQUIREMENT

      There is no Carbon Monoxide detector at front area where gas fireplace is located.

      Correction: Provide carbon monoxide detectors in all required locations.

      Code [A] ATCP 72.145 (3)

    • Not serious Non-critical Repeat

      EXIT LIGHTING - PROVIDED

      Several exit lights near rooms 136, 146 are out.

      Correction: Provide lighting for exit lights. Exit signs must be illuminated at all times. Check all exit lights and keep a log of checks.

      Code [R] ATCP 72.14 (1)

  6. Jun 20, 2023 Routine · 2 non-critical, 1 repeat
    • Not serious Non-critical

      CARBON MONOXIDE DETECTORS - REQUIREMENT

      There is no Carbon Monoxide detector at front area where gas fireplace is located.

      Correction: Provide carbon monoxide detectors in all required locations.

      Code [A] ATCP 72.145 (3)

    • Not serious Non-critical Repeat

      EXIT LIGHTING - PROVIDED

      Several exit lights near rooms 136, 146 are out.

      Correction: Provide lighting for exit lights. Exit signs must be illuminated at all times. Check all exit lights and keep a log of checks.

      Code [R] ATCP 72.14 (1)

Source: Eau Claire City-County Health Department. History last read Oct 15, 2026. Violation text is the inspector's wording. “Serious” is the source's own top tier. About this data.